Xylem Q 2Rils 485 Signal delivery panel EN 12845 Manuale d'uso

Pagina 33

Advertising
background image

33

9.1 SETS with: one ELECTRIC PUMP and one DIESEL UNIT.

Typology of compatible sets: (GEN..10D, GEN..11D) and auxiliary services (if present).


9.1.1 Position of micro-switches

Unit code

Unit

Micro-switch

Micro-switch configuration

GEN..10D

GEN..11D

KL2

Q2Rils485

SW1

Position

1

2

ON

ON

SW2

Position

1

2

3

ON

OFF

ON

SW3

Position

1

2

3

4..10

ON

OFF

OFF

-

KL3

Q2Rils485

SW1

Position

1

2

ON

ON

SW2

Position

1

2

3

OFF

ON

ON

SW3

Position

1

2

3

4..10

OFF

ON

OFF

-

9.1.2 Electric pump connections

ELECTRIC PUMP

Unit

Terminal board

Terminal

Description

Terminal

Terminal

board

Unit

ELECTRIC PUMP

PANEL

See panel

7

Common

2

XC2

KL2

Q-2Rils 485

8

Incorrect phase

sequence

12

9

Pump on demand

14

10

Pump running

16

11

Failure to start

18

Float switch

see float switch

*

Minimum level of

suction tank

2

*

8

Float switch

see float switch

*

Minimum level of

priming tank

2

*

10

* Identify the terminals from the device diagram. In case of alarm, the final contact must be NO.

Advertising