General description uk – FBT 37483_VAIE2550_manual1.pdf Manuale d'uso
Pagina 69

4-3
GENERAL DESCRIPTION
UK
4.2 FUNCTIONAL
SPECIFICATIONS
•
Two-channel sound broadcasting system.
•
Six broadcasting zones.
•
Controlled double output line for each single (A and B).
•
*.mp3 files read from USB flash memory as a source of background music.
•
Downloading of *.WAV files from USB flash memory for emergency voice messages and chime.
•
Independent 5-level volume control of the music for each zone.
•
Sources for service paging announcements settable to 7 priority levels and 36 zone lists.
•
System operating functions linked to different access levels, some of which protected by passwords
•
Continuous control and monitoring of the integrity of the critical path (from the sources of the emergency signal to the loudspeaker lines)
without interrupting the background music.
•
Monitoring of the loudspeaker lines (integrity and dispersion to earth) by means of the two-channel amplification system, even in voice
emergency conditions.
•
Digital audio control (DSP).
•
Easy and rapid configuration (large LCD display).
•
Provisions for a web server.
•
Emergency zone disabling function (Disabling).
•
Do Not Disturb function for protecting the zones from accidental enabling of music or service calls.
•
Acoustic signalling of failure status with automatic or manual muting.
•
Manual resetting of visual failure signals and automatic resetting with storage of the last occurring failure.
•
Direct procedure for starting up the system (start-up) and programming events, without using the management software.
•
Possibility of adding a 250 W external amplifier to increase the output power of the system.
•
Automatic management of the music amplifier as a stand-by for the operational amplifier (internal or external).
•
With a second remote VAIE 2250 unit, the system can be expanded to cover up to 12 zones.
•
Possibility of connecting up to 16 paging units.
•
It is possible to connect up to seven remote emergency units.
4.3 TECHNICAL
SPECIFICATIONS
•
Two 250 W RMS Class D amplifiers.
•
Built-in message generator for broadcasting voice alarms on two channels (EVAC and ALERT).
•
Controlled emergency microphone on the front panel.
•
LCD graphic display, 128x64 pixels.
•
USB socket on front panel for connecting to storage devices.
•
USB socket on front panel for connecting a PC.
•
Auxiliary line input for an external source of music.
•
Balanced microphone input (IN 1) with phantom power supply and precedence contact.
•
Balanced microphone or line input (IN 2) with phantom power supply (MIC), precedence contact or automatic VOX precedence.
• Balanced line input (IN 3) with automatic VOX precedence function.
•
8 programmable and controlled input contacts.
•
6 open-collector outputs, programmable as system status or override outputs for by-passing the attenuators.
•
2 relay outputs for “emergency” and “failure” conditions.
•
CAT5 socket for remote emergency consoles FMD 2001 and FMD 2012 (EMERGENCY UNITS).
•
CAT5 socket for service call consoles MBT 1106 / MBT 1112 range (PAGING UNITS).
•
CAT5 socket for connection to a remote VAIE 2250 unit (REMOTE LINK).
•
100-70V line input/output for connection to a 250 W external amplifier for expansion purposes.
•
Built-in loudspeaker for channel monitoring and acoustic failure signalling (beep) function.
•
Input 24 VDC secondary emergency power supply.