Riello UPS MultiCOM 301/302 Manuale d'uso
Pagina 40

- ENGLISH -
- 40 -
REGISTER
(1)
STS/ATS - MEASUREMENTS
UNIT
NUMBER
ADDRESS
9
8
Source S1 L1-N input Voltage
V
10
9
Source S1 L2-N input Voltage
V
11
10
Source S1 L3-N input Voltage
V
12
11
Source S1 input Frequency
0.1*Hz
13
12
Source S2 L1-N input Voltage
V
14
13
Source S2 L2-N input Voltage
V
15
14
Source S2 L3-N input Voltage
V
16
15
Source S2 input Frequency
0.1*Hz
17
16
L1 Output Load
%
18
17
L2 Output Load
%
19
18
L3 Output Load
%
20
19
L1 Output Load Current
0.1*A
21
20
L2 Output Load Current
0.1*A
22
21
L3 Output Load Current
0.1*A
23
22
Cabinet inside Temperature
°C
24
23
Synchron angle
25 72
24 71
Reserved
(1)
The register number n must be addressed n-1 in the data packet
REGISTER
(1)
STS/ATS - NOMINAL DATA
UNIT
NUMBER
ADDRESS
73
72
Nominal Current
A
74
73
Nominal Voltage
V
75
74
Nominal Frequency
0.1*Hz
80 112
79 111
(1)
The register number n must be addressed n-1 in the data packet