Class 5 status
codes

Class 5 status codes do not generally interfere with feeding energy into the grid, but can
cause restrictions. These status code are displayed until they are acknowledged by press-
ing a key (the inverter, however, continues to operate normally in the background).

Code

Description

Behaviour

Remedy

502

Insulation error on the solar
modules

Warning message is
shown on the display

**)

509

No energy fed into the grid in
the past 24 hours

Warning message is
shown on the display

Acknowledge status code;
Check whether all the conditions for
the problem-free feeding of energy
into the grid have been met (e.g. are
the solar modules covered with
snow?); **)

515

No communication with filter
possible

Warning message on
the display

*)

516

No communication possible
with the storage unit

Storage unit warning
message

*)

517

Power derating caused by too
high a temperature

When power derating
occurs, a warning mes-
sage is shown on the
display

If necessary, purge cooling air open-
ings and heat sink;
fault is rectified automatically; **)

518

Internal DSP malfunction

Warning message on
the display

*)

519

No communication possible
with the storage unit

Storage unit warning
message

*)

520

No energy fed into the grid by
MPPT1 in the past 24 hours

Warning message is
shown on the display

Acknowledge status code;
Check whether all the conditions for
the problem-free feeding of energy
into the grid have been met (e.g. are
the solar modules covered with
snow?); *)

522

DC low String 1

Warning message on
the display

*)

523

DC low String 2

558,
559

Functional incompatibility (one
or more PC boards in the in-
verter are not compatible with
each other, e.g. after a PC
board has been replaced)

Warning message on
the display

Update inverter firmware; *)

560

Power derating caused by
overfrequency

Displayed when grid fre-
quency becomes exces-
sively high. The power is
reduced.

As soon as the grid frequency is back
within the permissible range and the
inverter has returned to normal oper-
ation, the fault is rectified automati-
cally. **)

564

Functional incompatibility (one
or more PC boards in the in-
verter are not compatible with
each other, e.g. after a PC
board has been replaced)

Warning message on
the display

Update inverter firmware; *)

566

Arc detector switched off
(e.g. during external arc moni-
toring)

The status code is dis-
played every day until
the arc detector is reac-
tivated.

No error
Confirm status code by pressing 'En-
ter'