Xylem Q 2Rils 485 Signal delivery panel EN 12845 Manuale d'uso

Pagina 37

Advertising
background image

37

1) If the jockey pump running signal is not used, jumper terminals 2-4 on terminal block XC2 (KL3) in the Q-2Rils 485
panel or do not enable monitoring from QAL 12845.

DRAIN PUMP

Unit

Terminal board

Terminal

Description

Terminal

Terminal

board

Panel

DRAIN PUMP PANEL

See panel

**

Overload

2

XC2

KL3

Q-2Rils 485

**

8

**) Identify the terminals from the device diagram. In case of alarm, the final contact must be NO.

9.3 SETS with TWO DIESEL UNITS.
Typology of compatible sets: GEN..00D2, GEN..01D2 and auxiliary services (if present).

9.3.1 Position of micro-switches

Set code

Unit

Micro-switch

Micro-switch configuration

GEN..00D2,

GEN..01D2

KL2

Q2Rils485

SW1

Position

1

2

ON

ON

SW2

Position

1

2

3

OFF

ON

ON

SW3

Position

1

2

3

4..10

ON

OFF

OFF

-

KL3

Q2Rils485

SW1

Position

1

2

ON

ON

SW2

Position

1

2

3

OFF

ON

ON

SW3

Position

1

2

3

4..10

OFF

ON

OFF

-

9.3.2 Diesel unit 1 electrical connections

DIESEL UNIT 1

Unit

Terminal board

Terminal

Description

Terminal

Terminal

board

Panel

DIESEL UNIT 1 PANEL

See panel

25

Common

2

XC2

KL2

Q-2Rils 485

20

Switch not

automatic

12

21

Failure to start

14

22

Pump running

16