RC GROUP - 149_ItEn.0102
CONFIGURAZIONE UNITA’
UNIT CONFIGURATION
Premere per 4 secondi
HOME
1
PRG
3
Press for 4 seconds
quindi inserire Password
than digit Password
ON DISPLAY
TIPO DI SET
SET TYPE
DEFAULT
RANGE
SYMBOL
Clock board
scheda orologio
clock board
N
N - Y
—
Supervisor code
codice supervisione
supervisor code
0
00
÷
99
—
Supervisor mode
modo supervisore
supervisor mode
R
R - R/W
—
Probe selction
selezione sonda
probe selection
Supply air temp.
temperatura mandata aria
supply air temperature
N
N - Y
—
Outl. water temp.
uscita acqua refrigerata
outlet water temperature
N
N - Y
—
Ext. air temp.
temperatura aria esterna
external air temperature
N
N - Y
—
Inlet water temp.
ingresso acqua refrigerata
inlet water temperature
N
N - Y
—
Room humidity
umidità ambiente
room humidity
N
N - Y
—
Integr. humidif.
umidificatore integrato (*)
integrated humidifier (*)
N
N - Y
—
Pressure probe present
presenza sonda di pressione
pressure probe present
N
N - Y
—
Min. scale
scala minima pressione
min pressure scale
0 kPa
±
500 kPa
—
Max. scale
scala massima pressione
max pressure scale
3000 kPa
0
÷
5000 kPa
—
Analog input 7 used like
ingresso analogico 7 usato come (*)
analog input 7 used like (*)
not used
not used
—
voltage line
line current
ext. compens.
(*) con “Integr. humidif. Y” è utilizzato in
(*) with “Integr. humidif. Y” it is automatically
automatico per corrente umidificatore e
used for humidifier current measurement
questo set non viene visualizzato.
and this set is not displayed
Analog input 8 used like
ingresso analogico 8 usato come
analog input 8 used like
not used
not used
—
voltage line
line current
ext. compens.
conductivity
Voltage line max scale
scala massima tensione linea
max voltage line scale
600 V
0
÷
700 V
—
Line current max scale
scala massima corrente linea
max line current scale
100 A
0
÷
700 A
—
Configuration
configurazione unità
unit configuration
2 compr. - 2 circ. - 2 board
—
—
2 compr. - 1 circ. - 2 board
—
—
2 compr. - 1 circ. - 1 board
—
—
1 compr. - 2 board
—
—
1 compr. - 1 board
—
—
0 compr. - 2 board
—
—
0 compr. - 1 board
—
—
Unit no. present
numero unità presenti in rete
units no. present in network
1
1 - 2 - 3 - 4
—
Heater no.
numero stati riscaldamento elettrico
heaters step number
0
0 - 1 - 2 - binary
—
Unloader comp.
parzializzazione compressore
unloader compressor
N
N - Y
—
En. double speed
compressore doppia velocità
double speed compressor
N
N - Y
—
Analog input 7 board 2 used as
ingresso analogico 7 board 2 usato come
analog input 7 board 2 used as
Line current
corrente di linea
line current
N
N - Y
—
Max. scale
scala massima corrente
max current scale
100 A
0
÷
500 A
—
Analog input 8 board 2 used as
ingresso analogico 8 board 2 usato come
analog input 8 board 2 used as
Voltage line
voltaggio di linea
voltage line
N
N - Y
—
Max. scale
scala massima tensione
max voltage scale
600 V
0
÷
700 V
—
Analog output 1
uscita analogica xY0
analog output xY0
cooling valve
cooling valve
xY0
heating used
not used
cooling + freecooling
cool valve +dehumid
Cooling fl. valve
valvola 3 punti raffreddamento ad acqua
cooling floating valve (water)
N
N - Y
—
Heating fl. valve
valvola 3 punti riscaldamento ad acqua
heating floating valve (water)
N
N - Y
—
MP2000 AIR CONDITIONERS
Software per condizionatori d'aria • EPROM CZX....
• Software for air conditioners