10 WORKING SETPOINTS AND CONFIGURATION PARAMETERS

10.1

Working setpoints

MIN.

MAX.

U.M.

DEF.

WORKING SETPOINTS

r1

r2

°C/°F (1) 0.0

working setpoint

10.2

Configuration parameters

PARAM. MIN.

MAX.

U.M.

DEF.

WORKING SETPOINTS

SP

r1

r2

°C/°F (1) 0.0

working setpoint

PARAM. MIN.

MAX.

U.M.

DEF.

MEASURE INPUTS

o1

-25

25

°C/°F (1) 0.0

cabinet probe offset

P0

0

1

- - -

1

kind of probe
0 = PTC
1 = NTC

P1

0

1

- - -

1

decimal point Celsius degree (for the quantity to
show during the normal operation, between -9.9
and 19.9 °C)
1 = YES

P2

0

1

- - -

0

unit of measure temperature (2)
0 = °C
1 = °F

PARAM. MIN.

MAX.

U.M.

DEF.

MAIN REGULATOR

r0

0.1

15.0

°C/°F (1) 2.0

working setpoint differential

r1

-99

r2

°C/°F (1) -40

minimum working setpoint

r2

r1

199

°C/°F (1) 50

maximum working setpoint

r4

0.0

99

°C/°F (1) 0.0

temperature increase during function “energy sav-
ing”; also look at i5 and i8

r5

0

1

- - -

0

cooling or heating action
0 = cooling (defrost management is enabled)
1 = heating (defrost management is not enabled)

PARAM. MIN.

MAX.

U.M.

DEF.

COMPRESSOR PROTECTIONS

C0

0

199

min

0

compressor delay since you turn on the instrument

C2

0

199

min

3

minimum time the compressor remains turned off

C3

0

199

s

0

minimum time the compressor remains turned on

PARAM. MIN.

MAX.

U.M.

DEF.

DEFROST (3)

d0

0

99

h

8

defrost interval
0 = the defrost at intervals will never be activated

d3

0

99

min

30

defrost duration
0 = the defrost will never be activated

d4

0

1

- - -

0

defrost when you turn on the instrument
1 = YES

d5

0

199

min

0

defrost delay when you turn on the instrument
(only if d4 = 1)

d6

0

1

- - -

1

temperature shown during the defrost
0 = cabinet temperature
1 = if to the defrost activation the cabinet tempera-

ture is below “working setpoint + r0”, at most
“working setpoint + r0”; if to the defrost activa-
tion the cabinet temperature is above “work-
ing setpoint + r0”, at most the cabinet tempera-
ture to the defrost activation (4)

PARAM. MIN.

MAX.

U.M.

DEF.

TEMPERATURE ALARMS (5) (6)

A1

0.0

199

°C/°F (1) 10.0

temperature below which the lower temperature
alarm is activated (relative to the working setpoint
or "working setpoint - A1”) (7)
0.0 = alarm not enabled

A4

0.0

199

°C/°F (1) 10.0

temperature above which the upper temperature
alarm is activated (relative to the working setpoint
or "working setpoint + A4”) (7)
0.0 = alarm not enabled

A6

0

99

10 min

12

temperature alarm delay since you turn on the in-
strument

A7

0

199

min

15

temperature alarm delay

PARAM. MIN.

MAX.

U.M.

DEF.

DIGITAL INPUTS

i1

0

1

- - -

0

kind of contact digital input
0 = NO (the input will be active if you close the

contact)

1 = NC (the input will be active if you open the

contact)

i3

-1

120

min

15

maximum duration of the effect provoked by the
activation of the door switch input
-1 = the effect will last as long as the input will be

deactivated

i5

0

3

- - -

3

kind of digital input (effect provoked by the activa-
tion of the digital input)
0 = no effect
1 = MULTIPURPOSE (activation external alarm) -

spent the time i7 the display will show the code
“iA” flashing (as long as the input will be deac-
tivated)

2 = MULTIPURPOSE (activation manostat) - the com-

pressor will be turned off and the display will
show the code “iA” flashing (as long as the
input will be deactivated); also look at i7

3 = DOOR SWITCH INPUT (compressor turned off)

- the compressor will be turned off (at most for
the time i3 or as long as the input will be deac-
tivated) and spent the time i7 the display will
show the code “id” flashing (as long as the in-
put will be deactivated) (8)

i7

-1

120

min

30

if i5 = 1, delay to signal the multipurpose input alarm
-1 = no signal
if i5 = 2, compressor delay since the deactivation of
the multipurpose input (9)
if i5 = 3, delay to signal the door switch input alarm
-1 = no signal

i8

0

199

min

0

time without door switch input activations (after the
cabinet temperature has achieved the working
setpoint) in order that function “energy saving” is
activated
0 = the function will never be activated

i9

0

199

- - -

180

number of door switch input activations such as to
provoke the defrost activation
0 = the defrost will never be activated because of

the door switch input activation

iA

0

199

min

32

minimum duration of the door switch imput activa-
tion such as to provoke the defrost activation
0 = the defrost will never be activated because of

the door switch input activation

PARAM. MIN.

MAX. U.M.

DEF.

ENERGY SAVING

E0

0

99

10 min

0

maximum duration of function “energy saving”
0 = the function will last as long as the input will be

activated

(1)

the unit of measure depends on parameter P2

(2)

set the parameters related to the regulators appropriately after the
modification of the parameter P2

(3)

if parameter r5 has value 1 (heating action), function “energy saving” and the defrost
management will not be enabled

(4)

the display restores the normal operation as soon as the defrost ends and the cabinet
temperature falls below the one that has locked the display (or if a temperature alarm
arises)

(5)

during the defrost the temperature alarms are not enabled, on condition that they have
arisen after the activation of the defrost

(6)

during the activation of the door switch input the upper temperature alarm is not
enabled, on condition that it has arisen after the activation of the input

(7)

the differential of the parameter is 2.0 °C/4 °F

(8)

the compressor is turned off spent 10 s since the activation of the input; if the input is
activated during the defrost, the activation will provoke no effect on the compressor

(9)

if parameter i5 has value 2 and parameter i7 has value -1, the instrument will work as if
parameter i7 had value 0.

I ITALIANO

10 SETPOINT DI LAVORO E PARAMETRI

DI CONFIGURAZIONE

10.1

Setpoint di lavoro

SETPOINT DI LAVORO
setpoint di lavoro
10.2

Parametri di configurazione

SETPOINT DI LAVORO
setpoint di lavoro
INGRESSI DI MISURA
offset sonda cella
tipo di sonda
0 = PTC
1 = NTC
punto decimale grado Celsius (per la grandezza
visualizzata durante il normale funzionamento, tra
-9,9 e 19,9 °C)
1 = SI
unità di misura temperatura (2)
0 = °C
1 = °F
REGOLATORE PRINCIPALE
differenziale del setpoint di lavoro
minimo setpoint di lavoro
massimo setpoint di lavoro
incremento di temperatura durante la funzione
“energy saving”; si vedano anche i5 e i8
funzionamento per freddo o per caldo
0 = per freddo (la gestione dello sbrinamento è

abilitata)

1 = per caldo (la gestione dello sbrinamento non è

abilitata)

PROTEZIONI DEL COMPRESSORE
ritardo compressore dall’accensione dello strumen-
to
durata minima dello spegnimento del compressore
durata minima dell’accensione del compressore
SBRINAMENTO (3)
intervallo di sbrinamento
0 = lo sbrinamento a intervalli non verrà mai attiva-

to

durata dello sbrinamento
0 = lo sbrinamento non verrà mai attivato
sbrinamento all’accensione dello strumento
1 = SI
ritardo sbrinamento dall’accensione dello strumen-
to (solo se d4 = 1)
temperatura visualizzata durante lo sbrinamento
0 = temperatura della cella
1 = se all’attivazione dello sbrinamento la tempera-

tura della cella è al di sotto di “setpoint di lavo-
ro + r0”, al massimo “setpoint di lavoro + r0”; se
all’attivazione dello sbrinamento la temperatu-
ra della cella è al di sopra di “setpoint di lavoro
+ r0”, al massimo la temperatura della cella al-
l’attivazione dello sbrinamento (4)

ALLARMI DI TEMPERATURA (5) (6)
temperatura al di sotto della quale viene attivato
l’allarme di temperatura di minima (relativo al
setpoint di lavoro ovvero “setpoint di lavoro - A1”)
(7)
0.0 = allarme assente
temperatura al di sopra della quale viene attivato
l’allarme di temperatura di massima (relativo al
setpoint di lavoro ovvero “setpoint di lavoro + A4”)
(7)
0.0 = allarme assente
ritardo allarme di temperatura dall’accensione dello
strumento
ritardo allarme di temperatura
INGRESSI DIGITALI
tipo di contatto dell’ingresso digitale
0 = NA (ingresso attivo con contatto chiuso)
1 = NC (ingresso attivo con contatto aperto)

durata massima dell’effetto provocato dall'attivazio-
ne dell’ingresso micro porta
-1 = l’effetto durerà fino a quando l’ingresso verrà

disattivato

tipo di ingresso digitale (effetto provocato dall'atti-
vazione dell’ingresso digitale)
0 = nessun effetto
1 = INGRESSO MULTIFUNZIONE (attivazione allar-

me esterno) - trascorso il tempo i7 il display
visualizzerà il codice “iA” lampeggiante (fino a
quando l’ingresso verrà disattivato)

2 = INGRESSO MULTIFUNZIONE (intervento

pressostato) - il compressore verrà spento e il
display visualizzerà il codice “iA” lampeggiante
(fino a quando l’ingresso verrà disattivato); si
veda anche i7

3 = INGRESSO MICRO PORTA (compressore spen-

to) - il compressore verrà spento (al massimo
per il tempo i3 o fino a quando l’ingresso verrà
disattivato) e trascorso il tempo i7 il display
visualizzerà il codice “id” lampeggiante (fino a
quando l’ingresso verrà disattivato) (8)

se i5 = 1, ritardo segnalazione allarme ingresso
multifunzione
-1 = l’allarme non verrà segnalato
se i5 = 2, ritardo compressore dalla disattivazione
dell’ingresso multifunzione (9)
se i5 = 3, ritardo segnalazione allarme ingresso micro
porta
-1 = l’allarme non verrà segnalato
tempo che deve trascorrere in assenza di attivazioni
dell’ingresso micro porta (dopo che la temperatura
della cella ha raggiunto il setpoint di lavoro) affinchè
la funzione “energy saving” venga attivata
0 = la funzione non verrà mai attivata
numero di attivazioni dell’ingresso micro porta tale
da provocare l’attivazione dello sbrinamento
0 = lo sbrinamento non verrà mai attivato per effet-

to dell’attivazione dell’ingresso micro porta

durata minima dell’attivazione dell’ingresso micro
porta tale da provocare l’attivazione dello
sbrinamento
0 = lo sbrinamento non verrà mai attivato per effet-

to dell’attivazione dell’ingresso micro porta

ENERGY SAVING
durata massima della funzione “energy saving”
0 = la funzione durerà fino a quando l’ingresso ver-

rà attivato

(1) l’unità di misura dipende dal parametro P2
(2) impostare opportunamente i parame-

tri relativi ai regolatori dopo la modi-
fica del parametro P2

(3) se il parametro r5 è impostato a 1 (funziona-

mento per caldo), la funzione “energy saving”
e la gestione dello sbrinamento non saranno
abilitate

(4) il display ripristina il normale funzionamento

quando, concluso lo sbrinamento, la tempe-
ratura della cella scende al di sotto di quella
che ha bloccato il display (o se si manifesta un
allarme di temperatura)

(5) durante lo sbrinamento gli allarmi di tempera-

tura sono assenti, a condizione che questi si
siano manifestati dopo l’attivazione dello
sbrinamento

(6) durante l’attivazione dell’ingresso micro porta

l’allarme di temperatura di massima è assente,
a condizione che questi si sia manifestato dopo
l’attivazione dell’ingresso

(7) il differenziale del parametro è di 2,0 °C/4 °F
(8) il compressore viene spento trascorsi 10 s dal-

l’attivazione dell’ingresso; se l’ingresso viene
attivato durante lo sbrinamento, l’attivazione
non provocherà alcun effetto sul compresso-
re

(9) se il parametro i5 è impostato a 2 e il parame-

tro i7 è impostato a -1, lo strumento funzione-
rà come se il parametro i7 fosse impostato a
0.

Advertising
Questo manuale è associato alle seguenti prodotti: