Set receive to transmit delay, Report number of floats, Report receive to transmit delay – VEGA VEGABAR 82 Modbus and Levelmaster protocol - Operating Instructions Manuale d'uso

Pagina 79

Advertising
background image

79

10 Appendice

VEGABAR 82 • Protocollo Modbus e LevelMaster

46294-IT

-131205

Response:

Parametro

Length

Code/Data

Set Baud Rate

11 characters ASCII

Esempio: U01B9600E71
Modificare l'apparecchio all'indirizzo 1 impostando il baud rate 9600, parità pari, 7 bit di dati, 1 bit di

stop

Set Receive to Transmit Delay

Request:

Parametro

Length

Code/Data

Set Receive to Transmit Delay

7 characters ASCII

UuuRmmm
mmm = milliseconds (50 up to 250),

default = 127 ms

Response:

Parametro

Length

Code/Data

Set Receive to Transmit Delay

6 characters ASCII

UuuROK

Report Number of Floats

Request:

Parametro

Length

Code/Data

Set Receive to Transmit Delay

4 characters ASCII

UuuF

Response:

Parametro

Length

Code/Data

Set Receive to Transmit Delay

5 characters ASCII

UuuFn
n = number of measurement values

(0, 1 or 2)

Report Receive to Transmit Delay

Request:

Parametro

Length

Code/Data

Report Receive to Transmit Delay

4 characters ASCII

UuuR

Response:

Parametro

Length

Code/Data

Report Receive to Transmit Delay

7 characters ASCII

UuuRmmm
mmm = milliseconds (50 up to 250),

default = 127 ms