Using the system uk – FBT 37483_VAIE2550_manual1.pdf Manuale d'uso

Pagina 96

Advertising
background image

8-10

USING THE SYSTEM

UK

8.5.1 FAULTS

For viewing the failed components

Six groups are listed, with a generic indication of the fault condition.

From this panel it is possible to reset the beep (see point 8.5.1.1).

The categories of failed parts and generic signalling of their states
are shown in the table below.
Press the associated numerical key (1-6) to select the sub-panel and
view the details of the failure, as illustrated under points 8.5.1.3 to
8.5.1.8 below
or
Press ESC to return to the INSPECTION panel.

8.5.1.1 Manual resetting of the acoustic signal (beep)

by acknowledging the failure

When the built-in monitoring system of the VAIE 2250 detects a
new fault, the acoustic signal (beep) is automatically activated and
sounded at any and all emergency units and, in a 12-zone system,
also on the remote VAIE 2250.

To reset the beep, access the “FAULTS” menu showing the list of six
groups of diagnostic signals, of which at least one will show a FAULT
condition. To do this, follow the path:

HOME/INSPECTION/report> FAULTS

Press the RESET key

The beep will be reset on all the units within the system and on
any remote emergency units. The FAULT LED will remain active to
indicate that a “Fault Condition” continues to exist. If the Fault LED is
steady ON, it will be possible to identify the faulty item of equipment
by accessing the options of the FAULT menu (see points 8.5.1.3 to
8.5.1.8) to find the fault. If the Fault LED is flashing, this means that
the fault has to do with the remote VAIE 2250 unit, in which case
you should access the FAULTS menu proceeding via the other VAIE
2250 unit.

After resetting the beep, it will be possible to return to the MUSIC
panel by pressing repeatedly the ESC key.

8.5.1.2 Automatic resetting of the acoustic signal (beep) following clearing of a failure
If the cause of a failure is cleared before the beep is reset manually, the VAIE 2250 will reset the beep automatically, extinguish the
FAULT LED and indicate RES (RESOLVED) in the label of the part that had FAILED. The RESOLVED signal will be stored until a
MANUAL RESET of the failure signal is carried out from the FAULTS panel via the OPERATOR menu.

Label

Diagnostic category

See panel

Cause

1-Loudspk Line

Loudspeaker lines

LOUDSPK. LINE FAULT

ALL

OK

No faults

2-Voice Alarms

VES emergency sources

VOICE ALARMS FAULT

3-Amplifiers

Power amplifiers
Ground fault loudspeaker lines

AMPLIFIER FAULTS

4-Power Supply

Primary and secondary power
supplies
Management memory display

POWER SUPPLY FAULTS

FAULT

At least 1 fault detected
and on-going

5-Control Input

Local input contacts

CONTROL INPUT FAULT

RES

At least 1 fault cleared and
no on-going faults

6-Communication

VAIE 2250 internal data
communication

COMMUNICATION FAULT