EVCO EVKB91N7 Manuale d'uso

Pagina 2

Advertising
background image

EVCO S.p.A.

This document belongs to Evco; unless you are authorized by Evco, you can not publish it.

Via Mezzaterra 6, 32036 Sedico Belluno ITALY

Evco does not take any responsibility about features, technical data and possible mistakes related in this document or coming by its use.

Phone +39-0437-852468 • Fax +39-0437-83648

Evco does not take any responsibility about damages coming by the non-observance of the additional information.

[email protected] • www.evco.it

Evco reserves the right to make any change without prior notice and at any time without prejudice the basic safety and operating features.

PT • 18/11

GB ENGLISH

9

WORKING SETPOINTS AND CONFIGURATION PARAMETERS

9.1

Working setpoints

MIN.

MAX.

U.M.

DEF.

WORKING SETPOINTS

r1

r2

°C/°F (1) 50

working setpoint

9.2

Configuration parameters

PARAM. MIN.

MAX.

U.M.

DEF.

WORKING SETPOINTS

SP

r1

r2

°C/°F (1) 50

working setpoint

PARAM. MIN.

MAX.

U.M.

DEF.

MEASURE INPUTS

o1

-25

25

°C/°F (1) 0.0

DHW tank probe offset

P1

0

1

- - -

1

decimal point (for the quantity to show during the
normal operation, between -9.9 and 19.9 °C)
1 = YES

P2

0

1

- - -

0

unit of measure temperature (2)
0 = °C
1 = °F

PARAM. MIN.

MAX.

U.M.

DEF.

MAIN REGULATOR

r0

0.1

15.0

°C/°F (1) 2.0

working setpoint differential

r1

0.0

r2

°C/°F (1) 20

minimum working setpoint

r2

r1

199

°C/°F (1) 70

maximum working setpoint

r6

SP

199

°C/°F (1) 65

working setpoint during function “antilegionella”;
also look at r7 and r8

r7

0

r8

min

5

duratation of function “antilegionella” (3)

r8

r7

199

min

20

maximum duratation of function “antilegionella” (4)

PARAM. MIN.

MAX.

U.M.

DEF.

HEATER PROTECTIONS

C0

0

199

min

0

heater delay since you turn on the instrument

C2

0

199

min

0

minimum time the heater remains turned off

C3

0

199

s

0

minimum time the heater remains turned on

PARAM. MIN.

MAX.

U.M.

DEF.

TEMPERATURE ALARMS

A1

0.0

199

°C/°F (1) 40

temperature below which the lower temperature
alarm is activated (relative to the working setpoint
or "working setpoint - A1”) (5)
0.0 = alarm not enabled

A4

0.0

199

°C/°F (1) 20

temperature above which the upper temperature
alarm is activated (relative to the working setpoint
or "working setpoint + A4”) (5)
0.0 = alarm not enabled

A6

0

199

min

15

temperature alarm delay since you turn on the in-
strument

A7

0

199

min

15

temperature alarm delay

PARAM. MIN.

MAX.

U.M.

DEF.

DIGITAL INPUTS

i1

0

1

- - -

0

kind of contact multipurpose input
0 = NO (the input will be active if you close the

contact)

1 = NC (the input will be active if you open the

contact)

i5

0

5

- - -

3

effect provoked by the activation of the multipur-
pose input
0 = no effect
1 = ACTIVATION EXTERNAL ALARM - spent the time

i7 the display will show the code “iA” flashing
(as long as the input will be deactivated)

2 = ACTIVATION MANOSTAT - spent the time i7 the

heater will be turned off (as long as the input
will be deactivated)

3 = ACTIVATION MANOSTAT - the heater will be

turned off (as long as the input will be deacti-
vated) and spent the time i7 the display will
show the code “iA” flashing (as long as the
input will be deactivated)

4 = ACTIVATION MANOSTAT - the display will show

the code “iA” flashing (as long as the input will
be deactivated) and spent the time i7 the heater
will be turned off (as long as the input will be
deactivated)

5 = ACTIVATION MANOSTAT - spent the time i7 the

heater will be turned off and the display will
show the code “iA” flashing (as long as the
input will be deactivated)

i7

0

199

s

0

delay effect multipurpose input activation

(1)

the unit of measure depends on parameter P2

(2)

set the parameters related to the regulators appropriately after the
modification of the parameter P2

(3)

the count of the time you have set with the parameter is started when the ACS tank
temperature rises above the temperature r6 for the first time since the activation of
function “antilegionella”; the function is succesfully completed when the DHW tank
temperature will on the whole be remained above the temperature r6 for the time you
have set with the parameter

(4)

the count of the time you have set with the parameter is started to the activation of
function “antilegionella”

(5)

the differential of the parameter is 2.0 °C/4 °F.

I ITALIANO

9

SETPOINT DI LAVORO E PARA-
METRI DI CONFIGURAZIONE

9.1

Setpoint di lavoro

SETPOINT DI LAVORO
setpoint di lavoro
9.2

Parametri di configurazione

SETPOINT DI LAVORO
setpoint di lavoro
INGRESSI DI MISURA
offset sonda serbatoio ACS
punto decimale (per la grandezza visualizzata du-
rante il normale funzionamento, tra -9,9 e 19,9 °C)
1 = SI
unità di misura temperatura (2)
0 = °C
1 = °F
REGOLATORE PRINCIPALE
differenziale del setpoint di lavoro
minimo setpoint di lavoro
massimo setpoint di lavoro
setpoint di lavoro durante la funzione antilegionella;
si vedano anche r7 e r8
durata della funzione “antilegionella” (3)
durata massima della funzione “antilegionella” (4)
PROTEZIONI DEL RISCALDATORE
ritardo riscaldatore dall’accensione dello strumento
durata minima dello spegnimento del riscaldatore
durata minima dell’accensione del riscaldatore
ALLARMI DI TEMPERATURA
temperatura al di sotto della quale viene attivato
l’allarme di temperatura di minima (relativo al
setpoint di lavoro ovvero “setpoint di lavoro - A1”)
(5)
0.0 = allarme assente
temperatura al di sopra della quale viene attivato
l’allarme di temperatura di massima (relativo al
setpoint di lavoro ovvero “setpoint di lavoro + A4”)
(5)
0.0 = allarme assente
ritardo allarme di temperatura dall’accensione dello
strumento
ritardo allarme di temperatura
INGRESSI DIGITALI
tipo di contatto dell’ingresso multifunzione
0 = NA (ingresso attivo con contatto chiuso)
1 = NC (ingresso attivo con contatto aperto)

effetto provocato dall'attivazione dell’ingresso
multifunzione
0 = nessun effetto
1 = ATTIVAZIONE ALLARME ESTERNO - trascorso il

tempo i7 il display visualizzerà il codice “iA” lam-
peggiante (fino a quando l’ingresso verrà
disattivato)

2 = INTERVENTO PRESSOSTATO - trascorso il tem-

po i7 il riscaldatore verrà spento (fino a quando
l’ingresso verrà disattivato)

3 = INTERVENTO PRESSOSTATO - il riscaldatore ver-

rà spento (fino a quando l’ingresso verrà
disattivato) e trascorso il tempo i7 il display
visualizzerà il codice “iA” lampeggiante (fino a
quando l’ingresso verrà disattivato)

4 = INTERVENTO PRESSOSTATO - il display

visualizzerà il codice “iA” lampeggiante (fino a
quando l’ingresso verrà disattivato) e trascorso
il tempo i7 il riscaldatore verrà spento (fino a
quando l’ingresso verrà disattivato)

5 = INTERVENTO PRESSOSTATO - trascorso il tem-

po i7 il riscaldatore verrà spento e il display
visualizzerà il codice “iA” lampeggiante (fino a
quando l’ingresso verrà disattivato)

ritardo effetto attivazione dell’ingresso multifunzione
(1) l’unità di misura dipende dal parametro P2
(2) impostare opportunamente i parame-

tri relativi ai regolatori dopo la modi-
fica del parametro P2

(3) il conteggio del tempo stabilito con il parame-

tro viene avviato quando la temperatura del
serbatoio ACS sale al di sopra della temperatu-
ra r6 per la prima volta dall’attivazione della
funzione “antilegionella”; la funzione viene
completata con successo quando la tempera-
tura del serbatoio ACS sarà rimasta al di sopra
della temperatura r6 complessivamente per il
tempo stabilito con il parametro

(4) il conteggio del tempo stabilito con il parame-

tro viene avviato all’attivazione della funzione
“antilegionella”

(5) il differenziale del parametro è di 2,0 °C/4 °F.