Evco S.p.A. • Code 104KB23A01

EVKB23 and EVKB33

Simple digital thermostats for ventilated refrigerating units

version 1.01

GB ENGLISH

1

GETTING STARTED

1.1 Important
Read these instructions carefully before installing and using the instru-
ment and follow all additional information for installation and electrical
connection; keep these instructions close to the instrument for future
consultations.

The instrument must be disposed according to the local
legislation about the collection for electrical and electronic
equipment.

1.2 Installing the instrument
Panel mounting, with click brackets (supplied by the builder); dimen-
sions in mm (in).

DIMENS.

MINIMUM

TYPICAL

MAXIMUM

A

71.0 (2.795)

71.0 (2.795)

71.8 (2.826)

B

29.0 (1.141)

29.0 (1.141)

29.8 (1.173)

Additional information for installation:
• 59.0 (2.322) is the maximum depth with screw terminal blocks
• 81.5 (3.208) is the maximum depth with extractable terminal blocks
• the panel thickness must not be higher than 8.0 mm (0.314 in)
• working conditions (working temperature, humidity, etc.) must be be-

tween the limits indicated in the technical data

• do not install the instrument close to heating sources (heaters, hot air

ducts, etc.), devices provided with big magnetos (big speakers, etc.),
locations subject to direct sunlight, rain, humidity, dust, mechanical
vibrations or bumps

• according to the safety legislation, the protection against electrical

parts must be ensured by a correct installation of the instrument; the
parts that ensure the protection must be installed so that you can not
remove them if not by using a tool.

1.3 Wiring diagram
With reference to the wiring diagrams: the serial port (by request) is the
port for the communication with the programming key.

Models with power supply 230 VAC and 115 VAC.
Modelli con alimentazione 230 VCA e 115 VCA.

Models with power supply 12 VAC/DC.
Modelli con alimentazione 12 VCA/CC.

Models with power supply 230 VAC and 115 VAC.
Modelli con alimentazione 230 VCA e 115 VCA.

Models with power supply 12 VAC/DC.
Modelli con alimentazione 12 VCA/CC.
Additional information for electrical connection:
• do not operate on the terminal blocks with electrical or pneumatic

screwers

• if the instrument has been moved from a cold location to a warm one,

the humidity could condense on the inside; wait about an hour be-
fore supplying it

• test the working power supply voltage, working electrical frequency

and working electrical power of the instrument; they must correspond
with the local power supply

• disconnect the local power supply before servicing the instrument
• do not use the instrument as safety device
• for repairs and information on the instrument please contact Evco

sales network.

2

USER INTERFACE

2.1 Preliminary information
There are the following operation status:
• status “on” (the instrument is supplied and is turned on: the regulators

can be turned on)

• status “stand-by” (the instrument is supplied but it is turned off via

software: the regulators are turned off)

• status “off” (the instrument is not supplied).
“Turning on” means moving from status stand-by to status on; “turning
off” means moving from status on to status stand-by.
After an interruption of power supply the instrument moves to the sta-
tus it was before the interruption.
2.2 Turning on/off the instrument
• make sure the keyboard is not locked and no procedure is running
• press

4 s.

2.3 The display
If the instrument is turned on, during the normal operation the display
will show the cabinet temperature.
If the instrument is turned off, the display will be switched off.
2.4 Showing the evaporator temperature
• make sure the keyboard is not locked and no procedure is running
• press

2 s: the display will show “P2”

• press
To quit the procedure:
• press

or do not operate 60 s

• press

or

as long as the display shows the cabinet
temperature or do not operate 60 s.

If the evaporator probe is not enabled (parameter P3 = 0), the label
“P2” will not be shown.
2.5 Activating the defrost by hand
• make sure the keyboard is not locked and no procedure is running
• press

4 s.

If the function of the evaporator probe is the one of defrost probe (pa-
rameter P3 = 1) and to the defrost activation the evaporator tempera-
ture is above the one you have set with parameter d2, the defrost will
not be activated.
2.6 Locking/unlocking the keyboard
To lock the keyboard:
• make sure no procedure is running
• press

and

1 s: the display will show “Lo” 1 s.

If the keyboard is locked, you will not be allowed to:
• turn on/off the instrument through button
• show the evaporator temperature
• activate the defrost by hand
• modify the working setpoint with the procedure related in paragraph

3.1 (you also can modify the working setpoint through parameter SP).

These operations provoke the visualization of the label “Lo” 1 s.
To unlock the keyboard:
• press

and

1 s: the display will show “Un” 1 s.

3

SETTINGS

3.1 Setting the working setpoint
• make sure the keyboard is not locked and no procedure is running
• press

: LED will flash

• press

or

in 15 s; also look at parameters r1 and r2

• press

or do not operate 15 s.

You also can modify the working setpoint through parameter SP.
3.2 Setting configuration parameters
To gain access the procedure (for the models without access password):
• make sure the keyboard is not locked and no procedure is running
• press

and

4 s: the display will show “SP”.

To gain access the procedure (for the models with access password):
• make sure no procedure is running
• press

and

4 s: the display will show “PA”

• press
• press

or

in 15 s to set “-19”

• press

or do not operate 15 s

• press

and

4 s: the display will show “SP”.

To select a parameter:
• press

or

To modify a parameter:
• press
• press

or

in 15

• press

or do not operate 15 s.

To quit the procedure:
• press

and

4 s or do not operate 60 s.

Switch off/on the power supply of the instrument after the
modification of the parameters.
4

SIGNALS

4.1 Signals

LED

MEANING
LED compressor
if it is lit, the compressor will be turned on
if it flashes:
• the modification of the working setpoint will be running
• a compressor protection will be running (parameters C0

and C2)

LED defrost
if it is lit, the defrost will be running
if it flashes:
• the defrost will be required but a compressor protection

will be running (parameters C0 and C2)

• the dripping will be running (parameter d7)
• the heating of the freezing fluid will be running (param-

eter dA)

LED evaporator fan
if it is lit, the evaporator fan will be turned on
if it flashes, the after dripping evaporator fan delay will be
running (parameter F3)
LED alarm
if it is lit, an alarm or an error will be running

°

C

LED Celsius degree
if it is lit, the unit of measure of the temperatures will be
Celsius degree (parameter P2)

°

F

LED Fahrenheit degree
if it is lit, the unit of measure of the temperatures will be
Fahrenheit degree (parameter P2)

CODE MEANING

Lo

the keyboard is locked; look at paragraph 2.6

5

ALARMS

5.1 Alarms

CODE MEANING

AL

Lower temperature alarm
Remedies:
• check the cabinet temperature
• look at parameter A1
Effects:
• no effect

AH

Upper temperature alarm
Remedies:
• check the cabinet temperature
• look at parameter A4
Effects:
• no effect

iA

Multipurpose input alarm (only if parameter i5 has value 1
or 2)
Remedies:
• check the reasons that have provoked the activation of

the input

• look at parameters i1 and i5
Effects:
• if parameter i5 has value 1, there will be no effect
• if parameter i5 has value 2, the compressor will be turned

off

id

Door switch input alarm (only if parameter i5 has value 3 or
4)
Remedies:
• check the reasons that have provoked the activation of

the input

• look at parameters i1 and i5
Effects:
• if parameter i5 has value 3, the compressor and the evapo-

rator fan will be turned off

• if parameter i5 has value 4, the evaporator fan will be turned

off

When the cause that has provoked the alarm disappears, the instru-
ment restores the normal operation.
6

INTERNAL DIAGNOSTICS

6.1 Internal diagnostics

CODE MEANING

P1

Cabinet probe error
Remedies:
• check the kind of probe
• check the integrity of the probe
• check the connection instrument-probe
• check the cabinet temperature
Effects:
• in EVKB23 the compressor will be turned on cyclically,

10 min turned on and 10 min turned off; in EVKB33 the
compressor will be turned on

P2

Evaporator probe error
Remedies:
• the same you saw in the previous case but related to the

evaporator probe

Effects:
• if parameter P3 has value 1, the defrost will last the time

you will have set with parameter d3

• if parameter F0 has value 1 or 2, the instrument will work

as if the parameter had value 0

When the cause that has provoked the alarm disappears, the instru-
ment restores the normal operation.
7

TECHNICAL DATA

7.1 Technical data
Box: self-extinguishing grey.
Frontal protection: IP 65.
Connections (use copper conductors only): screw terminal blocks
(power supply, inputs and outputs), 6 poles connector (serial port; by
request); extractable terminal blocks (power supply, inputs and outputs)
by request.
Working temperature: from 0 to 55 °C (32 to 131 °F, 10 ... 90% of
relative humidity without condensate).
Power supply: 230 VAC, 50/60 Hz, 3 VA (approximate); 115 VAC or
12 VAC/DC by request.
Insulation class: 2.
Measure inputs: 2 (cabinet probe and evaporator probe) for
PTC or NTC probes (according to the model).
Digital inputs: 1 (multipurpose/door switch) for NO/NC contact (free
of voltage, 5 V 1 mA).
Working range: from -50 to 150 °C (-50 to 199 °F) for PTC probe,
from -40 to 105 °C (-40 to 199 °F) for NTC probe.
Resolution: 0.1 °C (between -19.9 and 19.9 °C)/1 °C/1 °F.
Digital outputs: 3 relays:

• compressor relay: 30 res. A @ 250 VAC,

12 FLA, 72 LRA in EVKB33; 16 res. A @ 250 VAC,
5 FLA, 30 LRA in EVKB23 with power supply
12 VAC/DC; 8 res. A @ 250 VAC, 2 FLA, 12 LRA
otherwise (NO contact)

• defrost relay: 8 res. A @ 250 VAC, 2 FLA,

12 LRA (NO contact in EVKB33 with power supply
12 VAC/DC; change-over contact otherwise)

• evaporator fan relay: 8 res. A @ 250 VAC,

2 FLA, 12 LRA in EVKB23 with power supply
12 VAC/DC; 5 res. A @ 250 VAC otherwise (NO
contact).

The maximum current allowed on the loads is 10 A.
Serial port: port for the communication with the programming key;
by request.

I ITALIANO

1

PREPARATIVI

1.1 Importante
Leggere attentamente queste istruzioni prima dell’installazione e prima
dell’uso e seguire tutte le avvertenze per l’installazione e per il collega-
mento elettrico; conservare queste istruzioni con lo strumento per con-
sultazioni future.

Lo strumento deve essere smaltito secondo le normative
locali in merito alla raccolta delle apparecchiature elettriche
ed elettroniche.

1.2 Installazione
A pannello, con le staffe a scatto in dotazione (si vedano i disegni del
paragrafo 1.2 della sezione in Inglese).
Avvertenze per l’installazione:
• 59,0 è la profondità massima con morsettiere a vite
• 81,5 è la profondità massima con morsettiere estraibili
• lo spessore del pannello non deve essere superiore a 8,0 mm

• accertarsi che le condizioni di lavoro (temperatura di impiego, umidi-

tà, ecc.) rientrino nei limiti indicati nei dati tecnici

• non installare lo strumento in prossimità di fonti di calore (resistenze,

condotti dell’aria calda, ecc.), di apparecchi con forti magneti (grossi
diffusori, ecc.), di luoghi soggetti alla luce solare diretta, pioggia, umi-
dità, polvere eccessiva, vibrazioni meccaniche o scosse

• in conformità alle normative sulla sicurezza, la protezione contro even-

tuali contatti con le parti elettriche deve essere assicurata mediante
una corretta installazione dello strumento; tutte le parti che assicura-
no la protezione devono essere fissate in modo tale da non poter
essere rimosse senza l’aiuto di un utensile.

1.3 Collegamento elettrico
Si vedano i disegni del paragrafo 1.3 della sezione in Inglese.
Con riferimento agli schemi elettrici: la porta seriale (su richiesta) è la
porta per la comunicazione con la chiave di programmazione.
Avvertenze per il collegamento elettrico:
• non operare sulle morsettiere utilizzando avvitatori elettrici o pneuma-

tici

• se lo strumento è stato portato da un luogo freddo a uno caldo,

l’umidità potrebbe condensare all’interno; attendere circa un’ora pri-
ma di alimentarlo

• accertarsi che la tensione di alimentazione, la frequenza e la potenza

elettrica operativa dello strumento corrispondano a quelle dell’alimen-
tazione locale

• disconnettere l’alimentazione prima di procedere con qualunque tipo

di manutenzione

• non utilizzare lo strumento come dispositivo di sicurezza
• per le riparazioni e per informazioni riguardanti lo strumento rivolgersi

alla rete di vendita Evco.

2

INTERFACCIA UTENTE

2.1 Cenni preliminari
Esistono i seguenti stati di funzionamento:
• lo stato “on” (lo strumento è alimentato ed è acceso: i regolatori pos-

sono essere accesi)

• lo stato “stand-by” (lo strumento è alimentato ma è spento via software:

i regolatori sono spenti)

• lo stato “off” (lo strumento non è alimentato).
Con il termine “accensione” si intende il passaggio dallo stato stand-by
allo stato on; con il termine “spegnimento” si intende il passaggio dallo
stato on allo stato stand-by.
Dopo un’interruzione dell’alimentazione lo strumento passa allo stato in
cui si trovava prima dell’interruzione.
2.2 Accensione/spegnimento dello strumento
• assicurarsi che la tastiera non sia bloccata e che non sia in corso alcu-

na procedura

• premere

per 4 s.

2.3 Il display
Se lo strumento è acceso, durante il normale funzionamento il display
visualizzerà la temperatura della cella.
Se lo strumento è spento, il display sarà spento.
2.4 Visualizzazione della temperatura dell’evaporatore
• assicurarsi che la tastiera non sia bloccata e che non sia in corso alcu-

na procedura

• premere

per 2 s: il display visualizzerà “P2”

• premere
Per uscire dalla procedura:
• premere

o non operare per 60 s

• premere

o

fino a quando il display visualizza la temperatura
della cella o non operare per 60 s.

Se la sonda evaporatore è assente (parametro P3 = 0), la label “P2” non
verrà visualizzata.
2.5 Attivazione dello sbrinamento in modo manuale
• assicurarsi che la tastiera non sia bloccata e che non sia in corso alcu-

na procedura

• premere

per 4 s.

Se la funzione della sonda evaporatore è quella di sonda di sbrinamento
(parametro P3 = 1) e all’attivazione dello sbrinamento la temperatura
dell’evaporatore è al di sopra di quella stabilita con il parametro d2, lo
sbrinamento non verrà attivato.
2.6 Blocco/sblocco della tastiera
Per bloccare la tastiera:
• assicurarsi che non sia in corso alcuna procedura
• premere

e

per 1 s: il display visualizzerà “Lo” per 1 s.

Se la tastiera è bloccata, non sarà consentito:
• accendere/spegnere lo strumento attraverso il tasto
• visualizzare la temperatura dell’evaporatore
• attivare lo sbrinamento in modo manuale
• modificare il setpoint di lavoro con la procedura indicata nel paragrafo

3.1 (il setpoint di lavoro è impostabile anche attraverso il parametro
SP).

Queste operazioni provocano la visualizzazione della label “Lo” per 1 s.
Per sbloccare la tastiera:
• premere

e

per 1 s: il display visualizzerà “Un” per 1 s.

3

IMPOSTAZIONI

3.1 Impostazione del setpoint di lavoro
• assicurarsi che la tastiera non sia bloccata e che non sia in corso alcu-

na procedura

• premere

: il LED lampeggerà

• premere

o

entro 15 s; si vedano anche i parametri r1 e r2

• premere

o non operare per 15 s.

È inoltre possibile impostare il setpoint di lavoro attraverso il param. SP.

3.2 Impostazione dei parametri di configurazione
Per accedere alla procedura (per i modelli senza password di accesso):
• assicurarsi che la tastiera non sia bloccata e che non sia in corso alcu-

na procedura

• premere

e

per 4 s: il display visualizzerà “SP”.

Per accedere alla procedura (per i modelli con password di accesso):
• assicurarsi che non sia in corso alcuna procedura
• premere

e

per 4 s: il display visualizzerà “PA”

• premere
• premere

o

entro 15 s per impostare “-19”

• premere

o non operare per 15 s

• premere

e

per 4 s: il display visualizzerà “SP”.

Per selezionare un parametro:
• premere

o

Per modificare un parametro:
• premere
• premere

o

entro 15 s

• premere

o non operare per 15 s.

Per uscire dalla procedura:
• premere

e

per 4 s o non operare per 60 s.

Interrompere l'alimentazione dello strumento dopo la mo-
difica dei parametri.
4

SEGNALAZIONI

4.1 Segnalazioni

LED

SIGNIFICATO
LED compressore
se è acceso, il compressore sarà acceso
se lampeggia:
• sarà in corso la modifica del setpoint di lavoro
• sarà in corso una protezione del compressore (parametri

C0 e C2)

LED sbrinamento
se è acceso, sarà in corso lo sbrinamento
se lampeggia:
• sarà richiesto lo sbrinamento ma sarà in corso una prote-

zione del compressore (parametri C0 e C2)

• sarà in corso il gocciolamento (parametro d7)
• sarà in corso il risc. del fluido refrigerante (parametro dA)
LED ventilatore dell’evaporatore
se è acceso, il ventilatore dell’evaporatore sarà acceso
se lampeggia, sarà in corso il fermo ventilatore
dell’evaporatore (parametro F3)
LED allarme
se è acceso, sarà in corso un allarme o un errore

°

C

LED grado Celsius
se è acceso, l’unità di misura delle temperature sarà il grado
Celsius (parametro P2)

°

F

LED grado Fahrenheit
se è acceso, l’unità di misura delle temperature sarà il grado
Fahrenheit (parametro P2)

CODICE SIGNIFICATO

Lo

la tastiera è bloccata; si veda il paragrafo 2.6

5

ALLARMI

5.1 Allarmi

CODICE SIGNIFICATO

AL

Allarme di temperatura di minima
Rimedi:
• verificare la temperatura della cella
• si veda il parametro A1
Conseguenze:
• lo strumento continuerà a funzionare regolarmente

AH

Allarme di temperatura di massima
Rimedi:
• verificare la temperatura della cella
• si veda il parametro A4
Conseguenze:
• lo strumento continuerà a funzionare regolarmente

iA

Allarme ingresso multifunzione (solo se il parametro i5 è im-
postato a 1 o 2)
Rimedi:
• verificare le cause che hanno provocato l’attivazione del-

l’ingresso

• si vedano i parametri i1 e i5
Conseguenze:
• se il parametro i5 è impostato a 1, lo strumento continue-

rà a funzionare regolarmente

• se il parametro i5 è impostato a 2, il compressore verrà

spento

id

Allarme ingresso micro porta (solo se il parametro i5 è impo-
stato a 3 o 4)
Rimedi:
• verificare le cause che hanno provocato l’attivazione del-

l’ingresso

• si vedano i parametri i1 e i5
Conseguenze:
• se il parametro i5 è impostato a 3, il compressore e il ven-

tilatore dell’evaporatore verranno spenti

• se il parametro i5 è impostato a 4, il ventilatore

dell’evaporatore verrà spento

Quando la causa che ha provocato l’allarme scompare, lo strumento
ripristina il normale funzionamento.