EVCO EV9411J6 Manuale d'uso

Pagina 2

Advertising
background image

EVCO S.p.A.

This document belongs to Evco; unless you are authorized by Evco, you can not publish it.

Via Mezzaterra 6, 32036 Sedico Belluno ITALY

Evco does not take any responsibility about features, technical data and possible mistakes related in this document or coming by its use.

Phone +39-0437-852468 • Fax +39-0437-83648

Evco does not take any responsibility about damages coming by the non-observance of the additional information.

[email protected] • www.evco.it

Evco reserves the right to make any change without prior notice and at any time without prejudice the basic safety and operating features.

PT • 13/10

PARAM. MIN.

MAX. U.M.

DEF.

SERIAL NETWORK (MODBUS)

LA

1

247

- - -

247

instrument address

Lb

0

3

- - -

2

baud rate
0 = 2,400 baud
1 = 4,800 baud
2 = 9,600 baud
3 = 19,200 baud

LP

0

2

- - -

2

parity
0 = none
1 = odd
2 = even

PARAM. MIN.

MAX. U.M.

DEF.

ENABLING

E1

0

1

- - -

1

enabling the buzzer
1 = YES

(1)

the unit of measure depends on parameter P2

(2)

the minimum value, the maximum value and the default value of parameter P0 depend
on the kind of model (respectively 2, 3 and 2 in the model for J/K thermocouples and 4,
13 and 4 in the model for 2/3 wires Pt 100 and Ni 120 probes)

(3)

set the parameters related to the regulators appropriately after the
modification of the parameter P2

(4)

the value depends on the instrument code, as follows:

The question mark (?) replaces one field, the asterisk (*) replaces one or
more fields (or no-one); the field C means cooling, the field H means heating

(5)

if parameter C1 has value 0, the delay since the end of the room probe error will
however be 2 min.

RETE SERIALE (MODBUS)
indirizzo strumento
baud rate
0 = 2.400 baud
1 = 4.800 baud
2 = 9.600 baud
3 = 19.200 baud
parità
0 = nessuna parità
1 = dispari
2 = pari
VARIE
abilitazione del buzzer
1 = SI
(1) l’unità di misura dipende dal parametro P2
(2) il valore minimo, il valore massimo e il valore di

default del parametro P0 dipendono dal tipo
di modello (rispettivamente 2, 3 e 2 per il mo-
dello per termocoppie J/K e 4, 13 e 4 per il
modello per sonde Pt 100 e Ni 120 2/3 fili)

(3) impostare opportunamente i parame-

tri relativi ai regolatori dopo la modi-
fica del parametro P2

(4) il valore dipende dal codice dello strumento,

nel modo indicato:

Il punto di domanda (?) sostituisce un
campo, l’asterisco (*) sostituisce uno
o più campi (o nessuno); il campo C si-
gnifica cooling (per freddo), il campo H signi-
fica heating (per caldo)

(5) se il parametro C1 è impostato a 0, il ritardo

dalla conclusione dell’errore sonda camera sarà
comunque di 2 min.

GB

ENGLISH

9

WORKING SETPOINTS AND CONFIGURATION PARAMETERS

9.1

Working setpoints
MIN.

MAX.

U.M.

DEF.

WORKING SETPOINT

r1

r2

°C/°F (1) 0.0

working setpoint

9.2

Configuration parameters

PARAM. MIN.

MAX.

U.M.

DEF.

WORKING SETPOINT

SP

r1

r2

°C/°F (1) 0.0

working setpoint

PARAM. MIN.

MAX.

U.M.

DEF.

WORKING SETPOINT

SP

r1

r2

°C/°F (1) 0.0

working setpoint

PARAM. MIN.

MAX.

U.M.

DEF.

MEASURE INPUTS

CA1

-25

25.0

°C/°F (1) 0.0

room probe offset

P0

(2)

(2)

- - -

(2)

kind of probe
2 = J (only visible in the model for J/K thermocou-

ples)

3 = K (only visible in the model for J/K thermocou-

ples)

4 = 3 wires Pt 100 (only visible in the model for

2/3 wires Pt 100 and Ni 120 probes)

5 = 2 wires Pt 100 (only visible in the model for

2/3 wires Pt 100 and Ni 120 probes)

12 = 3 wires Ni 120 (only visible in the model for

2/3 wires Pt 100 and Ni 120 probes)

13 = 2 wires Ni 120 (only visible in the model for

2/3 wires Pt 100 and Ni 120 probes)

P1

0

1

- - -

1

decimal point Celsius degree (only visible in the
model for 2/3 wires Pt 100 and Ni 120 probes)
1 = YES

P2

0

1

- - -

0

unit of measure temperature (3)
0 = °C
1 = °F

P5

0

2

- - -

0

quantity to show by the upper part of the display
during the normal operation
0 = room temperature
1 = working setpoint
2 = the display will be out

P6

0

2

- - -

1

quantity to show by the lower part of the display
during the normal operation
0 = room temperature
1 = working setpoint
2 = the display will be out

PARAM. MIN.

MAX.

U.M.

DEF.

REGULATOR

r0

0.1

99.0

°C/°F (1) 2.0

working setpoint differential

r1

-99

r2

°C/°F (1) 0.0

minimum working setpoint

r2

r1

999

°C/°F (1) 350

maximum working setpoint

r3

0

1

- - -

0

locking the working setpoint modification (with the
procedure related in paragraph 4.1)
1 = YES

r5

0

1

- - -

(4)

cooling or heating action
0 = cooling

PARAM. MIN.

MAX.

U.M.

DEF.

LOAD PROTECTIONS

C1

0

240

min

0

minimum time between two activations in succes-
sion of the load; also load delay since the end of
the room probe error (5)

C2

0

240

min

0

minimum time the load remains turned off; also
load delay since you turn on the instrument

C3

0

240

s

0

minimum time the load remains turned on

C4

0

240

min

10

time the load remains turned off during the room
probe error; also look at C5

C5

0

240

min

0

time the load remains turned on during the room
probe error; also look at C4

PARAM. MIN.

MAX.

U.M.

DEF.

TEMPERATURE ALARMS

A0

0.1

999

°C/°F (1) 2.0

differential of parameters A1 and A5

A1

-99

999

°C/°F (1) 0.0

temperature the first temperature alarm is activated;
also look at A0 and A3

A2

0

240

min

0

first temperature alarm delay

A3

0

4

- - -

0

kind of first temperature alarm
0 = alarm not enabled
1 = absolute lower alarm (or A1)
2 = absolute upper alarm (or A1)
3 = lower alarm relative to the first working setpoint

(or "first working setpoint - A1”; consider A1
without sign)

4 = upper alarm relative to the first working

setpoint (or "first working setpoint + A1”; con-
sider A1 without sign)

A4

0

240

min

0

temperature alarms delay since an independent
working setpoint modification

A5

-99

999

°C/°F (1) 0.0

temperature the second temperature alarm is acti-
vated; also look at A0 and A7

A6

0

240

min

0

second temperature alarm delay

A7

0

4

- - -

0

kind of second temperature alarm
0 = alarm not enabled
1 = absolute lower alarm (or A5)
2 = absolute upper alarm (or A5)
3 = lower alarm relative to the second working

setpoint (or "second working setpoint - A5”;
consider A5 without sign)

4 = upper alarm relative to the second working

setpoint (or "second working setpoint + A5”;
consider A5 without sign)

I

ITALIANO

9

SETPOINT DI LAVORO E PARA-
METRI DI CONFIGURAZIONE

9.1

Setpoint di lavoro

SETPOINT DI LAVORO
setpoint di lavoro
9.2

Parametri di configurazione

SETPOINT DI LAVORO
setpoint di lavoro
SETPOINT DI LAVORO
setpoint di lavoro
INGRESSI DI MISURA
offset sonda camera
tipo di sonda
2 = J (visibile solo nel modello per termocoppie

J/K)

3 = K (visibile solo nel modello per termocoppie

J/K)

4 = Pt 100 3 fili (visibile solo nel modello per sonde

Pt 100 e Ni 120 2/3 fili)

5 = Pt 100 2 fili (visibile solo nel modello per sonde

Pt 100 e Ni 120 2/3 fili)

12 = Ni 120 3 fili (visibile solo nel modello per sonde

Pt 100 e Ni 120 2/3 fili)

13 = Ni 120 2 fili (visibile solo nel modello per sonde

Pt 100 e Ni 120 2/3 fili)

punto decimale grado Celsius (visibile solo nel mo-
dello per sonde Pt 100 e Ni 120 2/3 fili)
1 = SI
unità di misura temperatura (3)
0 = °C
1 = °F
grandezza visualizzata dalla parte alta del display
durante il normale funzionamento
0 = temperatura della camera
1 = setpoint di lavoro
2 = il display sarà spento
grandezza visualizzata dalla parte bassa del display
durante il normale funzionamento
0 = temperatura della camera
1 = setpoint di lavoro
2 = il display sarà spento
REGOLATORE
differenziale del setpoint di lavoro
minimo setpoint di lavoro
massimo setpoint di lavoro
blocco della modifica del setpoint di lavoro (con la
procedura indicata nel paragrafo 4.1)
1 = SI
funzionamento per freddo o per caldo
0 = per freddo
PROTEZIONI DEL CARICO
tempo minimo tra due accensioni consecutive del
carico; anche ritardo carico dalla conclusione del-
l’errore sonda camera (5)
durata minima dello spegnimento del carico; an-
che ritardo carico dall’accensione dello strumento
durata minima dell’accensione del carico
durata dello spegnimento del carico durante l’erro-
re sonda camera; si veda anche C5
durata dell’accensione del carico durante l’errore
sonda camera; si veda anche C4
ALLARMI DI TEMPERATURA
differenziale dei parametri A1 e A5
temperatura alla quale viene attivato il primo allar-
me di temperatura; si vedano anche A0 e A3
ritardo primo allarme di temperatura
tipo di primo allarme di temperatura
0 = allarme assente
1 = di minima assoluto (ovvero A1)
2 = di massima assoluto (ovvero A1)
3 = di minima relativo al setpoint di lavoro (ovvero

“setpoint di lavoro - A1”; considerare A1 senza
segno)

4 = di massima relativo al setpoint di lavoro (ovvero

“setpoint di lavoro + A1”; considerare A1 senza
segno)

ritardo allarmi di temperatura dalla modifica del
setpoint di lavoro
temperatura alla quale viene attivato il secondo al-
larme di temperatura; si vedano anche A0 e A7
ritardo secondo allarme di temperatura
tipo di secondo allarme di temperatura
0 = allarme assente
1 = di minima assoluto (ovvero A5)
2 = di massima assoluto (ovvero A5)
3 = di minima relativo al setpoint di lavoro (ovvero

“setpoint di lavoro - A5”; considerare A5 senza
segno)

4 = di massima relativo al setpoint di lavoro (ovvero

“setpoint di lavoro + A5”; considerare A5 senza
segno)

CODE
EV9411???C*

EV9411??
EV9411???
EV9411???H?*

VALUE
r5 = 0 (for cooling)

r5 = 1 (for heating)
r5 = 1 (for heating)
r5 = 1 (for heating)

CODICE
EV9411???C*

EV9411??
EV9411???
EV9411???H?*

VALORE
r5 = 0 (per freddo)

r5 = 1 (per caldo)
r5 = 1 (per caldo)
r5 = 1 (per caldo)

Advertising
Questo manuale è associato alle seguenti prodotti: