Transmitter Function Blocks

Resource Block (RB)

1

Transducer Block (TB)

1

Standard Block (AI)

3

Execution Time

30 mS

Advanced Function Blocks

Discret Input (DI)

Yes

PID Control

Yes

Output Splitter (OS)

Yes

Signal Characterizer (SC)

Yes

Integrator

Yes

Input Selector (IS)

Yes

Arithmetic (AR)

Yes

Diagnostics

Standard

Yes

Advanced

Yes

Performance

No

Function Blocks Instantiable

No

General Information

LAS (Link Active Scheduler)

Yes

Master Capable

Yes

Number of VCRs (Virtual Communication Re-

lationships)

24

Blocchi funzionali

Transducer Block (TB)
Il blocco funzionale "Analog Input (AI)" raccoglie il valore di misura originario (Secondary Value 2),

esegue la taratura min./max. (Secondary Value 1), esegue una linearizzazione (Primary Value) e

mette a disposizione i valori sulla sua uscita per altri blocchi funzionali.

m(d)

%

Lin%

Primary

Value

Secondary

Value 2

Secondary

Value 1

TB

Sensor_Value

min/max

adjustment

Linearization

Figura 31: Rappresentazione schematica Transducer Block (TB)

Blocco funzionale Analog Input (AI)
Il blocco funzionale "Analog Input (AI)" raccoglie il valore di misura originario selezionato tramite un

Channel Number e lo mette a disposizione di altri blocchi funzionali sulla sua uscita.