8-20

USING THE SYSTEM

UK

8.6.2 CONTROL

OUTPUT

Local output contacts

Panel for programming the six local output contacts (CONTROL
OUTPUTS) and the two service relays, RELAY 1 and RELAY 2.
For each output it is possible to choose the idle status and to
associate the system status event leading to its activation.

On completing the programming, press ESC to return to the
OPERATOR menu.

8.6.2.1 Programming the output contacts

Note: The display will show the programming that has been set.

Choosing the output to be programmed:
Hold the OUT key (1) down and turn the +/- knob to select the number of the output from among the following:
>

OPEN COL. outputs from 1 to 6: open-collector CONTROL OUTPUTS.

>

RELAY AUX outputs from 1 to 2: RELAY 1 and RELAY 2 OUTPUTS.

Programming an output to associate it with a system event:
Hold the MODE key (2) down and turn the +/- knob to select one of the following options:

>

USER MODE: unprogrammed output.

>

Override Z1 - Z6: seizing of the zone indicated by a PA Source or a VES source.

>

Voice Alarm State: system currently in a generic “Voice Alarm Condition”.

> Manual Voice Alarm: system currently in a “Voice Alarm Condition” activated by a Manual Emergency (Operator) procedure.

>

Automatic Voice Alarm: system currently in a “Voice Alarm Condition” activated by an Automatic Emergency (Control Input)
procedure.

>

Z1-

Z6

Voice Alarm: system currently in a “Voice Alarm Condition” affecting the output zone indicated.

>

Evac Message Playing: system currently in a “Voice Alarm Condition” with the pre-recorded Evac message being played out.

>

Alert Message Playing: system currently in a “Voice Alarm Condition” with the pre-recorded Alert message being played out.

>

Disablement Condition: currently in a “Disablement Condition”.

>

General Fault: currently in a generic “Fault Warning Condition”.

>

Fault - Loudspk. Line: at least one speaker line currently in a “Fault Warning Condition”.

> Fault - Voice Alarm: at least one VES source currently in a “Fault Warning Condition”.

>

Fault - Amplifier: at least one amplifier currently in a “Fault Warning Condition”.

>

Fault - Main Power: main 2330 VAC power supply currently in a “Fault Warning Condition”.

>

Fault - 24 VDC: secondary 24 VDC currently in a “Fault Warning Condition”.

>

Fault - Control Input: at least one local input contact currently in a “Fault Warning Condition”.

>

Fault - Emerg. Unit: at least one emergency microphone station currently in a “Fault Warning Condition”.

>

Fault Line Z1 - Z6: one of the speaker lines pertaining to the zone indicated currently in a “Fault Warning Condition”.

>

Reply Input 1-8: the input contact indicated is in an active condition. This also applies to inputs that are not programmed or that

are inhibited by a higher priority.

> Reply any Input: any input contact is in an active condition. This also applies to inputs that are not operational or that are inhibited

by a higher priority.

Choice of the idle condition of an output with regard to the activating event (excluding the USER MODE):
Press the STATE key (6) to select:
>

Normal State OFF: output de-activated if the event is not active.

>

Normal State ON: output active if the event is not active.

Programming of the output contact to signal a System fault (System CPU Fault):
The RELAY 2 output can also be programmed to signal a “System fault” detected by the watchdog system.
After selecting the RELAY 2 output:

• Press W-D key (5) to select:

> watch dog OFF
for an output not programmed to signal System faults, or

> watch dog ON
for an output programmed to signal System faults.

Note: If the output is programmed as “watchdog ON”, the idle condition of the output can only be “Normal State OFF”.