Odici comandi – Riello UPS MultiCOM 301/302 Manuale d'uso
Pagina 17

- ITALIANO -
- 17 -
REGISTRO
(1)
FLAG SPECIALI (UPS SERIE SENTR)
(2)
UNITÀ
NUMERO
INDIRIZZO
121
120
Byte 1 of “s = xx..” code / Byte 2 of “s = ..xx” code
Flag
122
121
Byte 1 of “c = xx..” code / Byte 2 of “c = ..xx” code
Flag
123
122
Byte 1 of “b = xx..” code / Byte 2 of “b = ..xx” code
Flag
124
123
Byte 1 of “r = xx..-..” code / Byte 2 of “r = ..xx-..” code
Flag
125
124
Byte 3 of “r = ....-xx” code / Byte 1 of “i = xx..-..” code
Flag
126
125
Byte 2 of “i = ..xx-..” code / Byte 3 of “i = ....-xx” code
Flag
127
126
Byte 1 of “a = xx..-....” code / Byte 2 of “a = ..xx-....” code
Flag
128
127
Byte 3 of “a = ....-xx..” code / Byte 4 of “a = ....-..xx” code
Flag
REGISTRO
(1)
DATI DEL MultiCOM
UNITÀ
NUMERO
INDIRIZZO
129
128
Versione firmware
Intero*100
130ч131
129ч130
(1)
Il registro numero n deve essere indirizzato n-1 nel pacchetto dati
(2)
Fare riferimento al manuale dell’UPS per decodificare questi registri
UPS:
C
ODICI COMANDI
CODICE
COMANDO
1
(0x0001)
Spegnimento programmato (Shutdown)
2
(0x0002)
Spegnimento e riaccensione (Shutdown and restore)
3
(0x0003)
Cancellazione comandi codice 1, 2, 12
12 (0x000C)
UPS da bypass
20 (0x0014)
Test di batteria
22 (0x0016)
Test pannello LED