8-28

USING THE SYSTEM

UK

8.7 < CONFIGURATION > MENU
Panel for selecting options pertaining to personnel specifically
trained and authorised to use the advanced system functions
and to modify the configuration parameters for starting and
maintaining the system. A password for accessing these
functions may be added.

The options of the CONFIGURATION Menu enable the following management panels to be accessed:

8.7.1 IMP.

ACQUISITION panel (via the acquire > IMPEDANCE option)

For acquiring and storing the impedance values of the speaker unit lines, which is necessary for system initialisation and diagnostics.

8.7.2 SET

TOLERANCE panel (via the set > IMP. TOLERANCE option)

For setting the tolerance applicable to the line impedance. When the diagnostic system detects impedance that is out of tolerance, a “Fault
Warning Condition” is activated.

8.7.3 MESSAGES panel (via the set > MESSAGES option)
Panel for transferring the audio files for the Alert and Evacuation messages from an external Flash Memory Stick to the resident memory of
the VAIE 2250, for future use in “Voice Alarm” emergency conditions.

8.7.4 ALARM

LEVEL

panel (via the set > ALARM LEVEL option)

Panel for adjusting the output volume of the VES sources: Emergency Microphones and Alarm Messages.

8.7.5 AMPLIFIER

MODE

panel (via the set > AMPLIFIER MODE option)

For setting the system operating mode in relation to the presence or otherwise of an external amplifier.

8.7.6 IP

ADDRESS

panel (via the IP address option)

For setting the networking parameters for accessing the system functions via a Web Server.

8.7.7 PASSWORD

panel (via the Password option)

Panel for enabling, disabling and customising the password for accessing the system service levels.

< SERVICE >
Connection to the SERVICE menu for technical personnel having the necessary password. It is used to change the operating parameters
of the VAIE 2250 system, up-dating the firmware and servicing it.
Note: The settings of the Service Menu are not covered in this Manual.

If an access password has been enabled, at the time of configuration
the CONFIGURATION ACCESS panel will be displayed:
- enter the four-digit password then press OK to proceed, or
- press ESC to return to the MAIN page.

The default password is 3333.

Once the CONFIGURATION Menu is accessed, all the options
illustrated earlier in the “AUDIO SETTING”, “INSPECTION” and
“CONFIGURATION” menus will be shown, as well as the following
new options specific to the CONFIGURATION menu.
Turn the knob to browse through the options listed:
acquire > IMPEDANCE
set > IMP. TOLLERANCE
• ->-
• ->-
set > MESSAGES
set > ALARM LEVEL
• ->-
set > AMPLIFIER MODE
• ->-
• ->-
IP address
Password
< SERVICE >
Exit > Logout

Press OK to select the required item,

or

- press ESC to return to the MUSIC panel.
- press MENU to return to the MAIN page.

The characteristics of the specific panels of the CONFIGURATION Menu are illustrated below. For the other available options, refer to the
appropriate sections above. At the end of the setup, log out by selecting “Exit> Logout” as described in paragraph 8.6.8.