48

*) If the status code is displayed all the time: notify a Fronius-trained service engineer

**) If this status code keeps recurring, contact your system engineer

Class 6 status
codes

Some of the class 6 status codes necessitate intervention by a Fronius-trained service en-
gineer.

*) If the status code is displayed all the time: notify a Fronius-trained service engineer

**) Fault is rectified automatically. If this status code keeps recurring, contact your system
engineer

Class 7 status
codes

Class 7 status codes relate to the control system, the configuration and inverter data re-
cording, and may directly or indirectly affect the process of feeding energy into the grid.

572

Power limited by the power
stage set

Power is being limited
by the power stage set

*)

573

Undertemperature warning

Warning message on
the display

*)

Code

Description

Behaviour

Remedy

Code

Description

Behaviour

Remedy

601

CAN bus is full

The inverter is not feeding
any energy into the grid.

Update inverter firm-
ware; *)

603

AC module temperature sensor faulty
(L3)

The inverter will automati-
cally attempt to connect
again and, if possible, will
resume feeding energy into
the grid

*)

604

DC module temperature sensor faulty

607

RCMU error

The inverter is not feeding
any energy into the grid.

Reset status code by
pressing 'Enter'. The in-
verter resumes the feed-
ing of energy into the
grid; if the status code
keeps appearing, check
the complete photovol-
taic system for damage;
**)

608

Functional incompatibility (one or more
PC boards in the inverter are not com-
patible with each other, e.g. after a PC
board has been replaced)

The inverter is not feeding
any energy into the grid.

Update inverter firm-
ware; *)

Code

Description

Behaviour

Remedy

701 -
716

Provides information about the
internal processor status

Warning message on the
display

*)

721

EEPROM has been re-initial-
ised

Warning message on the
display

Acknowledge status code; *)

722 -
730

Provides information about the
internal processor status

Warning message on the
display

*)

Advertising