8-2

USING THE SYSTEM

UK

8.2 INITIALISING THE SYSTEM

Password
From the MAIN page, select the CONFIGURATION menu and press OK to confirm your choice. If the restriction calling for access with
a password has been enabled, the “CONFIGURATION ACCESS” screen will appear: enter the 4-digit code of the password, then press
OK to confirm (the default password is 3333, see point 8.7).

Resetting the BEEP
Failure signals may occur during the initialisation procedure due to the differences between the configuration of the system as connected
and the default settings. To reset the acoustic signal (beep), access the “Report> FAULT” menu and press the RESET key. For details,
see point 8.5.1.1.
o

Path: HOME / CONFIGURATION / report> FAULT (press the RESET key)

External amplifier
Configure the VAIE 2250 with or without an external amplifier. For details see “AMPLIFIER MODE” (see point 8.7.5).
o

Path: HOME / CONFIGURATION /

set> AMPLIFIER MODE

Acquisition of impedances
From the MUSIC menu, set all the outputs with music “OFF”. For details, see “MUSIC menu” (see point 8.3.4).
Acquire the new loading impedances of the loudspeaker lines, as indicated under “IMP. ACQUISITION” and enable the test by setting
the measurement tolerances.
o

Path: HOME / CONFIGURATION /

acquire> IMPEDANCE / IMP. ACQUISITION (press the OK key)

o

Path: HOME / CONFIGURATION /

set> TOLLERANCE / SET TOLLERANCE

Diagnostics for 24 VDC power supply
If the auxiliary 24 VDC power supply has been connected, enable the diagnostic test by setting “24 VDC P.S. ON”, as illustrated under
“BACKGROUND TEST” (see point 8.6.3.3).
o

Path: HOME / CONFIGURATION /

set> BACKGROUND TEST / 4-Power supply

Emergency messages
Load the *.WAV files for the ALERT and EVAC messages in the resident memory of the VAIE 2250, as illustrated under “MESSAGES”
(see point 8.7.3).
o

Path: HOME / CONFIGURATION /

set> MESSAGES

Input contacts
Based on the provisions of the Emergency and Evacuation Plan (EEP), programme the input contacts connected to the external peripheral
unit suitably. For details see under “CONTROL INPUTS” (see point 8.6.1).
o

Path: HOME / CONFIGURATION /

set> CONTROL INPUTS

Output contacts
Based on the provisions, if any, relating to the specific system, programme the output contacts connected to the external peripheral units
suitably. For details see under “CONTROL OUTPUT” (see point 8.6.2).
o

Path: HOME / CONFIGURATION /

set> CONTROL OUTPUT

Volume control
Adjust the output volume of the VES sources suitably so as to ensure that the messages are as intelligible as possible. The level set will
be used for ”Voice Alarm Conditions” and will be the same for all the zones. To adjust the volume of the Emergency Microphone and of
the ALERT and EVAC messages, follow the instructions provided under “ALARM LEVEL” (see point 8.7.4).
o

Path: HOME / CONFIGURATION /

set> ALARM LEVEL

Resetting failures
Upon completion of the system configuration, the reports concerning failure that have been stored and cleared should be cancelled
(RESOLVED). A FAULT RESET should therefore be carried out as indicated under “FAULTS” (see point 8.6.6.1).
o

Path: HOME / CONFIGURATION /

report> FAULT, access the subpanels for viewing failures

After initialising the system
After completing the system initialisation procedure, LOG OUT in order to reinstate any access restrictions associated with passwords
(see point 8.6.8).
o

Path: HOME / CONFIGURATION /

Exit> Logout (press the OK key).