8.6.3.4 COMMUNICATION

TEST

Setting the test for internal data

communication
Panel for enabling and disabling testing applied to communication
data between internal sections of VAIE 2250.

• Press the appropriate numerical key to enable or disable the

diagnostic test

> 1-IC2 line:

on (test enabled) - off (test disabled)

> 2-Audio SPI line:

on (test enabled) - off (test disabled)

> 3-Relay SPI line:

on (test enabled) - off (test disabled)

8.6.4 EMERGENCY

UNITS

Managing the addresses of the emergency units

Panel for displaying, acquiring and selecting the addresses of the
emergency units.

First of all, it must be said that it is essential for each station to have
its own univocal address. It is possible to connect up to seven FMD
2001 or FMD 2012 stations to a VAIE 2250 unit. These stations will
have the addresses numbered from 1 to 7. The default address of all
microphone stations is 1. At the time of connecting each of them to
the EMERGENCY UNIT port, the system automatically acquires its
address and enables its diagnosis.

Once all the stations have been connected to the system, the EMERGENCY UNIT panel displays the stations that have been acquired,
showing their respective addresses under the line of the corresponding model (FMD 2001 or FMD 2012).

Up-dating of the system configuration
If a station acquired by the system is disconnected or is given a different address, the VAIE 2250 signals a fault.
To up-date the memory on the basis of the new condition, press the RESET key. Any addresses of stations that are not present will be
erased, keeping only those that are detected.

Configuring the microphone station
Turn the +/- knob to position the cursor on the address of the station concerned (when an address is free, the cursor is shown on the two
lines of both models).

Press OK,

The “EMERGENCY UNIT CONFIG” panel of the selected station will appear.
Consult point 8.6.4 “EMERGENCY UNIT CONFIG” for the settings of the single bases.
To return to the previous level, press ESC.

In order to avoid lengthy conflicts between stations, it is recommended that the stations should be added one at a time, setting each with
a new free address.
N.B.: With regard to setting of the addresses, refer to the manual of the microphone station, under the heading “SETTINGS>Address”.