Class 3 status
codes

Class 3 includes status codes that may occur while feeding energy into the grid, but gen-
erally do not cause the process to be interrupted for any length of time.

The inverter disconnects automatically from the grid, the grid is then monitored as specified
and the inverter attempts to resume feeding energy into the grid.

*) If the status code is displayed all the time: notify a Fronius-trained service engineer

**) Fault is rectified automatically. If this status code keeps recurring, contact your system
engineer

Code

Description

Behaviour

Remedy

301

Overcurrent (AC)

Short-term interruption while
feeding energy into the grid.
The inverter resumes its start-
up routine.

*)

302

Overcurrent (DC)

303

DC module overtemperature

Short-term interruption while
feeding energy into the grid.
The inverter resumes with its
startup routine.

Purge cooling air open-
ings and heat sink; **)

304

AC module overtemperature

305

No power being fed in, despite closed
relay

Short-term interruption while
feeding energy into the grid.
The inverter resumes with its
startup routine.

**)

306

PV output too low for feeding energy
into the grid

Short-term interruption while
feeding energy into the grid
The inverter resumes its start-
up routine.

wait for sufficient level of
insolation;
**)

307

DC low
DC input voltage too low for feeding
energy into the grid

IMPORTANT! Due to the low level of insolation early in the morning and in the evening, the status codes 306
(Power low) and 307 (DC low) are displayed routinely at these times of day. These status codes do not indicate
any kind of fault.
308

Intermediate circuit voltage too high

Short-term interruption while
feeding energy into the grid
The inverter resumes its start-
up routine.

**)

309

DC input voltage MPPT 1 too high

311

Polarity of DC strings reversed

313

DC input voltage MPPT2 too high

314

Current sensor calibration timeout

Short-term interruption while
feeding energy into the grid.
The inverter resumes with its
startup routine.

*)

315

AC current sensor error

316

InterruptCheck fail

325

Overtemperature in the connection
area

326

Fan 1 error

327

Fan 2 error