Schreiber Chillers 500AC U Chiller Control Manuale d'uso

Pagina 13

Advertising
background image

9

ANTIGELO/RESISTENZE APPOGGIO

Tipo

Min.

Max.

U.M.

Variazione Default Pres. DVNP Nuovo

ANTIFREEZE/SUPPORTING HEATERS

Type

Min.

Max.

M.U.

Variation

Default Presence

New

A1 Set allarme antigelo/Bassa temperatura

U

A7

A4

/d

0.1

3.0

-----

Antifreeze/Low alarm set-point

A2 Differenziale allarme antigelo/bassa

U

0.3

19.9

/d

0.1

5.0

-----

temperatura / Differential for antifreeze/low
temperature alarm

A3 Tempo bypass allarme antigelo/bassa

U

0

150

sec

1

0

-----

temperatura all'accensione della macchina
in Inverno / Bypass time for antifreeze
alarm/Low ambient temperature when
turning on the unit in heating mode

A4 Set resistenza antigelo in raffreddamento

U

A1

rd

/d

0.1

5.0

-----

Set-point for the activation of antifreeze

A5 Differ. resistenza appoggio in raffreddamento U

0.3

19.9

/d

0.1

1.0

-----

Differ. for antifreeze in cooling

A6 Sonda resistenze di appoggio

F

0

1

flag

1

0

-----

Supporting heaters probe

A7 Limite set allarme antigelo

F

-40

122

/d

0.1

-40

-----

Limit antifreeze alarm set

A8 Set resistenza appoggio in riscaldamento

U

A1

rd

/d

0.1

25

-----

Set-point for the supporting heater

A9 Differ. resistenza appoggio in riscaldamento

U

0.3

19.9

/d

0.1

3.0

-----

Differ. for antifreeze supporting heater

AA Accensione automatica in antigelo

U

0

2

flag

1

0

-----

Automatic start in antifreeze
0= non abilitata / not enabled
1=resistenze di appoggio e pompa accesi / support heaters and pump on
2=accensione automatica con temp. < SET allarme antigelo / automatic start when temp. < antifreeze alarm SET

ALLARME

Tipo

Min.

Max.

U.M.

Variazione Default Pres. DVNP

Nuovo

ALARM

Type

Min.

Max.

M.U.

Variation

Default Presence

New

P1 Ritardo allarme di flusso dalla part. pompa

U

0

150

sec

1

20

-----

Flowmeter down delayed when starting the pump

P2 Ritardo allarme di flusso a regime

U

0

90

sec

1

5

-----

Flowswitch alarm delayed during normal operating

P3 Ritardo allarme B.P. da accensione compr.

U

0

199

sec

1

40

-----

Low pressure alarm delayed at compr. start-up

P4 Attivazione del cicalino / Buzzer ON

U

0

15

min

1

0

-----

P5 Rispristino allarmi / Reset of alarms

F

0

4

flag

1

0

P6
P7 Allarme di bassa pressione da sonda

F

0

2

flag

1

0

---P-

Low pressure alarm with pressure probes

P8 Tipo ingr. digitale 1-2 / Sel. of the digital input F

0

11

flag

1

0

-----

P9 0=nessuno / 0=no device connected

1=flussostato con ripristino manuale / 1=flow controller with manual reset
2=termico con ripristino automatico / 2=thermal with automatic reset
3=estate/inverno / 3=cooling/heating remote selection
4=fine defrost da contatto / 4=defrosting-end from pressure controller
5=flussostato con ripristino automatico / 5=flow controller with automatic reset
6=termico con ripristino manuale / 6=thermal with manual reset
7=estate/inverno con ritardi dC e dd / 7=cooling/heating with delay dC and dd
8=estate/inverno selezionato da H6 / 8=cooling/heating selected by H6
9=estate/inverno con ritardi dC e dd selezionato da H6 / 9=cooling/heating with delay dC and dd selected by H6
10=segnalazione allarme con ripristino automatico / 10=alarm signal with automatic reset
11=segnalazione allarme con ripristino manuale / 11=alarm signal with manual reset

PA Selezione allarme bassa pressione

F

0

1

flag

1

0

-----

Selection low pressure alarm
0=non attivo a compressore spento / 0=no activ with compressor OFF
1=attivo a compressore spento / 1=activ with compressor OFF

Pb Set allarme di alta temperatura

U

-40

199

/d

0.1

90

-----

High temperature alarm set

PC Ritardo allarme alta temp. all’accensione

U

0

150

min

1

30

-----

High temperature alarm delayed at start-up