5 comandi levelmaster, Fc43 sub 14, read device identification, Parametri per la comunicazione bus – VEGA VEGAFLEX 86 Modbus and Levelmaster protocol Manuale d'uso

Pagina 90

Advertising
background image

90

11 Appendice

VEGAFLEX 86 • Protocollo Modbus e LevelMaster

41848-IT

-130416

Response:

Parametri

Length

Code/Data

Function Code

1 Byte

0x11

Byte Number

1 Byte

Slave ID

1 Byte

Run Indicator Status

1 Byte

FC43 Sub 14, Read Device Identification

Con questo codice di funzione può essere richiesta la Device Identification.
Request:

Parametri

Length

Code/Data

Function Code

1 Byte

0x2B

MEI Type

1 Byte

0x0E

Read Device ID Code

1 Byte

0x01 to 0x04

Object ID

1 Byte

0x00 to 0xFF

Response:

Parametri

Length

Code/Data

Function Code

1 Byte

0x2B

MEI Type

1 Byte

0x0E

Read Device ID Code

1 Byte

0x01 to 0x04

Confirmity Level

1 Byte

0x01, 0x02, 0x03, 0x81, 0x82, 0x83

More follows

1 Byte

00/FF

Next Object ID

1 Byte

Object ID number

Number of Objects

1 Byte

List of Object ID

1 Byte

List of Object length

1 Byte

List of Object value

1 Byte

Depending on the Object ID

11.5 Comandi LevelMaster

Il VEGAFLEX 86 è idoneo anche ad essere collegato ai seguenti RTU con protocollo LevelMaster.

Questo protocollo viene spesso designato come "Protocollo Siemens" o "Protocollo serbatoio".

RTU

Protocol

ABB Totalflow

Levelmaster

Kimray DACC 2000/3000

Levelmaster

Thermo Electron Autopilot

Levelmaster

Parametri per la comunicazione bus

Nel VEGAFLEX 86 sono preimpostati i valori di default:

Advertising