EVCO EPU2BXP1S1 Manuale d'uso

Pagina 61

Advertising
background image

EVCO S.p.A.

c-pro 3 micro SAVE/c-pro 3 kilo SAVE | Manuale applicativo ver. 1.0 | Codice 144CP3UKSAI104

pagina 61 di 68

Bit16=AL16

0x0301

770

PackedAlarm_2

0

0

65535

Bit1=AL17,
Bit2=AL18,
Bit3=AL19,
Bit4=AL20,
Bit5=AL21,
Bit6=AL22,
Bit7=AL23, Bit8=Free,
Bit9=AL25,
Bit10=AL26,
Bit11=AL27,
Bit12=AL28,
Bit13=AL29

R/W

0x0400

1025

Status_OnOff_bySUP

0

0

1

R/W

0x0500

1281

CLOCK_RTC ( Low )

-

01/01/2000

19/01/2068

03:14:07

R/W

0x0501

1282

CLOCK_RTC ( High )

0x0502

1283

StatusUnit

0

0

5

R/W

0x0503

1284

UI_MainLabelDown

0

0

8

R/W

0x0504

1285

Status_SupplyFan

0

0

9

0=Disabilitato, 1=OFF,
2=Wait ON, 3=ON,
4=Wait OFF, 5=ALL,
6=Manual

R/W

0x0505

1286

Status_ReturnFan

0

0

9

0=Disabilitato, 1=OFF,
2=Wait ON, 3=ON,
4=Wait OFF, 5=ALL,
6=Manual

R/W

0x0506

1287

UI_byPassAntiFreeze

0

0

1

R/W

0x0507

1288

Status_AirNEUF

0

0

5

R/W

0x0508

1289

byPassRecover_Summer

0

0

1

R/W

0x0509

1290

Status_Resistor1

0

0

5

0=Disabilitato, 1=OFF,
2=Wait ON, 3=ON,
4=Wait OFF, 5=ALL

R/W

0x050A 1291

Status_Resistor2

0

0

5

0=Disabilitato, 1=OFF,
2=Wait ON, 3=ON,
4=Wait OFF, 5=ALL

R/W

0x050B 1292

Status_Resistor3

0

0

5

0=Disabilitato, 1=OFF,
2=Wait ON, 3=ON,
4=Wait OFF, 5=ALL

R/W

0x050C 1293

active_ProbeHeating

0.0

-3276.8

3276.7

R/O

0x050D 1294

active_SetPointHeating

0.0

-20.0

230.0

R/W

0x050E

1295

active_HeatingPower

0.00

0.00

100.00

R/W

0x050F

1296

Status_MixAirShutter

0

0

5

R/W

0x0510

1297

Request_AirQuality

0.00

0.00

100.00

R/W

0x0511

1298

Req_FreeCoolingHeating

0.00

0.00

100.00

R/W

0x0606

1543

SPHR_SetPoint_Return

20.0

-20.0

230.0

R/W

0x0607

1544

SPHM_SetPoint_Supply

22.0

-20.0

230.0

R/W

Advertising
Questo manuale è associato alle seguenti prodotti: