Mp2000 air conditioners – Dell MP2000 Manuale d'uso
Pagina 99
99
RC GROUP - 149_ItEn.0102
MP2000 AIR CONDITIONERS
Software per condizionatori d'aria a pompa di calore e Roof Top • EPROM CPX....
• Software for heat pump air conditioners and Roof Top
CONFIGURAZIONE UNITA’
UNIT CONFIGURATION
Premere per 4 secondi
HOME
1
PRG
3
Press for 4 seconds
quindi inserire Password
than digit Password
ON DISPLAY
TIPO DI SET
SET TYPE
DEFAULT
RANGE
SYMBOL
Clock board
scheda orologio
clock board
N
N - Y
—
Supervisor code
codice supervisione
supervisor code
0
00
÷
99
—
Supervisor mode
modo supervisore
supervisor mode
R
R - W
—
Probe selction
selezione sonda
probe selection
Supply air temp.
temperatura mandata aria
supply air temperature
N
N - Y
—
Outl. water temp.
uscita acqua condensatore
outlet condenser water
N
N - Y
—
Ext. air temp.
temperatura aria esterna
external air temperature
N
N - Y
—
Room humidity
umidità ambiente
room humidity
N
N - Y
—
Integr. humidif.
umidificatore integrato (*)
integrated humidifier (*)
N
N - Y
—
High pressure probe present
presenza sonda di alta pressione
high pressure probe present
N
N - Y
—
Min. scale
scala minima pressione
min pressure scale
0 kPa
±
500 kPa
—
Max. scale
scala massima pressione
max pressure scale
3000 kPa
0
÷
5000 kPa
—
Low pressure probe min. scale
scala minima sonda di bassa pressione
low pressure probe min. scale
0 kPa
0
÷
500 kPa
—
Low pressure probe max. scale
scala massima sonda di bassa pressione
low pressure probe max. scale
1500 kPa
0
÷
1500 kPa
—
Analog input 7 board 1 used like
ingr. analogico 7 board 1 usato come (*)
analog input 7 boad 1 used like (*) not used
not used
—
voltage line
line current
ext. compens.
(*) con “Integr. humidif. Y” è utilizzato in
(*) with “Integr. humidif. Y” it is automatically
automatico per corrente umidificatore e
used for humidifier current measurement
questo set non viene visualizzato.
and this set is not displayed
Analog input 7 board 2 used like
ingr. analogico 7 board 2 usato come
analog input 7 boad 2 used like
not used
not used
—
voltage line
line current
ext. compens.
Analog input 8 board 2 used like
ingr.analogico 8 board 2 usato come
analog input 8 board 2 used like
not used
not used
—
voltage line
line current
ext. compens.
Voltage line max scale
scala massima tensione linea
max voltage line scale
600 V
0
÷
700 V
—
Line current max scale
scala massima corrente linea
max line current scale
100 A
0
÷
700 A
—
Configuration
configurazione unità
unit configuration
2 compr. - 2 circ. - 2 board
—
—
2 compr. - 1 circ. - 2 board
—
—
2 compr. - 1 circ. - 1 board
—
—
1 compr. - 2 board
—
—
1 compr. - 1 board
—
—
Enable heater
abilitazione riscaldamento
enable heater
N
Y - N
—
Condenser type
tipo di condensatore
condenser type
AIR
AIR - WATER
—
Unloader comp.
parzializzazione compressore
unloader compressor
N
N - Y
—
En. double speed
compressore doppia velocità
double speed compressor
N
N - Y
—
Analog out.1 board 1
uscita analogica xY0 board 1
analog output xY0 board 1
cooling valve
cooling valve
xY0
heating valve
not used
cool valve +dehumid
Analog out.1 board 2
uscita analogica xY0 board 2
analog output xY0 board 2
cooling valve
cooling valve
xY0
heating valve
not used
cool valve +dehumid