JOCKEY PUMP

Unit

Terminal board

Terminal

Description

Terminal

Terminal

board

Panel

JOCKEY PUMP PANEL

Relay KA1

11

Jockey pump

running

2

XC2

KL3

Q-2Rils 485

14

4

Relay KA2

11

Overload

2

14

6

Important: The jockey pump panel, if present, must be version CP with clean contacts.

1) If the jockey pump running signal is not used, jumper terminals 2-4 on terminal block XC2 (KL3) in the Q-2Rils 485
panel or do not enable monitoring from QAL 12845.

DRAIN PUMP

Unit

Terminal board

Terminal

Description

Terminal

Terminal

board

Panel

DRAIN PUMP PANEL

See panel

**

Overload

2

XC2

KL3

Q-2Rils 485

**

8

**) Identify the terminals from the device diagram. In case of alarm, the final contact must be NO.

9.5 SETS with TWO DIESEL UNITS.

Typology of compatible sets: GEN..20, GEN..21 and auxiliary services (if present).

9.5.1 Position of micro-switches

Set code

Unit

Micro-switch

Micro-switch configuration

GEN..20,

GEN..21

KL2

Q2Rils485

SW1

Position

1

2

ON

ON

SW2

Position

1

2

3

ON

OFF

ON

SW3

Position

1

2

3

4..10

ON

OFF

OFF

-

KL3

Q2Rils485

SW1

Position

1

2

ON

ON

SW2

Position

1

2

3

ON

OFF

ON

SW3

Position

1

2

3

4..10

OFF

ON

OFF

-