EVCO EPU2LXP1CH Installer manual Manuale d'uso

Pagina 105

Advertising
background image

EVCO S.p.A.

c-pro 3 micro CHIL | Application manual ver. 1.0 | Codice 144CP3CHE104

page105 of122

Fan_C1

condensazione Circuito # 1

0x0663

1636

PM64_ForzaturaInv
Fan_C2

0

0

1

PM64 - Funzionamento manuale ventilatore di
condensazione Circuito # 2

R/W

0x0664

1637

PM65_EnManuFan_
FC

0

0

1

R/W

0x0665

1638

PM66_ForceFanAO_
FC

0.00

0.00

100.00

R/W

0x0666

1639

PM67_ForseFanDO_
FC

0

0

1

R/W

0x0667

1640

PM71_Calib_TExter
n

0.0

-18.0

18.0

R/W

0x0668

1641

PM72_Calib_TIn_FC

0.0

-18.0

18.0

R/W

0x0669

1642

PM73_Calib_TIn

0.0

-18.0

18.0

R/W

0x066A

1643

PM74_Calib_TOut_C
1

0.0

-18.0

18.0

R/W

0x066B

1644

PM75_Calib_TOut_C
2

0.0

-18.0

18.0

R/W

0x066C

1645

PM76_Calib_TOutSo
rg_C1

0.0

-18.0

18.0

R/W

0x066D

1646

PM77_Calib_TOutSo
rg_C2

0.0

-18.0

18.0

R/W

0x066E

1647

PM78_Calib_TCoil_C
1

0.0

-18.0

18.0

R/W

0x066F

1648

PM79_Calib_TCoil_C
2

0.0

-18.0

18.0

R/W

0x0670

1649

PM80_Calib_TGas_
C1

0.0

-18.0

18.0

R/W

0x0671

1650

PM81_Calib_TGas_
C2

0.0

-18.0

18.0

R/W

0x0672

1651

PM82_Calib_TAux

0.0

-18.0

18.0

R/W

0x0673

1652

PM83_Calib_PCond_
C1

0.0

-290.0

290.0

R/W

0x0674

1653

PM84_Calib_PCond_
C2

0.0

-290.0

290.0

R/W

0x0675

1654

PM85_Calib_PEvap_
C1

0.0

-290.0

290.0

R/W

0x0676

1655

PM86_Calib_PEvap_
C2

0.0

-290.0

290.0

R/W

0x0677

1656

PM87_Calib_PUniqu
e_C1

0.0

-290.0

290.0

R/W

0x0678

1657

PM88_Calib_PUniqu
e_C2

0.0

-290.0

290.0

R/W

0x0679

1658

PC01_Cmp_Rotatio
n_Type

0

0

3

PC01 –Rotazione compressore
0=FIFO,
1=LIFO,
2=FIFO+Hr,
3=LIFO+Hr

R/W

0x067A

1659

PC02_Compressors
Mode

0

0

1

PC02

–Modalità

compressori

(circuito

doppio)

0=bilanciamento, 1=saturazione

R/W

0x067B

1660

PC04_Cmp_TminOn

20

0

999

PC04 –Tempo in min per compressore ON

R/W

0x067C

1661

PC05_Cmp_TminOff

120

0

999

PC05 - Tempo in min per compressore OFF

R/W

0x067D

1662

PC06_Cmp_TonOn

360

0

999

PC06 –Tempo in min tra 2 avvii dello stesso comp

R/W

Advertising