8.2

QUADRO DI COMANDO

ALLARME INCENDI

RIVELATORE X2200

AVVERTENZE PER IL CABLAGGIO:

1 IN NORMAL OPERATION WITH NO FAULTS OCCURRING, THE FAULT RELAY COIL IS ENERGIZED

AND THE NORMALLY OPEN (N.O.) AND COMMON (COM) CONTACTS ARE CLOSED.

2 ALARM RELAY IS NORMALLY DE-ENERGIZED WITH NO ALARM CONDITION PRESENT.

3 INDIVIDUAL MANUAL

oi TEST SWITCHES CAN BE INSTALLED REMOTELY OR A DETECTOR

SELECTOR AND ACTIVATION SWITCH CAN BE INSTALLED AT THE FIRE PANEL. TEST SWITCHES

ARE NOT SUPPLIED.

4 PER I VALORI DELLA RESISTENZA EOL, FARE RIFERIMENTO ALLA SEZIONE SPECIFICHE. PER I

DETTAGLI RELATIVI ALL'INSTALLAZIONE, FARE RIFERIMENTO ALLA SEZIONE RESISTENZE EOL.

B2151

ALARM

24 VDC

+

E.O.L.

DEVICE4

oi TEST 3

9

8

7

6

5

4

3

2

1

19

18

17

16

15

14

13

12

11

COM FIRE2

COM FIRE

N.O. FIRE2

N.O. FIRE

N.C. FIRE2

N.C. FIRE

COM FAULT1

COM FAULT

N.O. FAULT1

N.O. FAULT

24 VDC +

24 VDC +

24 VDC –

24 VDC –

24 VDC –

29

28

27

26

25

24

23

22

21

SPARE

SPARE

RS-485 A

RS-485 B

MAN

Oi

4-20 mA +

4-20 mA –

4-20 mA + REF

4-20 mA – REF

COM AUX

N.O. AUX

N.C. AUX

Figura 7: Opzione cablaggio Ex d

QUADRO DI COMANDO

ALLARME INCENDI

RIVELATORE X2200

AVVERTENZE PER IL CABLAGGIO:

1 IN NORMAL OPERATION WITH NO FAULTS OCCURRING, THE FAULT RELAY COIL IS ENERGIZED

AND THE NORMALLY OPEN (N.O.) AND COMMON (COM) CONTACTS ARE CLOSED.

2 ALARM RELAY IS NORMALLY DE-ENERGIZED WITH NO ALARM CONDITION PRESENT.

3 INDIVIDUAL MANUAL

oi TEST SWITCHES CAN BE INSTALLED REMOTELY OR A DETECTOR

SELECTOR AND ACTIVATION SWITCH CAN BE INSTALLED AT THE FIRE PANEL. TEST

SWITCHES ARE NOT SUPPLIED.

4 RESISTENZE EOL ALIMENTATE DAL QUADRO.

B2152

ALARM

ALARM

24 VDC

+

EOL

DEVICE 4

oi TEST 3

9

8

7

6

5

4

3

2

1

19

18

17

16

15

14

13

12

11

COM FIRE2

COM FIRE

N.O. FIRE2

N.O. FIRE

N.C. FIRE2

N.C. FIRE

COM FAULT1

COM FAULT

N.O. FAULT1

N.O. FAULT

24 VDC +

24 VDC +

24 VDC –

24 VDC –

24 VDC –

29

28

27

26

25

24

23

22

21

SPARE

SPARE

RS-485 A

RS-485 B

MAN

Oi

4-20 mA +

4-20 mA –

4-20 mA + REF

4-20 mA – REF

COM AUX

N.O. AUX

N.C. AUX

Figura 8: Opzione cablaggio Ex e