EVCO EPU2LXP1CP Manuale d'uso

Pagina 116

Advertising
background image

Evco S.p.A.

c-pro 3 micro HPRU | Manuale utente ver. 2.0 | Codice 144CP3UHI204

pagina 116 di 120

0x07B7

1976 PG03_ModCmp_Model

0

0

6

R/W

0x07B8

1977 PG04_EnInverter

0

0

1

R/W

0x07B9

1978 PM94_TaraturaTsuction

0.0

-20.0

20.0

R/W

0x07BA

1979 PV26_StandByPosition

0.00

0.00

100.00

R/W

0x07BB

1980 PV27_AlarmPosition

0.00

0.00

100.00

R/W

0x07BC

1981 PV28_PID_SH_Filter

10

1

255

R/W

0x07BD

1982 PV29_PID_FastActionLevel

100

1

100

R/W

0x07BE

1983 PV30_PID_FastActionThreshold

-1.0

-18.0

0.0

R/W

0x07BF

1984 PV31_PID_DeadZoneHi

1.0

0.0

45.0

R/W

0x07C0

1985 PV32_PID_SmartBandThreshold

3.0

0.0

45.0

R/W

0x07C1

1986 PV33_DaysToResync

1

0

255

R/W

0x07C2

1987 PV34_LP_setpoint

0.00

0.00

290.00

R/W

0x07C3

1988 PV70_LoSH_hysteresis

0.5

0.0

45.0

R/W

0x07C4

1989 PV71_LoSH_delay

3

0

255

R/W

0x07C5

1990 PV72_HiSH_hysteresis

1.0

0.0

45.0

R/W

0x07C6

1991 PV73_HiSH_delay

3

0

255

R/W

0x07C7

1992 PV74_LP_hysteresis

0.30

0.20

1.00

R/W

0x07C8

1993 PV75_LP_delay

3

0

255

R/W

0x07C9

1994 PV76_MOP_hysteresis

1.0

0.0

18.0

R/W

0x07CA

1995 PV77_MOP_delay

3

0

255

R/W

0x07CB

1996 PV78_MOP_Band

8.0

0.0

45.0

R/W

0x07CC

1997 PV79_MOP_Filter

15

0

255

R/W

0x07CD

1998 PV80_MOP_maxDSH

7.0

0.0

45.0

R/W

0x07CE

1999 PV81_MOP_Bypass

10

0

255

R/W

0x07CF

2000 PV82_LOP_hysteresis

1.0

0.0

18.0

R/W

0x07D0

2001 PV83_LOP_delay

3

0

255

R/W

0x07D1

2002 PV90_ValveType

1

0

4

R/W

0x07D2

2003 PV91_GenericValve_MinSteps

0

0

4900

R/W

0x07D3

2004 PV92_GenericValve_MaxSteps

1000

0

4900

R/W

0x07D4

2005 PV93_GenericValve_OvrSteps

1500

0

4900

R/W

0x07D5

2006 PV94_GenericValve_StepRate

100

25

1000

R/W

0x07D6

2007 PV95_GenericValve_DrivingMode

2

0

2

R/W

0x07D7

2008 PV96_GenericValve_DutyCycleForce

100

50

100

R/W


Advertising