EVCO EPU2BXP1S1 Manuale d'uso

Pagina 66

Advertising
background image

EVCO S.p.A.

c-pro 3 micro SAVE/c-pro 3 kilo SAVE | Manuale applicativo ver. 1.0 | Codice 144CP3UKSAI104

pagina 66 di 68

0x0691

1682

PF17_Ti

0

0

300

R/W

0x0692

1683

PF30_MinSpeedFan

0.00

0.00

100.00

PF03 - Min speed fan

R/W

0x0693

1684

PF31_MaxSpeedFan

100.00

0.00

100.00

PF04 - Max speed fan

R/W

0x0694

1685

PF32_StaticPressSetPointRamp

300

0

30000

R/W

0x0695

1686

PF33_StaticPressSetPoint1

300

0

30000

R/W

0x0696

1687

PF34_StaticPressSetPoint2

400

0

30000

R/W

0x0697

1688

PF35_StaticPressSetPoint3

500

0

30000

R/W

0x0698

1689

PF36_StaticPressPropBand

200

0

10000

R/W

0x0699

1690

PF37_StaticPressIntegralTime

0

0

300

R/W

0x069A 1691

PF38_ForceOnErrorProbe

30.00

0.00

100.00

R/W

0x069B 1692

PG11_Recyclage

0

0

1

0=Disable, 1=Enable

R/W

0x069C 1693

PS06_EnableFreeHeating

0

0

1

0=Disable, 1=Enable

R/W

0x069D 1694

PS07_Type_ControlShutter

0

0

4

0=FreeCooling/Heating,
1=AirQuality,
2=Greater 3=Avarage
4=Fixed

R/W

0x069E

1695

PS08_MinRegulationValue_AirExternalShutter

20.00

0.00

100.00

R/W

0x069F

1696

PS09_MaxRegulationValue_AirExternalShutter

100.00

0.00

100.00

R/W

0x06A0 1697

PS10_FixRegulationValue_AirExternalShutter

50.00

0.00

100.00

R/W

0x06A1 1698

PS12_FreeCoolingHeatingTemp_enDiff

2.0

0.0

36.0

R/W

0x06A2 1699

PS13_FreeCoolingHeatingTemp_enSetPoint

4.0

0.0

68.0

R/W

0x06A3 1700

PS15_EnableMinVal_AirExternalShutter

0

0

2

0=Disable, 1=Only
Band, 2=Always

R/W

0x06A4 1701

PS20_AirQuality_SetPoint

600

0

10000

R/W

0x06A5 1702

PS21_AirQuality_Diff

100

0

2000

R/W

Advertising
Questo manuale è associato alle seguenti prodotti: