DATI TECNICI

8.1 Dati tecnici
Contenitore: autoestinguente grigio.
Grado di protezione del frontale: IP 65.
Connessioni (usare solo conduttori in rame): morsettiere a vite
(alimentazione, ingressi e uscite), connettore a 6 poli (porta seriale; su
richiesta); morsettiere estraibili (alim., ingressi e uscite) su richiesta.
Temperatura di impiego: da 0 a 55 °C (10 ... 90% di umidità relati-
va senza condensa).
Alimentazione: 230 VCA, 50/60 Hz, 3 VA (approssimativi); 115 VCA
o 12-24 VCA/CC o 12 VCA/CC su richiesta.
Classe di isolamento: 2.
Buzzer di allarme: su richiesta.
Ingressi di misura: 1 (sonda ambiente) per sonde PTC/NTC.
Ingressi digitali: 1 (multif.) per cont. NA/NC (cont. pulito, 5 V 1 mA).

GB ENGLISH

9

WORKING SETPOINTS AND CONFIGURATION PARAMETERS

9.1 Working setpoints

MIN.

MAX.

U.M.

DEF.

WORKING SETPOINTS

r1

r2

°C/°F (1) 0.0

working setpoint

9.2 Configuration parameters
PARAM. MIN.

MAX.

U.M.

DEF.

WORKING SETPOINTS

SP

r1

r2

°C/°F (1) 0.0

working setpoint

PARAM. MIN.

MAX.

U.M.

DEF.

MEASURE INPUTS

CA1

-25.0

25.0

°C/°F (1) 0.0

room probe offset

P0

0

1

- - -

0

kind of probe
0 = PTC
1 = NTC

P1

0

1

- - -

1

decimal point Celsius degree (for the quantity to
show during the normal operation)
1 = YES

P2

0

1

- - -

0

unit of measure temperature (2)
0 = °C
1 = °F

P5

0

1

- - -

0

quantity to show during the normal operation
0 = room temperature
1 = working setpoint

PARAM. MIN.

MAX.

U.M.

DEF.

MAIN REGULATOR

r0

0.1

99.0

°C/°F (1) 2.0

working setpoint differential

r1

-99.0

r2

°C/°F (1) 0.0

minimum working setpoint

r2

r1

(3)

°C/°F (1) 150.0 maximum working setpoint

r3

0

1

- - -

0

locking the working setpoint modification (with the
procedure related in paragraph 4.1)
1 = YES

r4

-99.0

99.0

°C/°F (1) 0.0

temperature variation during function Energy Sav-
ing; also look at i5

r5

0

1

- - -

(4)

cooling or heating action
0 = cooling

PARAM. MIN.

MAX.

U.M.

DEF.

LOAD PROTECTIONS

C1

0

240

min

0

minimum time between two activations in succes-
sion of the load; also load delay since the end of
the room probe error (5)

C2

0

240

min

0

minimum time the load remains turned off; also load
delay since you turn on the instrument

C3

0

240

s

0

minimum time the load remains turned on

C4

0

240

min

10

time the load remains turned off during the room
probe error; also look at C5

C5

0

240

min

10

time the load remains turned on during the room
probe error; also look at C4

PARAM. MIN.

MAX.

U.M.

DEF.

DEFROST (6)

d0

0

99

h

8

defrost interval (7)
0 = the defrost at intervals will never be activated

d3

0

99

min

0

defrost duration
0 = the defrost will never be activated

d4

0

1

- - -

0

defrost when you turn on the instrument
1 = YES

d5

0

99

min

0

defrost delay when you turn on the instrument (only
if d4 = 1)

d6

0

1

- - -

1

temperature shown during the defrost
0 = room temperature
1 = if to the defrost activation the room tempera-

ture is below “working setpoint + r0”, at most
“working setpoint + r0”; if to the defrost activa-
tion the room temperature is above “working
setpoint + r0”, at most the room temperature
to the defrost activation (8)

PARAM. MIN.

MAX.

U.M.

DEF.

TEMPERATURE ALARMS

A1

-99.0

(3)

°C/°F (1) 0.0

temperature the first temperature alarm is activated;
also look at A3 (9)

A2

0

240

min

0

first temperature alarm delay (10)

A3

0

4

- - -

0

kind of first temperature alarm
0 = alarm not enabled
1 = absolute lower alarm (or A1)
2 = absolute upper alarm (or A1)
3 = lower alarm relative to the working setpoint (or

"working setpoint - A1”; consider A1 without
sign, do not consider r4)

4 = upper alarm relative to the working setpoint (or

"working setpoint + A1”; consider A1 without
sign, do not consider r4)

A4

0

240

min

0

temperature alarms delay since the working setpoint
modification (10)

I ITALIANO

9

SETPOINT DI LAVORO E PARAMETRI
DI CONFIGURAZIONE

9.1 Setpoint di lavoro
SETPOINT DI LAVORO
setpoint di lavoro
9.2 Parametri di configurazione
SETPOINT DI LAVORO
setpoint di lavoro
INGRESSI DI MISURA
offset sonda ambiente
tipo di sonda
0 = PTC
1 = NTC
punto decimale grado Celsius (per la grandezza
visualizzata durante il normale funzionamento)
1 = SI
unità di misura temperatura (2)
0 = °C
1 = °F
grandezza visualizzata durante il normale funzionam.
0 = temperatura dell’ambiente
1 = setpoint di lavoro
REGOLATORE PRINCIPALE
differenziale del setpoint di lavoro
minimo setpoint di lavoro
massimo setpoint di lavoro
blocco della modifica del setpoint di lavoro (con la
procedura indicata nel paragrafo 4.1)
1 = SI
variazione di temperatura durante la funzione
Energy Saving; si veda anche i5
funzionamento per freddo o per caldo
0 = per freddo
PROTEZIONI DEL CARICO
tempo minimo tra due accensioni consecutive del
carico; anche ritardo carico dalla conclusione del-
l’errore sonda ambiente (5)
durata minima dello spegnimento del carico; an-
che ritardo carico dall’accensione dello strumento
durata minima dell’accensione del carico
durata dello spegnimento del carico durante l’erro-
re sonda ambiente; si veda anche C5
durata dell’accensione del carico durante l’errore
sonda ambiente; si veda anche C4
SBRINAMENTO (6)
intervallo di sbrinamento (7)
0 = lo sbrinam. a intervalli non verrà mai attivato
durata dello sbrinamento
0 = lo sbrinamento non verrà mai attivato
sbrinamento all’accensione dello strumento
1 = SI
ritardo sbrinamento dall’accensione dello strumen-
to (solo se d4 = 1)
temperatura visualizzata durante lo sbrinamento
0 = temperatura dell’ambiente
1 = se all’attivazione dello sbrinamento la tempera-

tura dell’ambiente è al di sotto di “setpoint di
lavoro + r0”, al massimo “setpoint di lavoro +
r0”; se all’attivazione dello sbrinamento la tem-
peratura dell’ambiente è al di sopra di “setpoint
di lavoro + r0”, al massimo la temperatura del-
l’ambiente all’attivazione dello sbrinamento (8)

ALLARMI DI TEMPERATURA
temperatura alla quale viene attivato il primo allar-
me di temperatura; si veda anche A3 (9)
ritardo primo allarme di temperatura (10)
tipo di primo allarme di temperatura
0 = allarme assente
1 = di minima assoluto (ovvero A1)
2 = di massima assoluto (ovvero A1)
3 = di minima relativo al setpoint di lavoro (ovvero

“setpoint di lavoro - A1”; considerare A1 senza
segno, non considerare r4)

4 = di massima relativo al setpoint di lavoro (ovvero

“setpoint di lavoro + A1”; considerare A1 senza
segno, non considerare r4)

ritardo allarmi di temperatura dalla modifica del
setpoint di lavoro (10)

A5

-99.0

(3)

°C/°F (1) 0.0

temperature the second temperature alarm is acti-
vated; also look at A7 (9)

A6

0

240

min

0

second temperature alarm delay (10)

A7

0

4

- - -

0

kind of second temperature alarm
0 = alarm not enabled
1 = absolute lower alarm (or A5)
2 = absolute upper alarm (or A5)
3 = lower alarm relative to the working setpoint (or

"working setpoint - A5”; consider A5 without
sign)

4 = upper alarm relative to the working setpoint (or

"working setpoint + A5”; consider A5 without
sign)

PARAM. MIN.

MAX. U.M.

DEF.

DIGITAL INPUTS

i1

0

1

- - -

0

kind of contact digital input
0 = NO (input active if you close the contact)
1 = NC (input active if you open the contact)

i5

0

3

- - -

0

effect provoked by the activation of the multipur-
pose input
0 = no effect
1 = ACTIVATING THE EXTERNAL ALARM - spent the

time i7 the display will show the code “iA” flash-
ing, the buzzer will be activated and the alarm
output (only EVK402) will be turned on (as long
as the input will be deactivated)

2 = LOAD PROTECTION - the load will be turned

off, the display will show the code “iA” flash-
ing, the buzzer will be activated and the alarm
output (only EVK402) will be turned on (as long
as the input will be deactivated)

3 = ACTIVATING THE ENERGY SAVING - function

Energy Saving will be activated (as long as the
input will be deactivated); also look at r4 (11)

i7

0

120

min

0

if i5 = 1, delay to signal the multipurpose input alarm
if i5 = 2, load delay since the deactivation of the
multipurpose input

PARAM. MIN.

MAX. U.M.

DEF.

SERIAL NETWORK (MODBUS)

LA

1

247

- - -

247

instrument address

Lb

0

3

- - -

2

baud rate
0 = 2,400 baud
1 = 4,800 baud
2 = 9,600 baud
3 = 19,200 baud

LP

0

2

- - -

2

parity
0 = none
1 = odd
2 = even

PARAM. MIN.

MAX. U.M.

DEF.

RESERVED

E9

0

1

- - -

1

reserved

(1)

the unit of measure depends on parameter P2

(2)

set the parameters related to the regulators appropriately after the
modification of the parameter P2

(3)

the value depends on parameter P2 (150.0 °C or 300 °F)

(4)

the value depends on the instrument code, as follows (example for EVK421):

The question mark (?) replaces one field, the asterisk (*) replaces one or
more fields (or no-one); the field C means cooling, the field H means heating

(5)

if parameter C1 has value 0, the delay since the end of the room probe error will
however be 2 min

(6)

if parameter r5 has value 1 (heating action), the defrost functions will not be enabled

(7)

the instrument stores the count of the defrost interval every 30 min; the modification of
parameter d0 has effect since the end of the previous defrost interval or since the
activation of a defrost by hand

(8)

the display restores the normal operation as soon as the defrost ends and the room
temperature falls below the one that has locked the display (or if a temperature alarm
arises)

(9)

the differential of the parameter is 2.0 °C/4 °F

(10)

during the defrost the temperature alarms are not enabled, on condition that they have
arisen after the activation of the defrost

(11)

the effect is not signalled.

The instrument must be disposed according to the local legislation about the collection
for electrical and electronic equipment.
Lo strumento deve essere smaltito secondo le normative locali in materia di raccolta
delle apparecchiature elettriche ed elettroniche.

temperatura alla quale viene attivato il secondo al-
larme di temperatura; si veda anche A7 (9)
ritardo secondo allarme di temperatura (10)
tipo di secondo allarme di temperatura
0 = allarme assente
1 = di minima assoluto (ovvero A5)
2 = di massima assoluto (ovvero A5)
3 = di minima relativo al setpoint di lavoro (ovvero

“setpoint di lavoro - A5”; considerare A5 senza
segno)

4 = di massima relativo al setpoint di lavoro (ovvero

“setpoint di lavoro + A5”; considerare A5 senza
segno)

INGRESSI DIGITALI
tipo di contatto dell’ingresso digitale
0 = NA (ingresso attivo con contatto chiuso)
1 = NC (ingresso attivo con contatto aperto)
effetto provocato dall'attivazione dell’ingresso
multifunzione
0 = nessun effetto
1 = ATTIVAZIONE ALLARME ESTERNO - trascorso il

tempo i7 il display visualizzerà il codice “iA” lam-
peggiante, il buzzer verrà attivato e l’uscita di
allarme (solo EVK402) verrà accesa (fino a quan-
do l’ingresso verrà disattivato)

2 = PROTEZIONE CARICO - il carico verrà spento, il

display visualizzerà il codice “iA” lampeggian-
te, il buzzer verrà attivato e l’uscita di allarme
(solo EVK402) verrà accesa (fino a quando l’in-
gresso verrà disattivato)

3 = ATTIVAZIONE ENERGY SAVING - verrà attivata

la funzione Energy Saving (fino a quando l’in-
gresso verrà disattivato); si veda anche r4 (11)

se i5 = 1, ritardo segnalazione allarme ingresso
multifunzione
se i5 = 2, ritardo carico dalla disattivazione dell’in-
gresso multifunzione
RETE SERIALE (MODBUS)
indirizzo strumento
baud rate
0 = 2.400 baud
1 = 4.800 baud
2 = 9.600 baud
3 = 19.200 baud
parità
0 = nessuna parità
1 = dispari
2 = pari
RISERVATO
riservato
(1) l’unità di misura dipende dal parametro P2
(2) impostare opportunamente i parame-

tri relativi ai regolatori dopo la modi-
fica del parametro P2

(3) il valore dipende dal parametro P2 (150,0 °C

o 300 °F)

(4) il valore dipende dal codice dello strumento,

nel modo indicato (esempio per EVK421):

Il punto di domanda (?) sostituisce un
campo, l’asterisco (*) sostituisce uno
o più campi (o nessuno); il campo C si-
gnifica cooling (per freddo), il campo H signi-
fica heating (per caldo)

(5) se il parametro C1 è impostato a 0, il ritardo

dalla conclusione dell’errore sonda ambiente
sarà comunque di 2 min

(6) se il parametro r5 è impostato a 1 (funziona-

mento per caldo), le funzioni dello sbrinamento
non saranno abilitate

(7) lo strumento memorizza il conteggio dell’in-

tervallo di sbrinam. ogni 30 min; la modifica
del parametro d0 ha effetto dalla conclusione
del precedente intervallo di sbrinam. o dall’at-
tivazione di uno sbrinam. in modo manuale

(8) il display ripristina il normale funzionamento

quando, concluso lo sbrinamento, la tempe-
ratura dell’ambiente scende al di sotto di quel-
la che ha bloccato il display (o se si manifesta
un allarme di temperatura)

(9) il differenziale del parametro è di 2,0 °C/4 °F
(10) durante lo sbrinam. gli allarmi di temperatura

sono assenti, a condizione che questi si siano
manifestati dopo l’attivazione dello sbrinam.

(11) l’effetto non viene segnalato.

Campo di misura: da -50,0 a 150,0 °C per sonda PTC, da -40,0 a
105,0 °C per sonda NTC.
Risoluzione: 0,1 °C/1 °C/1 °F.
Uscite digitali EVK421: 1 relè:

• relè carico: 16 A res. @ 250 VCA, 5 FLA,

30 LRA (contatto in scambio).

Uscite digitali EVK402: 2 relè:

• relè carico: 16 A res. @ 250 VCA, 5 FLA,

30 LRA (contatto in scambio)

• relè allarme: 8 A res. @ 250 VCA,

2 FLA, 12 LRA (contatto in scambio).

La corrente massima consentita sui carichi è di 10 A.
Porta seriale: porta per la comunicazione con il sistema di supervisione
(attraverso un’interfaccia seriale, via TTL, con protocollo di comunicazio-
ne MODBUS) o con la chiave di programmazione; su richiesta.

CODICE
EVK421???C*

EVK421??
EVK421???
EVK421???H?*

VALORE
r5 = 0 (per freddo)

r5 = 1 (per caldo)
r5 = 1 (per caldo)
r5 = 1 (per caldo)

CODE
EVK421???C*

EVK421??
EVK421???
EVK421???H?*

VALUE
r5 = 0 (cooling)

r5 = 1 (heating)
r5 = 1 (heating)
r5 = 1 (heating)