ОБЩИЕ ТЕХНИЧЕСКИЕ ДАННЫЕ И ХАРАКТЕРИСТИКИ – ТЕПЛОВЫЕ НАСОСЫ IP

МОД.

TW

ТЕМПЕРАТУРА НАРУЖНОГО ВОЗДУХА (С°)

20

25

30

35

40

45

50

kWf

kWa

kWf

kWa

kWf

kWa

kWf

kWa

kWf

kWa

kWf

kWa

kWf

kWa

200.4

5 212 46.0 198 53.0 187 58.3 176 64.3 164 70.9 152 77.3 139 83.6
6 218 46.5 204 53.5 193 58.9 181 64.9 168 71.6 156 78.0 143 84.4
7 225 46.9 210 54.0 198 59.5 186

65.6

173 72.3 160 78.8 147 85.2

8 231 47.5 216 54.6 204 60.2 191 66.3 178 73.1 165 79.7 -

-

9 237 47.9 221 55.1 209 60.8 197 67.0 183 73.8 169 80.5 -

-

10 244 48.4 227 55.7 215 61.4 202 67.7 188 74.6 174 81.3 -

-

11 250 48.9 233 56.2 220 62.0 207 68.3 193 75.3 178 82.1 -

-

12 257 49.4 239 56.8 226 62.6 213 69.0 198 76.0 183 82.9 -

-

230.4

5 237 52.7 222 60.6 210 66.8 197 73.6 183 81.2 169 88.5 156 95.7
6 244 53.2 228 61.2 215 67.4 202 74.3 188 81.9 174 89.3 160 96.6
7 251 53.7 234 61.8 222 68.1 208

75.1

194 82.8 179 90.2 165 97.6

8 258 54.3 241 62.5 228 68.9 214 75.9 199 83.7 184 91.2 -

-

9 265 54.9 248 63.1 234 69.6 220 76.7 204 84.5 189 92.2 -

-

10 272 55.4 254 63.8 240 70.2 226 77.5 210 85.4 194 93.1 -

-

11 279 56.0 261 64.4 247 70.9 231 78.2 215 86.2 199 94.0 -

-

12 287 56.5 268 65.0 253 71.6 238 79.0 221 87.0 205 94.9 -

-

260.4

5 269 58.3 251 67.1 238 73.9 223 81.5 208 89.8 192 97.9 177 106
6 277 58.9 258 67.7 244 74.6 229 82.3 213 90.7 198 98.8 182 107
7 285 59.5 266 68.4 251 75.4 236

83.1

220 91.6 203 99.9 187 108

8 293 60.1 273 69.2 259 76.2 243 84.0 226 92.6 209 101.0 -

-

9 301 60.7 281 69.9 266 77.0 249 84.9 232 93.5 215 102.0 -

-

10 309 61.3 288 70.5 273 77.7 256 85.7 238 94.5 221 103.0 -

-

11 317 61.9 296 71.2 280 78.5 263 86.5 244 95.4 226 104.0 -

-

12 326 62.5 304 71.9 287 79.3 270 87.4 251 96.3 232 105.0 -

-

290.4

5 305 67.0 284 77.1 269 84.9 252 93.7 235 103.2 218 113 200 122
6 313 67.6 292 77.8 276 85.7 259 94.5 241 104.2 224 114 205 123
7 322 68.3 301 78.6 285 86.6 267

95.5

248 105 230 115 211 124

8 331 69.1 309 79.5 293 87.6 275 96.6 255 106 237 116 -

-

9 341 69.8 318 80.3 301 88.5 282 97.5 262 107 243 117 -

-

10 350 70.5 326 81.1 309 89.3 290 98.5 269 109 250 118 -

-

11 359 71.2 335 81.9 316 90.2 297 99.5 276 110 256 120 -

-

12 368 71.9 344 82.7 325 91.1 305 100.4 284 111 263 121 -

-

330.4

5 342 75.8 320 87.2 302 96.1 284 106 264 117 244 127 225 138
6 352 76.5 328 88.0 311 97.0 291 107 271 118 251 128 231 139
7 362 77.3 338 88.9 320 98.0 300

108

279 119 259 130 237 140

8 372 78.1 348 89.9 329 99.0 309 109 287 120 266 131 -

-

9 383 78.9 357 90.8 338 100.0 317 110 295 122 273 133 -

-

10 393 79.7 367 91.7 347 101.0 325 111 303 123 280 134 -

-

11 403 80.5 376 92.6 356 102.0 334 112 310 124 288 135 -

-

12 414 81.3 386 93.5 365 103.0 343 114 319 125 295 136 -

-

375.4

5 395 84.2 369 96.9 349 107 327 118 304 130 282 141 259 153
6 406 85.0 379 97.8 358 108 336 119 313 131 290 143 266 154
7 418

85.9 390 98.8 369 109 346

120

322 132 298 144 274 156

8 430 86.8 401 99.9 379 110 356 121 331 134 307 146 -

-

9 441 87.7 412 100.9 390 111 366 123 340 135 315 147 -

-

10 453 88.5 423 101.9 400 112 375 124 349 136 323 149 -

-

11 465 89.4 434 102.9 410 113 385 125 358 138 332 150 -

-

12 477 90.3 446 103.9 421 114 395 126 368 139 341 152 -

-

420.4

5 439 94.7 410 109 388 120 364 132 339 146 314 159 288 172
6 452 95.6 422 110 399 121 374 134 348 147 322 161 296 174
7 465 96.6 434 111 410 122 385

135

358 149 332 162 305 175

8 478 97.7 446 112 422 124 396 136 368 150 341 164 -

-

9 491 98.6 458 113 434 125 407 138 379 152 351 166 -

-

10 504 99.6 471 115 445 126 418 139 389 153 360 167 -

-

11 517

100.6 483 116 456 128 428 141 398 155 369 169 -

-

12 531

101.6 496 117 469 129 440 142 409 156 379 171 -

-

Стандартные характеристики в режиме охлаждения: аппараты версии AS с низким уровнем шумов

Tw= температура испарения С° (температура конденсации) kWf= охлаждающая способность (kW) kWa = Входная мощность компрессоров (kW)

Стандартные характеристики относятся к перепаду температуры воды на входе и выходе теплообменника 5°C , Также учитывался
коэффициент загрязнения 0.44 x 10

-4

м

2

K/Вт, Аппарат установлен на уровне моря

(Pb = 1013 мбар).

Advertising