Power 3001, Host, Line interactive ups – Atlantis Land HostPower 3001 Manuale d'uso

Pagina 2: Specifi che tecniche

Advertising
background image

Host

Power 3001

Line Interactive UPS

Server UPS S3000. Potenza 3000 VA (1800W). Tecnologia Line Interactive ad onda sinusoidale con stabilizzazione di tensione. Filtri di protezione di linea

telefonica o LAN . Batterie tipo “long-life”. Autonomia 15 minuti al 50% del carico . Batterie “HotSwap” sostituibili dall’utente. Display LCD con stati di fun-
zionalità e parametri elettrici. Software di shutdown automatico e diagnostica del server per Windows 95/98/2000 Linux e UNIX..

Specifi che Tecniche

Power

3000VA / 1800W

Input

Voltage Single Phase; 220/230/240V selectable

by DIP Switch (±25% )

HZ 50Hz/60Hz ±5%

Output

Voltage(AC) Increase 15% (Input:-9% to

-25%); Decrease 15% (Input:+9% to +25%)

Voltage(INV) Inverter mode:±3%

Waveform(INV) Pure Sine-Wave with THD 3%

at linear load

Hz(INV) Inverter mode: 50Hz or 60Hz ± 0.1Hz

Transfer

Line/Battery Nearly Zero Transfer (<6ms typi-

cal)

Battery

Half-load runtime 9 min

Capacity 12V/9Ah

Quantity 4

Recharge Time 2-4 Hours to 90%

Type Sealed Maintenance Free Lead Acid VRLA

Type

Protection

Over/under Volt. Switch to Battery Output

whrn the Utility over regulation range

Overload(AC/INV) >110% Buzzer continuosly

alarms and shuts down after 10 minutes

Short Circuit(AC/INV) Input Fuse & Electronic

Circuit / Electronic Circuit

Low Battery Two stages, no battery drain after

cut-off

EMI/RFI Full time suppression

Surge Protection Meet with IEEE 587 cat. A&B

Standard

Modem/Network RJ11 / RJ45

Energy Rating 960 Joules instantaneous

response

Attenuation Better than 45dB @1Mhz for Nor-

mal/Common mode

Noise Filtering EN50991-1

Connections

Output 4*IEC(Battery Power Supply) +

1*Schuko

Computer RS232(DB9) and USB

Display And Diagnostics

With LCD and LED Display

LCD Display

Status: Normal, AC Input High, AC Input Low,

On Battery, Battery Low, Battery Bad, Over-
load, Fault, Phase error, Ground Fault

Data: Utility Voltage, Ouput Voltage, Output

Hz, Load%, UPS Temperature, Battery Voltage,
Runtime Timer

LED Display

Green=Normal, Amber=Warning, Red=Critical

LCD shows detalis in respect to the lighting

indication of LED

Beeping Alarm

Overload, Fault, High Temperature, Battery On,

Battery Low, Battery Bad, Over/Under Voltage,
Frequency Error

Advanced Mode

Self-diagnostic; Direct Time-based readout of

battery remained runtime

Communication Port

USB/DB9 port with TRUE RS232 serial signal

plus dry contact signals

Environmental Condition

0-40°C; 0-95% Non Condensing Humidity

Safety Approval

CE/UL

Dimension (W*H*D cm)

17*24*47

Weight (N.W/ G.W) Kg

26

Codice Ean

80269740062360

All rights registered
Microsoft and Windows are registered trademarks of Micro-
soft Corporation
All trade names and marks are registered trademarks of re-
spective companies
Specifi cations are subjected to change without prior notice.
No liability for technical errors and/or omissions.