11. Disposal

Proceed in compliance with local codes and regulations pertaining to disposal of waste,

including packaging materials.

12. Specifications

For sets with diesel pump, see also the handbook supplied with the diesel

pump.

Data refer to standard-design product.

Voltage rating

1 x 230V +/-10%, 50Hz (Single-phase)

3 x 400V +/-10%, 50Hz (Three-phase)

Current rating

See rating plate on electric panel

Protection class

Electric pump IP55

Electric panel IP54

Pressure switch IP54

Sound emission level

electric pump set

50Hz 2900

rpm

LpA (dB±2)

P2 (kW)

1P

2P

3P

4P

2.2

<70

<70

<70

<71

3

<70

<70

71

72

4

<70

70

72

73

5.5

<70

71

73

74

7.5

<70

72

74

75

11

73

76

78

79

15

75

78

80

81

18.5

75

78

80

81

22

75

78

80

81

Liquid temperature

+4 °C to + 40°C

Ambient temperature

+4 °C to + 40°C

Installation

Indoor, protected from the weather.

Away from heat sources.

Max 1000 m ASL.

Operating pressure

Max 8 bar, 10 bar, 16 bar. Depending on the type of

pump ( see pump handbook).

Minimum suction pressure

According to NPSH curve with a margin of at least 0.5

m for air-free water.

Maximum suction pressure

Make sure the inlet pressure plus the closed delivery pressure

does not exceed the maximum operating pressure.

Electric panel

Max power: see electric panel’s rating plate

Auxiliary voltage 12/24Vac

See diagram attached to panel.

Pumps

See pump instructions manual

Tanks

See tank instructions manual. If installed, they may limit

the operating temperature and pressure

Starts per hour

See pump instructions manual

WARNING