40

13.3 Electric panel

13.3 Electric panel

13.3 Electric panel

13.3 Electric panel troubleshooting table

troubleshooting table

troubleshooting table

troubleshooting table

All maintenance and repair operations must be performed by qualified
personnel.
Before servicing the set, disconnect the power supply and make sure there is no
pressure in the hydraulic components.

Problem

Problem

Problem

Problem

Cause

Cause

Cause

Cause

Solution

Solution

Solution

Solution

1. No mains power supply

Power the unit

2. Blown fuse inside panel

Replace fuse

The panels do not
switch on

3. Overload protection

triggered (only for jockey
pump panels)

Rearm the protection

1. No mains power supply

Power the unit

2. Key-operated selector switch

set to “0”

Set key-operated selector switch
to “AUTO” or “MAN”

3. Blown fuse

Replace the fuse

The main electric
pump does not
start

4. Incorrect pressure switch

calibration

Recalibrate the pressure switch

1. No mains power supply

Power the unit

2. Blown fuse

Replace the fuse

3. Overload protection

triggered

Rearm the protection

4. Faulty pressure switch

Replace the pressure switch

5. Pressure switch not

connected

Connect the pressure switch

6. Incorrect pressure switch

calibration

Recalibrate the pressure switch

7. Tank liquid level is too low

Fill the primary water supply tank
or adjust the sensitivity of the
sensors

8. Electric sensors not

connected

Connect the electric sensors

The electric jockey
pump does not
start

9. No jumper between

terminals 3-4

Insert the jumper

1. Faulty pressure switch

Replace the pressure switch

2. Incorrect pressure switch

calibration

Recalibrate the pressure switch

The jockey pump
does not stop

3. Faulty electronic control

board

Replace the electronic board or
calibrate the timers

1. Pump running pressure

switch faulty

Replace the pressure switch

Pump – motor coupling

damaged

Replace the coupling and realign
the pump – motor

Self-test failed

2. Faulty electric motor

Replace the motor

Advertising