Electrical installation

Mounting steps

4

EDKZS3X200 DE/EN/FR/ES/IT 1.1

31

H1_E_INST-Fi Verdraht_BF2

SSP94SF008

SSP94SF010

x

Stripping length depends on the filter size

How to connect the filter:
1. Loosen three screws  and remove the terminal cover 
2. Connect filter input cable to terminals 1U1, 1V1, 1W1 and PE.

Connect filter output cable to terminals 1U2, 1V2, 1W2 and PE.

– Observe tightening torques!

– The PE connection must comply with EN 50178.

3. The shield must be connected with a large surface to the shield sheet (PES).

– Turn down the shield and fix it with cable binders .

– Alternative: Insert shield mounting kit E94AZJSxxx (not included in the

scope of supply) and mount cable binders in addition for strain relief .

4. Insert terminal cover  and fix it with three screws .