39

N.B.:
1) If the flowmeter valve is not used, do not jumper terminals 1-22 on terminal block XC2 (KL3) in the Q-2Rils 485 panel

or do not enable monitoring from QAL 12845.
2) If the intake and/or delivery valve is not used, jumper terminals 1-4 / 1-6 on terminal block XC2 (KL2 / KL3) in the Q-
2Rils 485 panel or do not enable monitoring from QAL 12845.

JOCKEY PUMP

Unit

Terminal board

Terminal

Description

Terminal

Terminal

board

Panel

JOCKEY PUMP PANEL

Relay KA1

11

Jockey pump

running

2

XC2

KL2

Q-2Rils 485

14

20

Relay KA2

11

Overload

2

14

22


Important: The jockey pump panel, if present, must be version CP with clean contacts.

1) If the jockey pump running signal is not used, jumper terminals 2-20 on terminal block XC2 (KL2) in the Q-2Rils 485
panel or do not enable monitoring from QAL 12845.

DRAIN PUMP

Unit

Terminal board

Terminal

Description

Terminal

Terminal

board

Panel

DRAIN PUMP PANEL

See panel

**

Overload

2

XC2

KL3

Q-2Rils 485

**

20

**) Identify the terminals from the device diagram. In case of alarm, the final contact must be NO.

9.4 SETS with ONE DIESEL UNIT.

Typology of compatible sets: D.., GEN..00D, GEN..01D and auxiliary services (if present).

9.4.1 Position of micro-switches

Set code

Unit

Micro-switch

Micro-switch configuration

D..,

GEN..00D,

GEN..01D

KL2

Q2Rils485

SW1

Position

1

2

ON

ON

SW2

Position

1

2

3

OFF

ON

OFF

SW3

Position

1

2

3

4..10

ON

OFF

OFF

-

KL3

Q2Rils485

SW1

Position

1

2

3

ON

ON

-

SW2

Position

1

2

3

OFF

OFF

ON