Fronius Symo x.x-3-S Manuale d'uso

Pagina 48

Advertising
background image

46

*) If the status code is displayed all the time: notify a Fronius-trained service engineer

**) If this status code keeps recurring, contact your system engineer

447

Insulation fault

The inverter is not feeding
any energy into the grid.

*)

448

Neutral conductor not connected

450

Guard cannot be found

451

Memory error detected

The inverter will automati-
cally attempt to connect
again and, if possible, will
resume feeding energy into
the grid

*)

452

Communication error between the pro-
cessors

453

Grid voltage and power stage set are in-
compatible

454

Grid frequency and power stage set are
incompatible

456

Anti-islanding function is no longer im-
plemented correctly

457

Grid relay is sticking or the neutral con-
ductor ground voltage is too high

The inverter is not feeding
any energy into the grid.

Check the grounding
(the neutral conductor
ground voltage must be
less than 30 V), *)

458

Error when recording measuring signal

The inverter is not feeding
any energy into the grid.

*)

459

Error when recording the measuring sig-
nal for the insulation test

460

Reference voltage source for the digital
signal processor (DSP) is working out of
tolerance

461

Fault in the DSP data memory

462

Error with DC feed monitoring routine

463

Reversed AC polarity, AC connector in-
serted incorrectly

474

RCMU sensor faulty

The inverter is not feeding
any energy into the grid.

**)

475

Insulation fault (connection between so-
lar module and ground)

476

Driver supply voltage too low

480,
481

Functional incompatibility (one or more
PC boards in the inverter are not com-
patible with each other, e.g. after a PC
board has been replaced)

The inverter is not feeding
any energy into the grid.

Update inverter firm-
ware, *)

482

Setup after the initial start-up was inter-
rupted

The inverter is not feeding
any energy into the grid.

Restart Setup after an
AC reset (switch auto-
matic circuit breaker off
and on again)

483

Voltage U

DC fixed

on MPP2 string out of

limits

The inverter is not feeding
any energy into the grid.

Check MPP settings; *)

485

CAN transmit buffer is full

The inverter is not feeding
any energy into the grid.

Perform AC reset
(switch automatic circuit
breaker off and on
again); *)

Code

Description

Behaviour

Remedy