Xylem GEN series firefighting booster sets Manuale d'uso

Pagina 37

Advertising
background image

en

37

Pump on demand and start failure
In manual mode, the pump cannot be stared via a request from the pressure switch; a start

failure signal is activated.

1 - POWER LINE ON, green LED On
3 - PUMP ON DEMAND, yellow LED On
5 - START FAILURE, yellow LED On

DISABLED OPERATING MODE

Key-operated selector switch in automatic “0” position.

This disables the operation of the pump.


-

If the key-operated selector switch is set to the DISABLED “0” position, the motor

cannot be started either from the pressure switch or the keypanel. If the motor is already

running, it stops.

CONTROL TERMINALS, TERMINAL BOARD INSIDE CONTROL PANEL
Inside the electric service pump control panel there are dry contacts available for transmission

of the following alarm signals to the control room:

- Pump on demand

- Start failure

- Power line on

- Motor running.

Connection of the alarms and optional visual and audible signals to these contacts is the

installer’s responsibility. A separate power source from the one supplying the panel must be

utilized.

Optional accessories

For the connections, refer to the documentation attached to the electric panel.

In addition to the dry contacts, which are supplied as standard, an optional kit for relay of the

following signals is also available:

-

1: Start failure

-

2: Pump running

-

3: Pump on demand

-

4: Selector switch in automatic “AUTO” position

-

5: Selector switch in non-automatic “MAN” or “0” position

-

6: Power line on

WARNING