8-24

USING THE SYSTEM

UK

8.6.4.1a KEYS UNIT # SETTING

Configuring the keys of an emergency unit

Panel for viewing the parameters associated with the keys of a
microphone station and for changing their values.

From the “EMERGENCY UNIT CONFIG” panel, press the MENU
key. The following panel, concerning the address chosen for the
microphone station, will appear.

It is possible to programme the PTT and AUX keys and, only for the
FMD 2012, each of the 12 selection keys in order to alter the manner
of activation of the 12 zone-selection keys so as to enable selection of
groups of zones (keys 1 to 12 and the PTT key) or to create a specific
combination of messages for the various different zones (AUX key).

The default configurations of the keys are as follows:

Selection key 1 (Key 1): for selecting zone 1
Selection key 2 (Key 2): for selecting zone 2
Selection key 3 (Key 3): for selecting zone 3
..\..
Selection key 12 (Key 12): for selecting zone 12
PTT key: selection of all zones from 1 to 12
AUX key: no effect (NONE)

To programme the keys, it is necessary to select the key in question and then to set the required parameter for each zone.

Programming keys 1 to 12 and the PTT key to create a multiple zone selection:
With the cursor with the black background positioned on the “Key select” line, select the key to be programmed by turning the +/- knob to
run through the fields from 1 to 12 and PTT.

- Press the OK key.

The cursor will move to the bottom zone-selection panel.
- Move the +/- cursor and position it on the zone with the parameter to be altered.
- Press the MENU key cyclically

to set the following:
> NONE: zone not selected
> SEL: zone selected

Programming the AUX key to create a specific combination of messages for various different zones:
With the cursor with a black background positioned on the “Key select” line, turn the +/- knob to select the AUX key.

- Press the OK key.

The cursor will move to the bottom zone-selection panel.
- Move the +/- cursor and position it on the zone with the parameter to be altered.
- Press one of the following keys: MENU, ALERT or EVAC

to set the following:
> NONE: zone not activated (MENU)
> ALERT: zone with pre-recorded WARNING message
> EVAC: zone with pre-recorded EVACUATION message.

N.B.: The AUX key is operational only in Manual Emergency conditions.