Using the system uk – FBT 37483_VAIE2550_manual1.pdf Manuale d'uso

Pagina 111

Advertising
background image

8-25

USING THE SYSTEM

UK

8.6.5 DISABLEMENT

Disabling the emergency zones

Panel for setting the “Disablement Condition” for each output zone.

Application of the “Disablement Condition” refers to the functions
envisaged for a “Voice Alarm Condition”, and does not affect the
system in terms of its usual activities in a “Quiescent Condition”.
Thus, if “Disablement” is set for at least one output zone, the
dedicated “DIS” LED will in any case light up to show that there is a
generic “Disablement Condition” within the system.

• Configuring “Disablement” for the output zones:
Press each numerical zone key (1 - 6) to associate the required
setting with that zone, choosing one of the following options:

>

VOICE: Zone not Disabled. The output zone will broadcast

Alarm messages as called for in case of an Emergency or
Manual Alarm.

>

DIS: Zone Disabled. The output zone will not broadcast any

Alarm messages, even if called for by the Input Programming.

Note: The display will show the programming that has been set.

Upon completing configuration, press ESC to return to the
OPERATOR menu.

The zone in a “Disablement Condition” will not be affected by voice or pre-recorded emergency messages, regardless of how the input
contacts (CONTROL INPUTS) are programmed and of how the Operator proceeds during a Manual Emergency procedure.

The “disabled” zone will therefore not be affected by a “Voice Alarm Condition” of the system. The status label of each zone will signal a possible
“Disablement Condition” set with a priority higher than the signals called for by a “Voice Alarm Condition” and a “Fault Warning Condition”.
During a Manual Emergency procedure, it will not be possible to select the disabled zone for sending alarm messages.

For details consult point 8.9.