4 electrical installation, Electrical installation, Danger – Lenze EZS3-xxxA200 Sinusoidal filter 4-90A Manuale d'uso

Pagina 27

Advertising
background image

Electrical installation

Important notes

4

EDKZS3X200 DE/EN/FR/ES/IT 1.1

27

H1_E_INST-Fi Verdraht_BF2

4

Electrical installation

Important notes

Danger!

The terminals also carry dangerous voltages even if the motor is stopped!

ƒ

For this reason, check that the terminals are dead before you start working.

ƒ

The sinusoidal filters from a rated current of 23.5 A may only be operated

with a mounted terminal cover. Otherwise, an electrical shock may occur

when touching the terminals.

Connection data

Sinusoidal filter

Terminal

PE screw

Connection

cross-sections

Tightening torque

Tightening torque

[mm

2

]

[AWG]

[Nm]

[lb-in]

[Nm]

[lb-in]

EZS3-004A200

0.2 ... 6

24 ... 10

0.6

5.3

M4

2

17.7

EZS3-010A200
EZS3-017A200

0.5 ... 16

20 ... 6

1.5

13.3

EZS3-024A200

2.5 ... 25

10 ... 6

2

17.7

M5

3

26.5

EZS3-032A200
EZS3-037A200
EZS3-048A200

2.5 ... 35

12 ... 2

3

26.5

EZS3-061A200
EZS3-072A200

16 ... 50

1/0 ... 6

EZS3-090A200

Advertising