WORKING SETPOINTS AND CONFIGURATION PARAMETERS

8.1 Working setpoints

MIN.

MAX.

U.M.

DEF.

WORKING SETPOINTS

r1

r2

°C/°F (1) 0.0

working setpoint

8.2 Configuration parameters
PARAM. MIN.

MAX.

U.M.

DEF.

WORKING SETPOINTS

SP

r1

r2

°C/°F (1) 0.0

working setpoint

PARAM. MIN.

MAX.

U.M.

DEF.

MEASURE INPUTS

CA1

-25.0

25.0

°C/°F (1) 0.0

cabinet probe offset

CA2

-25.0

25.0

°C/°F (1) 0.0

evaporator probe offset

CA3

-25.0

25.0

°C/°F (1) 0.0

condenser probe offset (only EVK253)

P0

0

1

- - -

1

kind of probe
0 = PTC
1 = NTC

P1

0

1

- - -

1

decimal point Celsius degree (for the quantity to show during the normal operation)
1 = YES

P2

0

1

- - -

0

unit of measure temperature (2)
0 = °C
1 = °F

P3

0

2

- - -

1

evaporator probe function
0 = probe not enabled
1 = defrost probe and thermostat probe for the evaporator fan
2 = thermostat probe for the evaporator fan

P4

0

1

- - -

1

enabling the condenser probe (only EVK253)
1 = YES

P5

0

4

- - -

0

quantity to show during the normal operation
0 = cabinet temperature
1 = working setpoint
2 = evaporator temperature
3 = “cabinet temperature - evaporator temperature”
4 = condenser temperature (only EVK253, not visible otherwise)

PARAM. MIN.

MAX.

U.M.

DEF.

MAIN REGULATOR

r0

0.1

15.0

°C/°F (1) 2.0

working setpoint differential

r1

-99.0

r2

°C/°F (1) -50.0

minimum working setpoint

r2

r1

99.0

°C/°F (1) 50.0

maximum working setpoint

r3

0

1

- - -

0

locking the working setpoint modification (with the procedure related in paragraph 3.1)
1 = YES

r4

0.0

99.0

°C/°F (1) 0.0

temperature increase during function Energy Saving (only EVK213, EVK223 and EVK233); also look at i5

PARAM. MIN.

MAX.

U.M.

DEF.

COMPRESSOR PROTECTIONS

C0

0

240

min

0

compressor delay since you turn on the instrument

C1

0

240

min

5

minimum time between two activations in succession of the compressor; also compressor delay since
the end of the cabinet probe error (3)

C2

0

240

min

3

minimum time the compressor remains turned off

C3

0

240

s

0

minimum time the compressor remains turned on

C4

0

240

min

10

time the compressor remains turned off during the cabinet probe error; also look at C5

C5

0

240

min

10

time the compressor remains turned on during the cabinet probe error; also look at C4

C6

0.0

199.0 °C/°F (1) 80.0

condenser temperature above which the overheated condenser alarm is activated (only EVK253) (4)

C7

0.0

199.0 °C/°F (1) 90.0

condenser temperature above which the compressor locked alarm is activated (only EVK253)

C8

0

15

min

1

compressor locked alarm delay (only EVK253) (5)

PARAM. MIN.

MAX.

U.M.

DEF.

DEFROST

d0

0

99

h

8

defrost interval; also look at d8 (6)
0 = the defrost at intervals will never be activated

d1

0

1

- - -

0

kind of defrost
0 = electric defrost
1 = hot gas defrost

d2

-99.0

99.0

°C/°F (1) 2.0

defrost cutoff temperature (only if P3 = 1)

d3

0

99

min

30

defrost duration if P3 = 0 or 2; defrost maximum duration if P3 = 1
0 = the defrost will never be activated

d4

0

1

- - -

0

defrost when you turn on the instrument
1 = YES

d5

0

99

min

0

defrost delay when you turn on the instrument (only if d4 = 1); also look at i5

d6

0

1

- - -

1

temperature shown during the defrost
0 = cabinet temperature
1 = if to the defrost activation the cabinet temperature is below “working setpoint + r0”, at most “work-

ing setpoint + r0”; if to the defrost activation the cabinet temperature is above “working setpoint +
r0”, at most the cabinet temperature to the defrost activation (7)

d7

0

15

min

2

dripping duration

d8

0

2

- - -

0

kind of defrost interval
0 = the defrost will be activated when the instrument will have remained turned on the time d0
1 = the defrost will be activated when the compressor will have remained turned on the time d0
2 = the defrost will be activated when the evaporator temperature will have remained below the tem-

perature d9 the time d0 (8)

d9

-99.0

99.0

°C/°F (1) 0.0

evaporator temperature above which the count of the defrost interval is suspended (only if d8 = 2)

dA

0

99

min

0

minimum time the compressor must be remained turned on (to the defrost activation) in order that the
defrost can be activated (only if d1 = 1) (9)

PARAM. MIN.

MAX.

U.M.

DEF.

TEMPERATURE ALARMS

A0

0

2

- - -

0

temperature joined to the lower temperature alarm
0 = cabinet temperature
1 = evaporator temperature (10)
2 = condenser temperature (only EVK253, not visible otherwise) (11)

A1

-99.0

99.0

°C/°F (1) -10.0

temperature below which the lower temperature alarm is activated; also look at A0 and A2 (4)

A2

0

2

- - -

1

kind of lower temperature alarm
0 = alarm not enabled
1 = relative to the working setpoint (or "working setpoint - A1”; consider A1 without sign)
2 = absolute (or A1)

A3

0

1

- - -

0

temperature joined to the upper temperature alarm (only EVK253, not visible = 0 otherwise)
0 = cabinet temperature
1 = condenser temperature (11)

A4

-99.0

99.0

°C/°F (1) 10.0

temperature above which the upper temperature alarm is activated; also look at A3 and A5 (4)

A5

0

2

- - -

1

kind of upper temperature alarm
0 = alarm not enabled
1 = relative to the working setpoint (or "working setpoint + A4”; consider A4 without sign)
2 = absolute (or A4)

A6

0

240

min

120

upper temperature alarm delay since you turn on the instrument (only if A3 = 0)

A7

0

240

min

15

temperature alarm delay

A8

0

240

min

15

upper temperature alarm delay since the end of the after dripping evaporator fan delay (only if A3 = 0)
(12)

A9

0

240

min

15

upper temperature alarm delay since the deactivation of the door switch input (only EVK213, EVK223
and EVK233) (13)

PARAM. MIN.

MAX. U.M.

DEF.

EVAPORATOR FAN

F0

0

4

- - -

1

evaporator fan activity during the normal operation
0 = turned off
1 = turned on
2 = according to the compressor
3 = according to F1 (14)
4 = turned off if the compressor is turned off, according to F1 if the compressor is turned on (14)

F1

-99.0

99.0

°C/°F (1) -1.0

evaporator temperature above which the evaporator fan is turned off (only if F0 = 3 or 4) (4)

F2

0

2

- - -

0

evaporator fan activity during the defrost and the dripping
0 = turned off
1 = turned on
2 = according to F0

F3

0

15

min

2

duration of the after dripping evaporator fan delay

PARAM. MIN.

MAX. U.M.

DEF.

DIGITAL INPUTS (only EVK213, EVK223 and EVK233)

i0

0

3

- - -

2

kind of digital input
0 = MULTIPURPOSE INPUT - in this case look at parameters i1, i5, i7, i8 and i9
1 = RESERVED
2 = DOOR SWITCH INPUT - in this case look at parameters i1, i2 and i3; the activation of the input will

turn off the evaporator fan (at most the time i3 or as long as the input will be deactivated)

3 = DOOR SWITCH INPUT - in this case look at parameters i1, i2 and i3; the activation of the input will

turn off the compressor and the evaporator fan (at most the time i3 or as long as the input will be
deactivated) (15)

i1

0

2

- - -

0

kind of contact digital input
0 = NO (the input will be active if you close the contact)
1 = NC (the input will be active if you open the contact)
2 = input not enabled

i2

-1

120

min

30

delay to signal the door switch input alarm
-1 = no signal

i3

-1

120

min

15

maximum duration of the effect provoked by the activation of the door switch input
-1 = the effect will last as long as the input will be deactivated

i5

0

6

- - -

3

effect provoked by the activation of the multipurpose input
0 = no effect
1 = SYNCHRONIZING THE DEFROSTS - spent the time d5 the defrost will be activated (16)
2 = ACTIVATING THE ENERGY SAVING - function Energy Saving will be activated (as long as the input

will be deactivated); also look at r4 (16)

3 = ACTIVATING THE EXTERNAL ALARM - spent the time i7 the display will show the code “iA” flashing

and the buzzer will be activated (as long as the input will be deactivated)

4 = ACTIVATING THE MANOSTAT - the compressor will be turned off, the display will show the code “iA”

flashing and the buzzer will be activated (as long as the input will be deactivated); also look at i7, i8
and i9

5 = TURNING OFF THE INSTRUMENT - the instrument will be turned off via software (as long as the

input will be deactivated); also look at C0, d4 and A6

6 = ACTIVATION COOLING (only EVK213 and EVK223) - the compressor will be turned on (as long as

the input will be deactivated); in this case parameters C4 and C5 are not meaningful (16)

i7

0

120

min

0

if i5 = 3, delay to signal the multipurpose input alarm
if i5 = 4, compressor delay since the deactivation of the multipurpose input (17)

i8

0

15

- - -

0

number of multipurpose input alarms such as to provoke the instrument locked alarm (only if i5 = 4)
0 = alarm not enabled

i9

1

999

min

240

time without multipurpose input alarms in order that the alarm counter is cleared (only if i5 = 4)

PARAM. MIN.

MAX. U.M.

DEF.

SERIAL NETWORK (MODBUS)

LA

1

247

- - -

247

instrument address

Lb

0

3

- - -

2

baud rate
0 = 2,400 baud
1 = 4,800 baud
2 = 9,600 baud
3 = 19,200 baud

LP

0

2

- - -

2

parity
0 = none
1 = odd
2 = even

PARAM. MIN.

MAX. U.M.

DEF.

RESERVED

E9

0

1

- - -

1

reserved

(1)

the unit of measure depends on parameter P2

(2)

set the parameters related to the regulators appropriately after the modification of the parameter P2

(3)

if parameter C1 has value 0, the delay since the end of the cabinet probe error will however be 2 min

(4)

the differential of the parameter is 2.0 °C/4 °F

(5)

if (when you turn on the instrument) the condenser temperature is above the one you have set with parameter C7, parameter C8 will have
no effect

(6)

the instrument stores the count of the defrost interval every 30 min; the modification of parameter d0 has effect since the end of the previous
defrost interval or since the activation of a defrost by hand

(7)

the display restores the normal operation as soon as the after dripping evaporator fan delay ends and the cabinet temperature falls below
the one that has locked the display (or if a temperature alarm arises)

(8)

if parameter P3 has value 0 or 2, the instrument will work as if parameter d8 had value 0

(9)

if (to the defrost activation) the duration of the activation of the compressor is shorter than the time you have set with parameter dA, the
compressor will further remain turned on the fraction of time required to complete it

(10)

if parameter P3 has value 0, the instrument will work as if parameter A0 had value 0

(11)

if parameter P4 has value 0, the instrument will work as if parameter had value 0

(12)

during the defrost, the dripping and the evaporator fan delay the temperature alarms are not enabled, on condition that they have arisen
after the activation of the defrost

(13)

during the activation of the door switch input the upper temperature alarm is not enabled, on condition that it has arisen after the activation
of the input

(14)

if parameter P3 has value 0, the instrument will work as if parameter F0 had value 2

(15)

the compressor is turned off spent 10 s since the activation of the input; if the input is activated during the defrost or the after dripping
evaporator fan delay, the activation will provoke no effect on the compressor

(16)

the effect is not signalled

(17)

make sure the time you have set with parameter i7 is shorter than the one you have set with parameter i9.

The instrument must be disposed according to the local legislation about the collection for electrical and electronic equipment.