C-PRO KILO AHU MANUALE APPLICATIVO

Pag. 82

6=Manual, 7=OFFt

0x050F

1296

Status_Recover

0

0

4

R/W

0x0510

1297

Status_Resistor1

0

0

5

0=Disabilitato, 1=OFF,
2=Wait ON, 3=ON,
4=Wait OFF, 5=ALL

R/W

0x0511

1298

Status_Resistor2

0

0

5

0=Disabilitato, 1=OFF,
2=Wait ON, 3=ON,
4=Wait OFF, 5=ALL

R/W

0x0512

1299

Status_Resistor3

0

0

5

0=Disabilitato, 1=OFF,
2=Wait ON, 3=ON,
4=Wait OFF, 5=ALL

R/W

0x0513

1300

Status_AirExtShutter

0

0

6

0=Disabilitato, 1=OFF,
2=Opening, 3=ON,
4=Closing, 5=ALL,
6=Allineamento

R/W

0x0514

1301

Position_AirShutter

0.00

0.00

100.00

0% -100.00%

R/W

0x0600

1537

PT01_Start_NightTB ( Low )

0

0

86399

R/W

0x0601

1538

PT01_Start_NightTB ( High )

0x0602

1539

PT02_End_NightTB ( Low )

0

0

86399

R/W

0x0603

1540

PT02_End_NightTB ( High )

0x0604

1541

PT03_OffsetSetPoint_Night

0.0

-36.0

36.0

R/W

0x0605

1542

MOdE_SummerWinterMode

1

0

1

0=Estate (Cooling),
1=Inverno (Heating)

R/W

0x0606

1543

SEtC_SummerSetPoint

24.0

-15.0

158.0

R/W

0x0607

1544

SEtH_WinterSetPoint

20.0

-15.0

158.0

Winter Set Point or Set
Point unique(if
selected by PH27)

R/W

0x0608

1545

PU01_Humidity_SetPoint

50

0

100

R/W

0x0609

1546

OS01_OffsetSetPoint_DI

0.0

-36.0

36.0

R/W

0x060A

1547

OS02_OffsetSetPoint_SUP

0.0

-36.0

36.0

R/W

0x060B

1548

PM00_Limit_HourFan ( Low )

20000

0

100000

R/W

0x060C

1549

PM00_Limit_HourFan ( High )

0x060D

1550

PM01_SupplyFan_Hours ( Low )

0

0

100000

R/W

0x060E

1551

PM01_SupplyFan_Hours ( High )

0x060F

1552

PM02_ReturnFan_Hours ( Low )

0

0

100000

R/W

0x0610

1553

PM02_ReturnFan_Hours ( High )

0x0611

1554

PM10_Limit_HourPump ( Low )

20000

0

100000

R/W

0x0612

1555

PM10_Limit_HourPump ( High )

0x0613

1556

PM11_PumpHeat_Hours ( Low )

0

0

100000

R/W

0x0614

1557

PM11_PumpHeat_Hours ( High )