Riello UPS NetMan 204 Manuale d'uso

Pagina 42

Advertising
background image

REGISTRO

(1)

FLAG SPECIALI (UPS SERIE SENTR)

(2)

UNITÀ

NUMERO INDIRIZZO

121

120

Byte 1 of “s = xx..” code / Byte 2 of “s = ..xx” code

Flag

122

121

Byte 1 of “c = xx..” code / Byte 2 of “c = ..xx” code

Flag

123

122

Byte 1 of “b = xx..” code / Byte 2 of “b = ..xx” code

Flag

124

123

Byte 1 of “r = xx..-..” code / Byte 2 of “r = ..xx-..” code

Flag

125

124

Byte 3 of “r = ....-xx” code / Byte 1 of “i = xx..-..” code

Flag

126

125

Byte 2 of “i = ..xx-..” code / Byte 3 of “i = ....-xx” code

Flag

127

126

Byte 1 of “a = xx..-....” code / Byte 2 of “a = ..xx-....” code

Flag

128

127

Byte 3 of “a = ....-xx..” code / Byte 4 of “a = ....-..xx” code

Flag

REGISTRO

(1)

DATI DI NETMAN

UNITÀ

NUMERO INDIRIZZO

129

128

Versione firmware

Intero

130ч131

129ч130

(1)

Il registro numero

n deve essere indirizzato n-1 nel pacchetto dati.

(2)

Per decodificare questi registri, fare riferimento al manuale dell'UPS.

UPS:

C

ODICI COMANDI

CODICE

COMANDO

1

(0x0001)

Spegnimento (Shutdown)

2

(0x0002)

Spegnimento e riaccensione (shutdown e restore)

3

(0x0003)

Cancellazione (codice 1, 2, 12)

12

(0x000C)

UPS da bypass

20

(0x0014)

Test batteria

22

(0x0016)

Test pannello

- 42 -