Technical data

Standards

Conformity

CE

Low-Voltage Directive

Approval

UR

UL508, Industrial Control

Equipment, Underwriter

Laboratories (File-No. E219022)

for USA and Canada

Operating conditions

Climatic conditions

Class 3K3 according to EN 50178 Without condensation, average

relative humidity 85 %

Permissible ambient

operating temperature

-10 °C ... +55 °C

Above 40 °C, the rated current I

N

must be reduced by 2.5 %/°C

Permissible installation

height

0 ... 4000 m amsl

Above 1000 m, the rated current I

N

must be reduced by 5 %/1000 m

Vibration resistance

Accelerational stability up to 1 g

EN50178, IEC61800-5-1 and

Germanischer Lloyd, general

conditions

Degree of protection

IP20 (protection against contact to NEMA 250 type 1)

Mounting position

Vertical with fixing bracket below

Depending on the weight, wall mounting is possible

Connecting cables

Drive controller ↔ filter As short as possible, shielded

Filter ↔ motor Max. 200 m shielded or max. 300 m unshielded