74

11 Appendice

VEGAPULS 61 • Protocollo Modbus e LevelMaster

41361-IT

-121116

Request:

Parametri

Length

Code/Data

Function Code

1 Byte

0x2B

MEI Type

1 Byte

0x0E

Read Device ID Code

1 Byte

0x01 to 0x04

Object ID

1 Byte

0x00 to 0xFF

Response:

Parametri

Length

Code/Data

Function Code

1 Byte

0x2B

MEI Type

1 Byte

0x0E

Read Device ID Code

1 Byte

0x01 to 0x04

Confirmity Level

1 Byte

0x01, 0x02, 0x03, 0x81, 0x82, 0x83

More follows

1 Byte

00/FF

Next Object ID

1 Byte

Object ID number

Number of Objects

1 Byte

List of Object ID

1 Byte

List of Object length

1 Byte

List of Object value

1 Byte

Depending on the Object ID

11.5 Comandi LevelMaster

Il VEGAPULS 61 è idoneo anche ad essere collegato ai seguenti RTU con protocollo LevelMaster.

Questo protocollo viene spesso designato come "Protocollo Siemens" o "Protocollo serbatoio".

RTU

Protocol

ABB Totalflow

Levelmaster

Kimray DACC 2000/3000

Levelmaster

Thermo Electron Autopilot

Levelmaster

Parametri per la comunicazione bus

Nel VEGAPULS 61 sono preimpostati valori di default:

Parametri

Configurable Values

Default Value

Baud Rate

1200, 2400, 4800, 9600, 19200

9600

Start Bits

1

1

Data Bits

7, 8

8

Parity

None, Odd, Even

None

Stop Bits

1, 2

1

Address range Levelmaster

32

32

I comandi LevelMaster si basano sulla seguente sintassi:

Le lettere maiuscole si trovano all'inizio di determinati campi di dati

Le lettere minuscole designano campi di dati

Tutti i comandi vengono conclusi con "<cr>" (carriage return)