EVCO EVK002N7 Manuale d'uso

Pagina 2

Advertising
background image

EVCO S.p.A.

This document belongs to Evco; unless you are authorized by Evco, you can not publish it.

Via Mezzaterra 6, 32036 Sedico Belluno ITALY

Evco does not take any responsibility about features, technical data and possible mistakes related in this document or coming by its use.

Phone +39-0437-852468 • Fax +39-0437-83648

Evco does not take any responsibility about damages coming by the non-observance of the additional information.

[email protected] • www.evco.it

Evco reserves the right to make any change without prior notice and at any time without prejudice the basic safety and operating features.

PT • 35/10

GB ENGLISH

9

WORKING SETPOINTS AND CONFIGURATION PARAMETERS

9.1 Working setpoints

MIN.

MAX.

U.M.

DEF.

WORKING SETPOINTS

r1

r2

°C/°F (1) 0.0

working setpoint

9.2 Configuration parameters
PARAM. MIN.

MAX.

U.M.

DEF.

WORKING SETPOINTS

SP1

r1

r2

°C/°F (1) 0.0

working setpoint

SP2

-99.0

99.0

°C/°F (1) -30.0

temperature below which the auxiliary output is
turned on; also look at r12 and r13

PARAM. MIN.

MAX.

U.M.

DEF.

MEASURE INPUTS

CA1

-25.0

25.0

°C/°F (1) 0.0

cabinet probe offset

P0

0

1

- - -

1

kind of probe
0 = PTC
1 = NTC

P1

0

1

- - -

1

decimal point Celsius degree (for the quantity to
show during the normal operation)
1 = YES

P2

0

1

- - -

0

unit of measure temperature (2)
0 = °C
1 = °F

P5

0

1

- - -

0

quantity to show during the normal operation
0 = cabinet temperature
1 = working setpoint

PARAM. MIN.

MAX.

U.M.

DEF.

REGULATORS

r0

0.1

15.0

°C/°F (1) 2.0

working setpoint differential

r1

-99.0

r2

°C/°F (1) -50.0

minimum working setpoint

r2

r1

99.0

°C/°F (1) 50.0

maximum working setpoint

r3

0

1

- - -

0

locking the working setpoint modification (with the
procedure related in paragraph 4.1)
1 = YES

r12

0

2

- - -

0

kind of parameter SP2
0 = the auxiliary output will never be turned on
1 = relative to the working setpoint (or "working

setpoint - SP2”; consider SP2 without sign)

2 = absolute (or SP2)

r13

0.1

15.0

°C/°F (1) 2.0

differential of parameter SP2

PARAM. MIN.

MAX.

U.M.

DEF.

LOAD PROTECTIONS

C0

0

240

min

0

compressor delay since you turn on the instrument

C1

0

240

min

5

minimum time between two activations in succes-
sion of the compressor; also compressor delay since
the end of the cabinet probe error (3)

C2

0

240

min

3

minimum time the compressor remains turned off

C3

0

240

s

0

minimum time the compressor remains turned on

C4

0

240

min

10

time the compressor remains turned off during the
cabinet probe error; also look at C5

C5

0

240

min

10

time the compressor remains turned on during the
cabinet probe error; also look at C4

C11

0

240

min

0

auxiliary output delay since the compressor gets
turned off

PARAM. MIN.

MAX.

U.M.

DEF.

DEFROST

d0

0

99

h

8

defrost interval; also look at d8 (5)
0 = the defrost at intervals will never be activated

d3

0

99

min

30

defrost duration
0 = the defrost will never be activated

d4

0

1

- - -

0

defrost when you turn on the instrument
1 = YES

d5

0

99

min

0

defrost delay when you turn on the instrument (only
if d4 = 1)

d6

0

1

- - -

1

temperature shown during the defrost
0 = cabinet temperature
1 = if to the defrost activation the cabinet tempera-

ture is below “working setpoint + r0”, at most
“working setpoint + r0”; if to the defrost activa-
tion the cabinet temperature is above “work-
ing setpoint + r0”, at most the cabinet tempera-
ture to the defrost activation (6)

d8

0

1

- - -

0

kind of defrost interval
0 = the defrost will be activated when the instru-

ment will have remained turned on the time
d0

1 = the defrost will be activated when the compres-

sor will have remained turned on the time d0

PARAM. MIN.

MAX.

U.M.

DEF.

TEMPERATURE ALARMS

A1

-99.0

99.0

°C/°F (1) -10.0

temperature below which the lower temperature
alarm is activated; also look at A2 (4)

A2

0

2

- - -

1

kind of lower temperature alarm
0 = alarm not enabled
1 = relative to the working setpoint (or "working

setpoint - A1”; consider A1 without sign)

2 = absolute (or A1)

A4

-99.0

99.0

°C/°F (1) 10.0

temperature above which the upper temperature
alarm is activated; also look at A5 (4)

A5

0

2

- - -

1

kind of upper temperature alarm
0 = alarm not enabled
1 = relative to the working setpoint (or "working

setpoint + A4”; consider A4 without sign)

2 = absolute (or A4)

A6

0

240

min

120

upper temperature alarm delay since you turn on
the instrument

A7

0

240

min

15

temperature alarm delay

A8

0

240

min

15

upper temperature alarm delay since the end of the
defrost (7)

PARAM. MIN.

MAX. U.M.

DEF.

SERIAL NETWORK (MODBUS)

LA

1

247

- - -

247

instrument address

Lb

0

3

- - -

2

baud rate
0 = 2,400 baud
1 = 4,800 baud
2 = 9,600 baud
3 = 19,200 baud

LP

0

2

- - -

2

parity
0 = none
1 = odd
2 = even

PARAM. MIN.

MAX. U.M.

DEF.

RESERVED

E9

0

1

- - -

1

reserved

(1)

the unit of measure depends on parameter P2

(2)

set the parameters related to the regulators appropriately after the
modification of the parameter P2

(3)

if parameter C1 has value 0, the delay since the end of the cabinet probe error will
however be 2 min

(4)

the differential of the parameter is 2.0 °C/4 °F

(5)

the instrument stores the count of the defrost interval every 30 min; the modification of
parameter d0 has effect since the end of the previous defrost interval or since the
activation of a defrost by hand

(6)

the display restores the normal operation as soon as the defrost ends and the cabinet
temperature falls below the one that has locked the display (or if a temperature alarm
arises)

(7)

during the defrost the temperature alarms are not enabled, on condition that they have
arisen after the activation of the defrost.

The instrument must be disposed according to the local legislation about the collection
for electrical and electronic equipment.
Lo strumento deve essere smaltito secondo le normative locali in materia di raccolta
delle apparecchiature elettriche ed elettroniche.

I ITALIANO

9

SETPOINT DI LAVORO E PARAMETRI
DI CONFIGURAZIONE

9.1 Setpoint di lavoro
SETPOINT DI LAVORO
setpoint di lavoro
9.2 Parametri di configurazione
SETPOINT DI LAVORO
setpoint di lavoro
temperatura al di sotto della quale l’uscita ausiliaria
viene accesa; si vedano anche r12 ed r13
INGRESSI DI MISURA
offset sonda cella
tipo di sonda
0 = PTC
1 = NTC
punto decimale grado Celsius (per la grandezza
visualizzata durante il normale funzionamento)
1 = SI
unità di misura temperatura (2)
0 = °C
1 = °F
grandezza visualizzata durante il normale funziona-
mento
0 = temperatura della cella
1 = setpoint di lavoro
REGOLATORI
differenziale del setpoint di lavoro
minimo setpoint di lavoro
massimo setpoint di lavoro
blocco della modifica del setpoint di lavoro (con la
procedura indicata nel paragrafo 4.1)
1 = SI
tipo di parametro SP2
0 = l’uscita ausiliaria non verrà mai accesa
1 = relativo al setpoint di lavoro (ovvero “setpoint

di lavoro - SP2”; considerare SP2 senza segno)

2 = assoluto (ovvero SP2)
differenziale del parametro SP2
PROTEZIONI DEI CARICHI
ritardo compressore dall’accensione dello strumen-
to
tempo minimo tra due accensioni consecutive del
compressore; anche ritardo compressore dalla con-
clusione dell’errore sonda cella (3)
durata minima dello spegnimento del compressore
durata minima dell’accensione del compressore
durata dello spegnimento del compressore duran-
te l’errore sonda cella; si veda anche C5
durata dell’accensione del compressore durante l’er-
rore sonda cella; si veda anche C4
ritardo uscita ausiliaria dallo spegnimento del com-
pressore
SBRINAMENTO
intervallo di sbrinamento; si veda anche d8 (5)
0 = lo sbrinamento a intervalli non verrà mai attiva-

to

durata dello sbrinamento
0 = lo sbrinamento non verrà mai attivato
sbrinamento all’accensione dello strumento
1 = SI
ritardo sbrinamento dall’accensione dello strumen-
to (solo se d4 = 1)
temperatura visualizzata durante lo sbrinamento
0 = temperatura della cella
1 = se all’attivazione dello sbrinamento la tempera-

tura della cella è al di sotto di “setpoint di lavo-
ro + r0”, al massimo “setpoint di lavoro + r0”; se
all’attivazione dello sbrinamento la temperatu-
ra della cella è al di sopra di “setpoint di lavoro
+ r0”, al massimo la temperatura della cella al-
l’attivazione dello sbrinamento (6)

tipo di intervallo di sbrinamento
0 = lo sbrinamento verrà attivato quando lo stru-

mento sarà rimasto acceso per il tempo d0

1 = lo sbrinamento verrà attivato quando il com-

pressore sarà rimasto acceso per il tempo d0

ALLARMI DI TEMPERATURA
temperatura al di sotto della quale viene attivato
l’allarme di temperatura di minima; si veda anche
A2 (4)
tipo di allarme di temperatura di minima
0 = allarme assente
1 = relativo al setpoint di lavoro (ovvero “setpoint

di lavoro - A1”; considerare A1 senza segno)

2 = assoluto (ovvero A1)
temperatura al di sopra della quale viene attivato
l’allarme di temperatura di massima; si veda anche
A5 (4)
tipo di allarme di temperatura di massima
0 = allarme assente
1 = relativo al setpoint di lavoro (ovvero “setpoint

di lavoro + A4”; considerare A4 senza segno)

2 = assoluto (ovvero A4)

ritardo allarme di temperatura di massima dall’ac-
censione dello strumento
ritardo allarme di temperatura
ritardo allarme di temperatura di massima dalla con-
clusione dello sbrinamento (7)
RETE SERIALE (MODBUS)
indirizzo strumento
baud rate
0 = 2.400 baud
1 = 4.800 baud
2 = 9.600 baud
3 = 19.200 baud
parità
0 = nessuna parità
1 = dispari
2 = pari
RISERVATO
riservato
(1) l’unità di misura dipende dal parametro P2
(2)

impostare opportunamente i parame-
tri relativi ai regolatori dopo la modi-
fica del parametro P2

(3) se il parametro C1 è impostato a 0, il ritardo

dalla conclusione dell’errore sonda cella sarà
comunque di 2 min

(4) il differenziale del parametro è di 2,0 °C/4 °F
(5) lo strumento memorizza il conteggio dell’in-

tervallo di sbrinamento ogni 30 min; la modi-
fica del parametro d0 ha effetto dalla conclu-
sione del precedente intervallo di sbrinamento
o dall’attivazione di uno sbrinamento in modo
manuale

(6) il display ripristina il normale funzionamento

quando, concluso lo sbrinamento, la tempe-
ratura della cella scende al di sotto di quella
che ha bloccato il display (o se si manifesta un
allarme di temperatura)

(7) durante lo sbrinamento gli allarmi di tempera-

tura sono assenti, a condizione che questi si
siano manifestati dopo l’attivazione dello
sbrinamento.

Advertising