FRONIUS ECO

25.0-3-S

27.5-3-S

Input data
MPP voltage range

580 - 850 V DC

580 - 850 V DC

Max. input voltage
(at 1,000 W/m²/ -10 °C in an open circuit)

1000 V DC

Min. input voltage

580 V DC

Max. input current

44.2 A

47.7 A

Max. short circuit current of the solar modules
(I

SC PV

)

66.3 A

71.6 A

Max. feedback current

4)

48 A (RMS)

5)

Output data
Nominal output power (P

nom

)

25000 W

27000 W

Max. output power

25000 W

27000 W

Nominal grid voltage

3 ~ NPE 220/230 V / 380/400 V

Min. grid voltage

150 V / 260 V

Max. grid voltage

275 V / 477 V

Nominal output current at 220 / 230 V

37.9 / 36.2 A

40.9 / 39.1 A

Max. output current

38 A

41 A

Nominal frequency

50 / 60 Hz

1)

Total harmonic distortion

< 2 %

Power factor cos phi

0 - 1 ind./cap.

2)

Max. output fault current per period

A/ms

General data
Maximum efficiency

98 %

European efficiency U

DCmin

/ U

DCnom

/ U

DCmax

97.99 / 97.47 / 97.07 %

97.98 / 97.59 / 97.19 %

Overnight self-consumption

W & VA

Cooling system

Controlled forced-air ventilation

Degree of protection

IP 66

Dimensions h x w x d

725 x 510 x 225 mm

Weight (light version)

35.69 kg (35.44 kg)

Permissible ambient temperature

-25 °C - +60 °C

Permitted humidity

0 - 100 %

EMC device class

Q

Overvoltage category DC / AC

2 / 3

Pollution level

2

Noise emission

dB(A) (ref. 1pW)

Protection devices
DC insulation measurement

Integrated

Response to DC overload

Operating point shift, power limitation

DC disconnector

Integrated

DC overvoltage protection

Integrated

RCMU

Integrated