EVCO S.p.A. • Code 104CP3HPA113 • page 1/2

c-pro 3 hecto+

Programmable controllers

version 1.1

5

ELECTRICAL CONNECTION

5.1

Electrical connection

The following tables show the meaning of the connectors.
MODBUS
RS-485 port with Modbus master / slave communication protocol
(configurable via application software).
MICRO-SWITCH
Micro-switch to:
- plug in the termination of the RS-485 port; also look at paragraph 5.2
- polarize the network of the RS-485 port; also look at paragraph 5.3
- plug in the termination of the CAN port; also look at paragraph 5.4.
CAN BUS
CAN port.

TERM. MEANING
CAN + signal +

CAN -

signal -

GND

ground

DIGITAL OUTPUTS
- digital outputs 1, 2, 3, 4 and 5 (electromechanical relays).

TERM. MEANING

CO1/2 common digital outputs 1 and 2

NO1

normally open contact digital output 1

NO2

normally open contact digital output 2

NO3

normally open contact digital output 3

CO3/4/5 common digital outputs 3, 4 and 5
CO3/4/5 common digital outputs 3, 4 and 5

NO4

normally open contact digital output 4

NO5

normally open contact digital output 5

- digital output 6 (electromechanical relay).

TERM. MEANING

CO6

common digital output 6

NO6

normally open contact digital output 6

NC6

normally closed contact digital output 6

ANALOG OUTPUTS / OUTPUTS
The analog input 4 is for NTC probes.

TERM. MEANING

AI4

analog input 4

AO1

analog output 1 (PWM signal)

GND

ground

AO2

analog output 2 (configurable via configuration parameter
for 0-20 mA / 4-20 mA / 0-10 V signal)

AO3

analog output 3 (configurable via configuration parameter
for 0-20 mA / 4-20 mA / 0-10 V signal)

The analog output 1 is usable on condition that the controller is sup-
plied in alternate current and the phase supplying the controller is the
same supplying the user driven by the output.
The analog output 1 and the analog output 2 are not independent
each other but they work in the same way.
DIGITAL INPUTS

TERM. MEANING

COM

common digital inputs

DI1

digital input 1

DI2

digital input 2

DI3

digital input 3

DI4

digital input 4

DI5

digital input 5

The digital inputs are usable on condition that they are supplied at 24
VAC / DC.
ANALOG INPUTS
The analog inputs 1, 2 and 3 are configurable via configuration param-
eter for PTC / NTC / Pt 1000 probes / 0-20 mA / 4-20 mA / 0-5 V ratiometric
/ 0-10 V transducers.

TERM. MEANING

AI1

analog input 1

AI2

analog input 2

AI3

analog input 3

GND

ground

GB

ENGLISH

1

GETTING STARTED

1.1

Important

Read these instructions carefully before installing and using the control-
ler and follow all additional information for installation and electrical
connection; keep these instructions close to the controller for future
consultations.

The controller must be disposed according to the local
legislation about the collection for electrical and electronic
equipment.

2

INTRODUCTION

2.1

Introduction

c-pro 3 hecto+ is a family of programmable controllers.
The family is available in the version:
• with 128 x 64 pixel single colour LCD graphic display (black with

rearlighting through white LED) and with a 6 buttons (with preset
functions) keyboard made of silicone rubber integrated in the control-
ler, hereinafter also called built-in versions

• blind (usable for example with an user interface such as

Vgraph or

Vtouch), hereinafter also called blind versions.

The controllers have got:
- real time clock
- alarm buzzer (not available in the blind versions)
- 4 analog inputs of which 3 configurable via configuration parameter

for PTC / NTC / Pt 1000 probes / 0-20 mA / 4-20 mA / 0-5 V ratiometric
/ 0-10 V transducers and 1 for NTC probes

- 5 optoisolated digital inputs at 24 VAC / DC
- 3 analog outputs of which 1 non optoisolated PWM output and 2

non optoisolated outputs configurable via configuration parameter
for 0-20 mA / 4-20 mA / 0-10 V signal

- 6 digital outputs (electromechanical relays) of which five

3 res. A @ 250 VAC SPST outputs and one 5 res. A @ 250 VAC SPDT
output

- 3 non optoisolated communication ports of which 1 CAN port with

CANbus communication protocol, 1 RS-485 port with Modbus
master / slave communication protocol (configurable via application
software) and 1 programming and debugging port.

Through the I/O expansion

c-pro 3 EXP hecto or c-pro 3 EXP hecto+

it is possible to increase the number of inputs and outputs.
Through the development environment UNI-PRO 3 (to order separately)
it is possible to realize the application software and through the pro-
gramming kit EVIF20TUXI (to order separately) it is possible to program
the controller.
The devices look in case 4 DIN modules.
Installation is in electrical panel, on DIN rail.
Through the programming key EVKEY10 (to order separately) it is also
possible to make the upload and the download of the configuration
parameters.
For further information please consult the

Hardware manual of

c-pro 3.
3

DESCRIPTION

3.1

Description

The following table shows the meaning of the parts of the controller.

PART

MEANING

1

RS-485 port with Modbus master / slave communication
protocol

2

micro-switch to:
- plug in the termination of the RS-485 port
- polarize the network of the RS-485 port
- plug in the termination of the CAN port

3

CAN port

4

digital outputs

5

display and keyboard (not available in the blind versions)

6

analog outputs

7

analog inputs

8

programming and debugging port

9

power supply

10

digital inputs

11

signalling LEDs

4

SIZE AND INSTALLATION

4.1

Size

4 DIN modules; size in mm (in).

4.2

Installation

On DIN rail 35.0 x 7.5 mm (1.377 x 0.295 in) or 35.0 x 15.0 mm
(1.377 x 0.590 in).
To install

c-pro 3 hecto+ operate as shown in the following drawing.

To remove

c-pro 3 hecto+ remove possible extractable screw terminal

blocks plugged at the bottom first, then operate on the DIN rail clips
with a screwdriver as shown in the following drawing.

To install

c-pro 3 hecto+ again press the DIN rail clips to the end first.

4.3

Additional information for installation

• working conditions (working temperature, humidity, etc.) must be be-

tween the limits indicated in the technical data

• do not install the controller close to heating sources (heaters, hot air

ducts, etc.), devices provided with big magnetos (big speakers, etc.),
locations subject to direct sunlight, rain, humidity, dust, mechanical
vibrations or bumps

• according to the safety legislation, the protection against electrical

parts must be ensured by a correct installation of the controller; the
parts that ensure the protection must be installed so that you can not
remove them if not by using a tool.

+5V

power supply 0-5 V ratiometric transducers (5 VDC,
40 mA max.)

+24V

power supply 0-20 mA / 4-20 mA / 0-10 V transducers
(24 VDC, 120 mA max.)

PROG
Programming and debugging port.
POWER SUPPLY

TERM. MEANING

V≅

power supply controller (24 VAC / 20... 40 VDC)

V≅

power supply controller (24 VAC / 20... 40 VDC)

If the controller is supplied in direct current, one will not have to respect
the polarity of the power supply voltage.
5.2

Plugging in the termination of the RS-485 port

Position micro-switch 1 on position ON to plug in the termination of the
RS-485 port.

5.3

Polarizing the network of the RS-485 port

Position micro-switches 2 and 3 on position ON to polarize the network
of the RS-485 port.

5.4

Plugging in the termination of the CAN port

Position micro-switch 4 on position ON to plug in the termination of the
CAN port.

5.5

Additional information for electrical connection

• do not operate on the terminal blocks with electrical or pneumatic

screwers

• if the controller has been moved from a cold location to a warm one,

the humidity could condense on the inside; wait about an hour be-
fore supplying it

• test the working power supply voltage, working electrical frequency

and working electrical power of the controller; they must correspond
with the local power supply

• connect the controller to the other devices using a twisted pair
• disconnect the local power supply before servicing the controller
• do not use the controller as safety device
• for repairs and information on the controller please contact EVCO

sales network.

6

SIGNALS

6.1

LEDs at the front of the controller

LED

MEANING

ON

LED power supply
if it is lit, the controller will be supplied
if it is out, the controller will not be supplied

RUN

LED run
if it is lit, the application software will be compiled and run-
ning in release modality
if it flashes slowly, the application software will be compiled
and running in debug modality
if it flashes quickly, the application software will be compiled,
running in debug modality and stopped in a breakpoint
if it is out:
- the controller will not be compatible with the application

software

- the controller will not be enabled to work with the special

ABL (Application Block Libraries)

LED system alarm
if it is lit, an alarm system not resettable via software will be
running
if it flashes slowly, a system alarm with automatic reset will
be running
if it flashes quickly, a system alarm with manual reset will be
running
if it is out, no alarm system will be running

CAN

LED CANbus communication
if it is lit, the controller will be configured to communicate
via CANbus with another device but the CAN communica-
tion will not have been set up
if it flashes slowly, the CANbus communication will have been
set up but it will not be completely correct
if it flashes quickly, the CANbus communication will have
been set up and will be correct
if it is out, no CANbus communication will be running

L1

LED auxiliary
The operation of this LED can be programmed through the
development environment UNI-PRO 3

6.2

LEDs of the RS-485 port

COLOUR MEANING

yellow LED Modbus communication

if it is lit, no Modbus communication will be running
if it flashes quickly, the Modbus communication will have
been set up and will be correct
if it is out, the controller will not be configured to communi-
cate via Modbus

red

LED Error
if it is lit, an internal error will have arisen
if it flashes quickly, a configuration error will have arisen
if it is out, no error will be running

7

TECHNICAL DATA

7.1

Technical data

Purpose of control: programmable controller for applications in re-
frigeration, ventilation and air conditioning.
Construction of control: electronic control device to be incorpo-
rated.
Box: self-extinguishing grey.
Size: 71.0 x 128.0 x 60.0 mm (2.795 x 5.039 x 2.362 in); 4 DIN mod-
ules.
Size refers to the controller with all the connectors properly plugged.
Installation: on DIN rail 35.0 x 7.5 mm (1.377 x 0.295 in) or
35.0 x 15.0 mm (1.377 x 0.590 in).
Index of protection: IP20; IP40 the front.
Connections: male extractable screw terminal blocks pitch 5.0 mm
(0.196 in; power supply, inputs, outputs and CAN port) for conductors
up to 2.5 mm² (0.0038 in²), 8 poles female telephone connector
(RS-485 port), 6 poles female telephone connector (programming and
debugging port).
The maximum lengths of the connecting cables are the followings:
• power supply controller: 30 m (98 ft)
• analog inputs: 100 m (328 ft)
• power supply transducers: 100 m (328 ft)
• digital inputs: 100 m (328 ft)
• PWM analog output: 1 m (3.280 ft)
• 0-20 mA / 4-20 mA / 0-10 V analog outputs: 30 m (98 ft)
• digital outputs (electromechanical relays): 100 m (328 ft)
• RS-485 port: 1,000 m (3,280 ft); also look at the

Modbus specifications

and implementation guides manual

• CAN port:
- 1,000 m (3,280 ft) with baud rate 20,000 baud
- 500 m (1,640 ft) with baud rate 50,000 baud
- 250 m (820 ft) with baud rate 125,000 baud
- 50 m (164 ft) with baud rate 500,000 baud.
One suggests using the connecting kit CJAV15 (female extractable screw
terminal blocks pitch 5.0 mm, 0.196 in; to order separately).
To program the controller one has to use the programming kit
EVIF20TUXI (TTL / USB isolated serial interface + TTL cable 2.5 m, 8 ft
long + USB cable 2 m, 6 ft long; to order separately).
Working temperature: from -10 to 55 °C (14 to 131 °F) for the
built-in versions, from -20 to 55 °C (-4 to 131 °F) for the blind versions.
Working humidity: from 5 to 95% of relative humidity without con-
densate.
Pollution situation: 2.
Power supply: 24 VAC, 50 / 60 Hz, 30 VA max. or 20... 40 VDC,
22 W max, supplied from a class 2 circuit.
Protect the power supply with a fuse rated 0.8A-T 250 V.
Overvoltage category: III.
Real time clock: incorporated (with SuperCap battery).
Real time clock data maintenance in absence of power sup-
ply: 3 days will battery fully charged.
Alarm buzzer: incorporated (not available in the blind versions).
Analog inputs: 4 inputs, of which 3 configurable via configuration
parameter for PTC / NTC / Pt 1000 probes / 0-20 mA / 4-20 mA / 0-5 V
ratiometric / 0-10 V transducers and 1 for NTC probes.
Power supply 0-5 V ratiometric transducers: 5 VDC, 40 mA max.
Power supply 0-20 mA / 4-20 mA / 0-10 V transducers: 24 VDC, 120 mA
max.
Working range: from -50 to 150 °C (-58 to 302 °F) for PTC probe,
from -50 to 120 °C (-58 to 248 °F) for NTC probe, from -100 to 400 °C
(-148 to 752 °F) for Pt 1000 probe.
Digital inputs: 5 optoisolated inputs at 24 VAC / DC.
Resolution: 0.1 °C for PTC / NTC probes, 0.1 °C for Pt 1000 probes,
0.01 mA for 0-20 mA / 4-20 mA transducers, 0.01 V for 0-10 V transduc-
ers.
Analog outputs: 3 outputs:
• 1 non optoisolated PWM output
• 2 non optoisolated outputs configurable via configuration parameter

for 0-20 mA / 4-20 mA / 0-10 V signal.

Power supply driving the PWM analog output: 24 VDC, 50 mA max.
Digital outputs: 6 outputs (electromechanical relays):
• five 3 res. A @ 250 VAC SPST outputs (K1, K2, K3, K4 and K5)
• one 5 res. A @ 250 VAC SPDT output (K6).
Type of actions and additional features: 1B.

Communication ports: 3 non optoisolated ports:
• 1 CAN port with CANbus communication protocol
• 1 RS-485 port with Modbus master / slave communication protocol

(configurable via application software)

• 1 programming and debugging port.
Program memory: 288 KB (FLASH memory).
Data memory: 12 KB (RAM memory).

I

ITALIANO

1

IMPORTANTE

1.1

Importante

Leggere attentamente queste istruzioni prima dell’installazione e prima
dell’uso e seguire tutte le avvertenze per l’installazione e per il collega-
mento elettrico; conservare queste istruzioni con il controllore per con-
sultazioni future.

Il controllore deve essere smaltito secondo le normative
locali in merito alla raccolta delle apparecchiature elettriche
ed elettroniche.

2

INTRODUZIONE

2.1

Introduzione

c-pro 3 hecto+ è una famiglia di controllori programmabili.
La famiglia è disponibile nella versione:
• con visualizzatore grafico LCD monocolore (nero con retroilluminazione

a LED bianchi) da 128 x 64 pixel e con tastiera in gomma siliconica a 6
tasti (con funzioni predefinite) integrati nel controllore, in seguito de-
nominate anche versioni built-in

• cieca (utilizzabile per esempio con un terminale utente come

Vgraph

o

Vtouch), in seguito denominate anche versioni cieche.

I controllori dispongono di:
- orologio
- buzzer di allarme (non disponibile nelle versioni cieche)
- 4 ingressi analogici di cui 3 configurabili via parametro di configura-

zione per sonde PTC / NTC / Pt 1000 / trasduttori 0-20 mA / 4-20 mA
/ 0-5 V raziometrici / 0-10 V e 1 per sonde NTC

- 5 ingressi digitali optoisolati a 24 VAC / DC
- 3 uscite analogiche di cui 1 non optoisolata di tipo PWM e 2 non

optoisolate configurabili via parametro di configurazione per segnale
di tipo 0-20 mA / 4-20 mA / 0-10 V

- 6 uscite digitali (relè elettromeccanici) di cui 5 da 3 A res. @ 250 VAC di

tipo SPST e 1 da 5 A res. @ 250 VAC di tipo SPDT

- 3 porte di comunicazione non optoisolate di cui 1 di tipo CAN con

protocollo di comunicazione CANbus, 1 di tipo RS-485 con protocollo
di comunicazione Modbus master / slave (configurabile via software
applicativo) e 1 per la programmazione e il debug.

Attraverso l’espansione di I/O

c-pro 3 EXP hecto o c-pro 3 EXP hecto+

è possibile incrementare il numero di ingressi e di uscite.
Attraverso l’ambiente di sviluppo UNI-PRO 3 (da ordinare separatamente)
è possibile realizzare il software applicativo e attraverso il kit di program-
mazione EVIF20TUXI (da ordinare separatamente) è invece possibile pro-
grammare il controllore.
I dispositivi si presentano in contenitore 4 moduli DIN.
L'installazione è prevista in un quadro elettrico, su guida DIN.
Attraverso la chiave di programmazione EVKEY10 (da ordinare
separatamente) è possibile eseguire l'upload e il download dei parame-
tri di configurazione.
Per ulteriori informazioni consultare il

Manuale hardware di c-pro 3.

3

DESCRIZIONE

3.1

Descrizione

La seguente tabella illustra il significato delle parti del controllore.

PARTE SIGNIFICATO

1

porta RS-485 con protocollo di comunicazione Modbus
master / slave

2

micro-switch per:
- inserire la terminazione della porta RS-485
- polarizzare la rete della porta RS-485
- inserire la terminazione della porta CAN

3

porta CAN

4

uscite digitali

Advertising
Questo manuale è associato alle seguenti prodotti: