13.3 Electric panel troubleshooting table

All maintenance and repair operations must be performed by qualified

personnel.

Before servicing the set, disconnect the power supply and make sure there is no

pressure in the hydraulic components.

Problem

Cause

Solution

The panels do not

switch on

1. No mains power supply

Power the unit

2. Blown fuse inside panel

Replace fuse

3. Overload protection

triggered (only for jockey

pump panels)

Rearm the protection

The main electric

pump does not

start

1. No mains power supply

Power the unit

2. Key-operated selector switch

set to “0”

Set key-operated selector switch

to “AUTO” or “MAN”

3. Blown fuse

Replace the fuse

4. Incorrect pressure switch

calibration

Recalibrate the pressure switch

The electric jockey

pump does not

start

1. No mains power supply

Power the unit

2. Blown fuse

Replace the fuse

3. Overload protection

triggered

Rearm the protection

4. Faulty pressure switch

Replace the pressure switch

5. Pressure switch not

connected

Connect the pressure switch

6. Incorrect pressure switch

calibration

Recalibrate the pressure switch

7. Tank liquid level is too low

Fill the primary water supply tank

or adjust the sensitivity of the

sensors

8. Electric sensors not

connected

Connect the electric sensors

9. No jumper between

terminals 3-4

Insert the jumper

The jockey pump

does not stop

1. Faulty pressure switch

Replace the pressure switch

2. Incorrect pressure switch

calibration

Recalibrate the pressure switch

3. Faulty electronic control

board

Replace the electronic board or

calibrate the timers

Self-test failed

1. Pump running pressure

switch faulty

Replace the pressure switch

Pump – motor coupling

damaged

Replace the coupling and realign

the pump – motor

2. Faulty electric motor

Replace the motor